1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
KR11-10302-CLC-001
Input Data
1.1
Type of Panel
1.2
System
1.3
Rated Voltage
1.4
degree of Protection
1.5
Panel Max. Current Rating in Amp (Design)
1.6
Fault Current & Duration (KA RMS Symmetrical for 1 Sec.)
1.7
Ambient Temperature (Deg. C.)
1.8
Maximum Bus bar Temperature (Deg. C.)
1.9
Maximum Enclosure Temperature (Deg. C.)
1.10
Degree of Protection
Bus bar Size for Phase
Bus bar Size for Neutral
No. of Runs
:
:
:
No. of times Interleaved
:
:
:
1.12
Width of Bus Bar in mm
Thickness of Bus Bar in mm
Bus bar cross section for Neutral in Sq.mm
1.13
Cross section of Bus bar Selected in Sq. mm
1.14
Type of Insulator
1.15
Basic Insulation Level:
1.11
a
1.16
1.17
One Minute Power Frequency voltage
Painting:
a. Enclosure Interior & Exterior
b. Bus bar
Minimum Clearance:
Page 1 of 42
1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
KR11-10302-CLC-001
a. Phase to Phase
b. Phase to Earth
:
:
1.18
Applicable Standard
1.19
Degree of Protection
1.20
Span Between 2 support
Page 2 of 42
1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
2
2.1
KR11-10302-CLC-001
Bus duct Sizing Calculation for MCC
Short Time Thermal Withstand Capability of Bus bar
Minimum Cross Sectional Area of Busbar (A) In Sq. Inches
Isc = Short Circuit Symmetrical Fault Current in KA
T = Fault duration in Sec
T1 = Initial Temperature of Busbar in Deg.C
T2 = Final Temperature in Deg.C
A = Cross sectional area of busbar in Sq.inches
A in sq.mm = A x 645.16
2.2
Required cross sectional Area
2.2
Actual Cross section of Bus bar Selected (As per Clause1.13) in
Sq.mm
Conclusion:
2.3
3
3.10
The required cross section 650.226 Sq.mm is less than actual cross section 1250 Sq.mm of
chosen is safe for the envisaged system.
Bus bar Selection for Continuous Current Rating :
Bus bar Selected
Open air rating of bus bar for 50 Deg. C rise over ambient in
Amps.
No. of times Interleaved (As per Clause1.11)
Overall Rating of Bus Bar in Amps.
3.12
Phase spacing in mm.
3.13
Enclosed Size in (W x D x H ) mm
3.14
Bus bar Enclosed in (W x D ) mm
3.15
Design Ambient Temperature
3.16
Maximum allowable temp. rise
3.11
Page 3 of 42
1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
3.17
KR11-10302-CLC-001
Enclosure Material
Page 4 of 42
1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
3.18
3.19
KR11-10302-CLC-001
De-rating / Up rating:
a Ambient correction factor for 35 Deg. Rise
b Enclosure correction factor corresponding to bus bar
c Enclosure Correction factor Material (MS)
d Proximity Effect Factor
e Bus bar Configuration Factor
=
=
g Combined Correction Factor
De-rated Current rating of bus bar after applying Correction factor
in Amps.
=
=
3.20
Rating of Panel required (As per Clause 1.5)
Conclusion :
3.21
The de-rated Current rating 1238.51 amp of Panel selected is more than the required curren
the bus bar size chosen is safe for the envisaged system.
4
4.10
Support Insulator Span Calculation During Short Circuit
Fm = Peak Electromagnetic force along the centre line of busbar
without enclosure
Isc = Short Circuit Symmetrical Fault Current in KA
S = Phase spacing in Meter
K = Multiplying factor (s-a)/(a+b)
corresponding to a that is 60
Fm (Nm / cm )
Fm ( Kg / cm ) = (Fm x 0.1019716)
F = Force acting on top of the insulator
=
=
4.12
a
b
Where, H = Cantilever Height of insulator in mm
h = Distance between surface of insulator to centre of Bus bar in
mm
=
F
Page 5 of 42
1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
4.13
KR11-10302-CLC-001
Average span to be addopted in mm
=
=
SK = Cantilever strength of insulator(Kg/cm)
SF = Safety factor
Length of Span of insulator in mm
Adopted Span is
Conclusion:
4.4
Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe for th
Page 6 of 42
1000 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
5
5.1
KR11-10302-CLC-001
Temperature Rise Calculation
Where, I1=Calculated Rating in Amps (After deration) As
per Clause 3.19
5.2
I2 = Specified Rating in Amps as per clause 1.5
5.3
T1 = Max. Temp. Rise (in Deg.C) Specified
5.4
T2 = Temp. Rise in Deg. C to be calculated as
=
T2
=
=
Calculated Temperature is
Conclusion :
5.5
The Calculated Temperature rise of bus bar is 24.64 Deg. C, which is within the design Spe
System envisaged.
