Product data sheet
Characteristics
ATV71HC11N4
variable speed drive ATV71 - 110KW 150HP 480V - EMC filter
Product availability: Stock - Normally stocked in distribution facility
Price*: 12652.30 USD
Feb 6, 2015
Commercial Status
Commercialised
Range of product
Altivar 71
Product or component
type
Variable speed drive
Product specific
application
Complex, high-power machines
Component name
ATV71
Motor power kW
110 kW at 380...480 V 3 phases
Motor power hp
150 hp at 380...480 V 3 phases
Motor cable length
<= 200 m unshielded cable
<= 100 m shielded cable
[Us] rated supply
voltage
380...480 V (- 15...10 %)
Network number of
phases
3 phases
Line current
202 A for 380 V 3 phases 110 kW / 150 hp
163 A for 480 V 3 phases 110 kW / 150 hp
EMC filter
Integrated
Assembly style
With heat sink
Variant
Reinforced version
Apparent power
133 kVA at 380 V 3 phases 110 kW / 150 hp
Prospective line Isc
<= 35 kA, 3 phases
Nominal output current
215 A at 2.5 kHz 460 V 3 phases 110 kW / 150 hp
215 A at 2.5 kHz 380 V 3 phases 110 kW / 150 hp
Maximum transient
current
355 A for 2 s 3 phases 110 kW / 150 hp
323 A for 60 s 3 phases 110 kW / 150 hp
Speed drive output
frequency
0.1...500 Hz
Nominal switching
frequency
2.5 kHz
Switching frequency
2.5...8 kHz with derating factor
2.5...8 kHz adjustable
Asynchronous motor
control profile
ENA (Energy adaptation) system for unbalanced loads
Flux vector control (FVC) with sensor (current vector)
Sensorless flux vector control (SFVC) (voltage or current
vector)
Voltage/Frequency ratio (2 or 5 points)
Type of polarization
No impedance for Modbus
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. *Prices are indicative
Main
Complementary
Product destination
Asynchronous motors
Synchronous motors
Supply voltage limits
323...528 V
Supply frequency
50...60 Hz (- 5...5 %)
Network frequency limits
47.5...63 Hz
Speed range
1...50 for synchronous motor in open-loop mode, without speed feedback
1...1000 for asynchronous motor in closed-loop mode with encoder feedback
1...100 for asynchronous motor in open-loop mode, without speed feedback
Speed accuracy
+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation without speed feedback
+/- 0.01 % of nominal speed for 0.2 Tn to Tn torque variation in closed-loop mode with
encoder feedback
Torque accuracy
+/- 5 % in closed-loop mode with encoder feedback
+/- 15 % in open-loop mode, without speed feedback
Transient overtorque
220 % of nominal motor torque +/- 10 % for 2 s
170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes
Braking torque
30 % without braking resistor
< 150 % with braking or hoist resistor
Synchronous motor control profile
Vector control without speed feedback
Regulation loop
Adjustable PI regulator
Motor slip compensation
Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio (2 or 5 points)
Suppressable
Local signalling
1 LED red presence of drive voltage
Output voltage
<= power supply voltage
Insulation
Electrical between power and control
Type of cable
Without mounting kit: 1-strand IEC cable at 113 F (45 C), copper 90 C XLPE/EPR
Without mounting kit: 1-strand IEC cable at 113 F (45 C), copper 70 C PVC
With an IP21 or an IP31 kit: 3-strand IEC cable at 104 F (40 C), copper 70 C PVC
With a NEMA Type1 kit: 3-strand UL 508 cable at 104 F (40 C), copper 75 C PVC
Electrical connection
PC/-, PO, PA/+ terminal 2 x 150 mm
PA, PB terminal 60 mm
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3 terminal 2 x 100 mm
AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR terminal 2.5 mm /
AWG 14
Tightening torque
PC/-, PO, PA/+ 362.83 lbf.in (41 N.m) / 360 lb.in
PA, PB 106.19 lbf.in (12 N.m) / 106 lb.in
L1/R, L2/S, L3/T, U/T1, V/T2, W/T3 212.39 lbf.in (24 N.m) / 212 lb.in
AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR 5.31 lbf.in (0.6 N.m)
Supply
Internal supply, 24 V DC, voltage limits 21...27 V, <= 200 mA for overload and shortcircuit protection
Internal supply for reference potentiometer (1 to 10 kOhm), 10.5 V DC +/- 5 %, <= 10
mA for overload and short-circuit protection
Analogue input number
Analogue input type
AI2 software-configurable voltage 0...10 V DC, input voltage 24 V max, impedance
30000 Ohm, resolution 11 bits
AI2 software-configurable current 0...20 mA, impedance 242 Ohm, resolution 11 bits
AI1-/Al1+ bipolar differential voltage +/- 10 V DC, input voltage 24 V max, resolution
11 bits + sign
Sampling duration
LI6 (if configured as logic input) 2 ms, +/- 0.5 ms for discrete input(s)
LI1...LI5 2 ms, +/- 0.5 ms for discrete input(s)
Al2 2 ms, +/- 0.5 ms for analog input(s)
AI1-/Al1+ 2 ms, +/- 0.5 ms for analog input(s)
Response time
R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)
R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s)
AO1 2 ms, tolerance +/- 0.5 ms for analog output(s)
<= 100 ms in STO (Safe Torque Off)
Accuracy
AO1 +/- 1 % for a temperature variation 60 C
AI2 +/- 0.6 % for a temperature variation 60 C
AI1-/Al1+ +/- 0.6 % for a temperature variation 60 C
Linearity error
AO1 +/- 0.2 %
AI1-/Al1+, AI2 +/- 0.15 % of maximum value
Analogue output number
Analogue output type
AO1 software-configurable voltage 0...10 V DC, impedance 470 Ohm, resolution 10
bits
AO1 software-configurable current 0...20 mA, impedance 500 Ohm, resolution 10 bits
AO1 software-configurable logic output 10 V <= 20 mA
Discrete output number
Discrete output type