Prepared By: Ganpat C
Checked By : Kamlakar D.
Page 7 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cubical Type
3PH ,3 Wire / 4 Wire
415V
50 Hz.
1000
50
50
85
70
IP: 52 & IP: 42 for ACB Incomer
1 x 1 x 125 x 10 MM
1 x 125 x 06 MM
1
1
125
10
750
1250
SMC support with ribbed construction
2.5KV RMS
Epoxy paint RAL-7032, Siemens Grey
Heat Shrinkable Sleeved.
Page 8 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
25 mm
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
IP: 54 for Indoor & IP: 55 for Outdoor
0.5mtr. (500mm)
Page 9 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
of Bus bar
( Isc / T ) / {14 x 10 log [T1 +258)/(T2+258)] }
50
1
85
200
1.0078517941
650.226
650.226 Sq.mm for pure aluminium.
1250
is less than actual cross section 1250 Sq.mm of the bus bar selected. Hence, the bus bar size
nt Rating :
As per Clause1.11
1850
1 x 1850
1850
150
5500 x 800 x 2400 mm
800 x 400 mm
50 Deg. C
35 Deg. C
Page 10 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
MS Steel
Page 11 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
0.9
0.87
0.9
0.95
1
0.67
1850 x 0.67
1238.51025
1000
of Panel selected is more than the required current rating 1000 amp of Bus duct Bus bar. Hence,
aged system.
ring Short Circuit
K x 16 x Isc x 10 / S
50
0.250
0.904
0.4 (Reffering to curve K is 0.9)
14400.000
1468.391
Fm (H+h)/4H
38
75
1091.6328126316
Page 12 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cantilever Strength of insulator / safety factor x F
Sk / (SF x F )
1600
2.5
586.278
OK
ut span adopted is 500 mm, hence it is safe for the system envisaged.
Page 13 of 42
MCC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
1238.51025
1000
35
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )1.64
24.64
OK
r is 24.64 Deg. C, which is within the design Specified Temp. 35 Deg. C and it is safe for the
hecked By : Kamlakar D.
Approved By : A.B.H
Page 14 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
KR11-10302-CLC-001
Input Data
1.1
Type of Panel
1.2
System
1.3
Rated Voltage
1.4
degree of Protection
1.5
Panel Max. Current Rating in Amp (Design)
1.6
Fault Current & Duration (KA RMS Symmetrical for 1 Sec.)
1.7
Ambient Temperature (Deg. C.)
1.8
Maximum Bus bar Temperature (Deg. C.)
1.9
Maximum Enclosure Temperature (Deg. C.)
1.10
Degree of Protection
Bus bar Size for Phase
Bus bar Size for Neutral
No. of Runs
:
:
:
No. of times Interleaved
:
:
:
1.12
Width of Bus Bar in mm
Thickness of Bus Bar in mm
Bus bar cross section for Neutral in Sq.mm
1.13
Cross section of Bus bar Selected in Sq. mm
1.14
Type of Insulator
1.15
Basic Insulation Level:
1.11
a
1.16
1.17
One Minute Power Frequency voltage
Painting:
a. Enclosure Interior & Exterior
b. Bus bar
Minimum Clearance:
Page 15 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
KR11-10302-CLC-001
a. Phase to Phase
b. Phase to Earth
:
:
1.18
Applicable Standard
1.19
Degree of Protection
1.20
Span Between 2 support
Page 16 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
2
2.1
KR11-10302-CLC-001
Bus duct Sizing Calculation for MCC
Short Time Thermal Withstand Capability of Bus bar
Minimum Cross Sectional Area of Busbar (A) In Sq. Inches
Isc = Short Circuit Symmetrical Fault Current in KA
T = Fault duration in Sec
T1 = Initial Temperature of Busbar in Deg.C
T2 = Final Temperature in Deg.C
A = Cross sectional area of busbar in Sq.inches
A in sq.mm = A x 645.16
2.2
Required cross sectional Area
2.2
Actual Cross section of Bus bar Selected (As per Clause1.13) in
Sq.mm
Conclusion:
2.3
3
3.10
The required cross section 650.226 Sq.mm is less than actual cross section 900 Sq.mm of th
chosen is safe for the envisaged system.
Bus bar Selection for Continuous Current Rating :
Bus bar Selected
Open air rating of bus bar for 50 Deg. C rise over ambient in
Amps.
No. of times Interleaved (As per Clause1.11)
Overall Rating of Bus Bar in Amps.
3.12
Phase spacing in mm.
3.13
Enclosed Size in (W x D x H ) mm
3.14
Bus bar Enclosed in (W x D ) mm
3.15
Design Ambient Temperature
3.16
Maximum allowable temp. rise
3.11
Page 17 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
3.17
KR11-10302-CLC-001
Enclosure Material
Page 18 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
3.18
3.19
KR11-10302-CLC-001
De-rating / Up rating:
a Ambient correction factor for 35 Deg. Rise
b Enclosure correction factor corresponding to bus bar
c Enclosure Correction factor Material (MS)
d Proximity Effect Factor
e Bus bar Configuration Factor
=
=
g Combined Correction Factor
De-rated Current rating of bus bar after applying Correction factor
in Amps.
=
=
3.20
Rating of Panel required (As per Clause 1.5)
Conclusion :
3.21
The de-rated Current rating 903.78 amp of Panel selected is more than the required current
the bus bar size chosen is safe for the envisaged system.
4
4.10
Support Insulator Span Calculation During Short Circuit
Fm = Peak Electromagnetic force along the centre line of busbar
without enclosure
Isc = Short Circuit Symmetrical Fault Current in KA
S = Phase spacing in Meter
K = Multiplying factor (s-a)/(a+b)
corresponding to a that is 60
Fm (Nm / cm )
Fm ( Kg / cm ) = (Fm x 0.1019716)
F = Force acting on top of the insulator
=
=
4.12
a
b
Where, H = Cantilever Height of insulator in mm
h = Distance between surface of insulator to centre of Bus bar in
mm
=
F
Page 19 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
4.13
KR11-10302-CLC-001
Average span to be addopted in mm
=
=
SK = Cantilever strength of insulator(Kg/cm)
SF = Safety factor
Length of Span of insulator in mm
Adopted Span is
Conclusion:
4.4
Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe for th
Page 20 of 42
630 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
5
5.1
KR11-10302-CLC-001
Temperature Rise Calculation
Where, I1=Calculated Rating in Amps (After deration) As
per Clause 3.19
5.2
I2 = Specified Rating in Amps as per clause 1.5
5.3
T1 = Max. Temp. Rise (in Deg.C) Specified
5.4
T2 = Temp. Rise in Deg. C to be calculated as
=
T2
=
=
Calculated Temperature is
Conclusion :
5.5
The Calculated Temperature rise of bus bar is 19.37 Deg. C, which is within the design Spe
System envisaged.
Prepared By: Ganpat C
Checked By : Kamlakar D.
Page 21 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cubical Type
3PH ,3 Wire / 4 Wire
415V
50 Hz.
630
50
50
85
70
IP: 52 & IP: 42 for ACB Incomer
1 x 1 x 75 x 12 MM
1 x 75 x 06 MM
1
1
75
12
450
900
SMC support with ribbed construction
2.5KV RMS
Epoxy paint RAL-7032, Siemens Grey
Heat Shrinkable Sleeved.