R2A, R2B configurable relay logic NO, electrical durability 100000 cycles
R1A, R1B, R1C configurable relay logic NO/NC, electrical durability 100000 cycles
Minimum switching current
Configurable relay logic 3 mA at 24 V DC
Maximum switching current
R1, R2 on resistive load, 5 A at 30 V DC, cos phi = 1,
R1, R2 on resistive load, 5 A at 250 V AC, cos phi = 1,
R1, R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4,
R1, R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4,
Discrete input number
Discrete input type
PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d
LI6: switch-configurable PTC probe 0...6, impedance: 1500 Ohm
LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm
Discrete input logic
LI6 (if configured as logic input) positive logic (source), < 5 V (state 0), > 11 V (state 0)
LI6 (if configured as logic input) negative logic (sink), > 16 V (state 0), < 10 V (state 0)
LI1...LI5 positive logic (source), < 5 V (state 0), > 11 V (state 0)
LI1...LI5 negative logic (sink), > 16 V (state 0), < 10 V (state 0)
Acceleration and deceleration ramps
Automatic adaptation of ramp if braking capacity exceeded, by using resistor
Linear adjustable separately from 0.01 to 9000 s
S, U or customized
Braking to standstill
By DC injection
Protection type
Motor thermal protection
Motor power removal
Motor motor phase break
Drive thermal protection
Drive short-circuit between motor phases
Drive overvoltages on the DC bus
Drive overheating protection
Drive overcurrent between output phases and earth
Drive line supply undervoltage
Drive line supply overvoltage
Drive input phase breaks
Drive break on the control circuit
Drive against input phase loss
Drive against exceeding limit speed
Insulation resistance
> 1 mOhm at 500 V DC for 1 minute to earth
Frequency resolution
Display unit 0.1 Hz
Analog input 0.024/50 Hz
Communication port protocol
CANopen
Modbus
Type of connector
Male SUB-D 9 on RJ45 for CANopen
1 RJ45 for Modbus on terminal
1 RJ45 for Modbus on front face
Physical interface
2-wire RS 485 for Modbus
Transmission frame
RTU for Modbus
Transmission rate
9600 bps, 19200 bps for Modbus on front face
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
Data format
8 bits, odd even or no configurable parity for Modbus on terminal
8 bits, 1 stop, even parity for Modbus on front face
Number of addresses
1...247 for Modbus
1...127 for CANopen
Method of access
Slave for CANopen
Marking
CE
Operating position
Vertical +/- 10 degree
Height
40.24 in (1022 mm)
Depth
14.84 in (377 mm)
3
Width
14.17 in (360 mm)
Product weight
163.14 lb(US) (74 kg)
Option card
Profibus DP V1 communication card
Profibus DP communication card
Overhead crane card
Modbus/Uni-Telway communication card
Modbus TCP communication card
Modbus Plus communication card
Interface card for encoder
Interbus-S communication card
I/O extension card
Fipio communication card
Ethernet/IP communication card
DeviceNet communication card
Controller inside programmable card
CC-Link communication card
Environment
Noise level
69.5 dB conforming to 86/188/EEC
Dielectric strength
5092 V DC between control and power terminals
3535 V DC between earth and power terminals
Electromagnetic compatibility
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3 level 3
Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4
Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
1.2/50 s - 8/20 s surge immunity test conforming to IEC 61000-4-5 level 3
Standards
EN 55011 class A group 2
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C3
EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 60721-3-3 class 3C2
UL Type 1
Product certifications
CSA
C-Tick
GOST
NOM 117
UL
Pollution degree
3 conforming to UL 840
2 conforming to EN/IEC 61800-5-1
IP degree of protection
IP54 on lower part conforming to EN/IEC 61800-5-1
IP54 on lower part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP30 on the front panel conforming to EN/IEC 61800-5-1
IP30 on the front panel conforming to EN/IEC 60529
IP30 on side parts conforming to EN/IEC 61800-5-1
IP30 on side parts conforming to EN/IEC 60529
IP00 conforming to EN/IEC 61800-5-1
IP00 conforming to EN/IEC 60529
Vibration resistance
1.5 mm peak to peak (f = 3...10 Hz) conforming to EN/IEC 60068-2-6
0.6 gn (f = 10...200 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
7 gn for 11 ms conforming to EN/IEC 60068-2-27
Relative humidity
5...95 % without dripping water conforming to IEC 60068-2-3
5...95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation
14...122 F (-10...50 C) without derating
Ambient air temperature for storage
-13...158 F (-25...70 C)
Operating altitude
3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m
<= 3280.84 ft (1000 m) without derating
Ordering and shipping details
Category
22132 - ATV71 460V 25 THRU 100HP DRIVES
Discount Schedule
CP4C
GTIN
00785901446224
Nbr. of units in pkg.
Package weight(Lbs)
217.80
Product availability
Stock - Normally stocked in distribution facility
Returnability
Country of origin
CN
Offer Sustainability
Sustainable offer status
RoHS
REACh
Green Premium product
Compliant - since 1002 -
Schneider Electric declaration of conformity
Reference contains SVHC above the threshold -
Product environmental profile
Available
Download Product Environmental
Product end of life instructions
Available
Download End Of Life Manual
go to CaP for more details
Contractual warranty
Period
18 months