Page 22 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
25 mm
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
IP: 54 for Indoor & IP: 55 for Outdoor
0.5mtr. (500mm)
Page 23 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
of Bus bar
( Isc / T ) / {14 x 10 log [T1 +258)/(T2+258)] }
50
1
85
200
1.0078517941
650.226
650.226 Sq.mm for pure aluminium.
900
is less than actual cross section 900 Sq.mm of the bus bar selected. Hence, the bus bar size
nt Rating :
As per Clause1.11
1350
1 x 1350
1350
150
7800 x 800 x 2400 mm
800 x 400 mm
50 Deg. C
35 Deg. C
Page 24 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
MS Steel
Page 25 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
0.9
0.87
0.9
0.95
1
0.67
1350 x 0.67
903.77775
630
Panel selected is more than the required current rating 630 amp of Bus duct Bus bar. Hence,
aged system.
ring Short Circuit
K x 16 x Isc x 10 / S
50
0.250
0.904
0.4 (Reffering to curve K is 0.9)
14400.000
1468.391
Fm (H+h)/4H
38
75
1091.6328126316
Page 26 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cantilever Strength of insulator / safety factor x F
Sk / (SF x F )
1600
2.5
586.278
OK
ut span adopted is 500 mm, hence it is safe for the system envisaged.
Page 27 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
903.77775
630
35
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )1.64
19.37
OK
r is 19.37 Deg. C, which is within the design Specified Temp. 35 Deg. C and it is safe for the
hecked By : Kamlakar D.
Approved By : A.B.H
Page 28 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
KR11-10302-CLC-001
Input Data
1.1
Type of Panel
1.2
System
1.3
Rated Voltage
1.4
degree of Protection
1.5
Panel Max. Current Rating in Amp (Design)
1.6
Fault Current & Duration (KA RMS Symmetrical for 1 Sec.)
1.7
Ambient Temperature (Deg. C.)
1.8
Maximum Bus bar Temperature (Deg. C.)
1.9
Maximum Enclosure Temperature (Deg. C.)
1.10
Degree of Protection
Bus bar Size for Phase
Bus bar Size for Neutral
No. of Runs
:
:
:
No. of times Interleaved
:
:
:
1.12
Width of Bus Bar in mm
Thickness of Bus Bar in mm
Bus bar cross section for Neutral in Sq.mm
1.13
Cross section of Bus bar Selected in Sq. mm
1.14
Type of Insulator
1.15
Basic Insulation Level:
1.11
a
1.16
1.17
One Minute Power Frequency voltage
Painting:
a. Enclosure Interior & Exterior
b. Bus bar
Minimum Clearance:
Page 29 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
KR11-10302-CLC-001
a. Phase to Phase
b. Phase to Earth
:
:
1.18
Applicable Standard
1.19
Degree of Protection
1.20
Span Between 2 support
Page 30 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
2
2.1
KR11-10302-CLC-001
Bus duct Sizing Calculation for MCC
Short Time Thermal Withstand Capability of Bus bar
Minimum Cross Sectional Area of Busbar (A) In Sq. Inches
Isc = Short Circuit Symmetrical Fault Current in KA
T = Fault duration in Sec
T1 = Initial Temperature of Busbar in Deg.C
T2 = Final Temperature in Deg.C
A = Cross sectional area of busbar in Sq.inches
A in sq.mm = A x 645.16
2.2
Required cross sectional Area
2.2
Actual Cross section of Bus bar Selected (As per Clause1.13) in
Sq.mm
Conclusion:
2.3
3
3.10
The required cross section 650.226 Sq.mm is less than actual cross section 1000 Sq.mm of
chosen is safe for the envisaged system.
Bus bar Selection for Continuous Current Rating :
Bus bar Selected
Open air rating of bus bar for 50 Deg. C rise over ambient in
Amps.
No. of times Interleaved (As per Clause1.11)
Overall Rating of Bus Bar in Amps.
3.12
Phase spacing in mm.
3.13
Enclosed Size in (W x D x H ) mm
3.14
Bus bar Enclosed in (W x D ) mm
3.15
Design Ambient Temperature
3.16
Maximum allowable temp. rise
3.11
Page 31 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
3.17
KR11-10302-CLC-001
Enclosure Material
Page 32 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
3.18
3.19
KR11-10302-CLC-001
De-rating / Up rating:
a Ambient correction factor for 35 Deg. Rise
b Enclosure correction factor corresponding to bus bar
c Enclosure Correction factor Material (MS)
d Proximity Effect Factor
e Bus bar Configuration Factor
=
=
g Combined Correction Factor
De-rated Current rating of bus bar after applying Correction factor
in Amps.
=
=
3.20
Rating of Panel required (As per Clause 1.5)
Conclusion :
3.21
The de-rated Current rating 1004.19 amp of Panel selected is more than the required curren
the bus bar size chosen is safe for the envisaged system.
4
4.10
Support Insulator Span Calculation During Short Circuit
Fm = Peak Electromagnetic force along the centre line of busbar
without enclosure
Isc = Short Circuit Symmetrical Fault Current in KA
S = Phase spacing in Meter
K = Multiplying factor (s-a)/(a+b)
corresponding to a that is 60
Fm (Nm / cm )
Fm ( Kg / cm ) = (Fm x 0.1019716)
F = Force acting on top of the insulator
=
=
4.12
a
b
Where, H = Cantilever Height of insulator in mm
h = Distance between surface of insulator to centre of Bus bar in
mm
=
F
Page 33 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
4.13
KR11-10302-CLC-001
Average span to be addopted in mm
=
=
SK = Cantilever strength of insulator(Kg/cm)
SF = Safety factor
Length of Span of insulator in mm
Adopted Span is
Conclusion:
4.4
Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe for th
Page 34 of 42
800 A MCC BUSBAR SIZING CAL
PROJECT
CLIENT
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
M/s. K.P.R. SUGAR MILL LTD
CONSULTANT
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
EPC
CONTRACTOR
ISGEC HEAVY ENGINEERING LIMITED
Document ID
5
5.1
KR11-10302-CLC-001
Temperature Rise Calculation
Where, I1=Calculated Rating in Amps (After deration) As
per Clause 3.19
5.2
I2 = Specified Rating in Amps as per clause 1.5
5.3
T1 = Max. Temp. Rise (in Deg.C) Specified
5.4
T2 = Temp. Rise in Deg. C to be calculated as
=
T2
=
=
Calculated Temperature is
Conclusion :
5.5
The Calculated Temperature rise of bus bar is 24.11 Deg. C, which is within the design Spe
System envisaged.
Prepared By: Ganpat C
Checked By : Kamlakar D.
Page 35 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cubical Type
3PH ,3 Wire / 4 Wire
415V
50 Hz.
800
50
50
85
70
IP: 52 & IP: 42 for ACB Incomer
1 x 1 x 100 x 10 MM
1 x 100 x 06 MM
1
1
100
10
600
1000
SMC support with ribbed construction
2.5KV RMS
Epoxy paint RAL-7032, Siemens Grey
Heat Shrinkable Sleeved.
Page 36 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
25 mm
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
IP: 54 for Indoor & IP: 55 for Outdoor
0.5mtr. (500mm)
Page 37 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
of Bus bar
( Isc / T ) / {14 x 10 log [T1 +258)/(T2+258)] }
50
1
85
200
1.0078517941
650.226
650.226 Sq.mm for pure aluminium.
1000
is less than actual cross section 1000 Sq.mm of the bus bar selected. Hence, the bus bar size
nt Rating :
As per Clause1.11
1500
1 x 1500
1500
150
4400 x 800 x 2400 mm
800 x 400 mm
50 Deg. C
35 Deg. C
Page 38 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
MS Steel
Page 39 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
0.9
0.87
0.9
0.95
1
0.67
1500 x 0.67
1004.1975
800
of Panel selected is more than the required current rating 800 amp of Bus duct Bus bar. Hence,
aged system.
ring Short Circuit
K x 16 x Isc x 10 / S
50
0.250
0.904
0.4 (Reffering to curve K is 0.9)
14400.000
1468.391
Fm (H+h)/4H
38
75
1091.6328126316
Page 40 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
Cantilever Strength of insulator / safety factor x F
Sk / (SF x F )
1600
2.5
586.278
OK
ut span adopted is 500 mm, hence it is safe for the system envisaged.
Page 41 of 42
CC BUSBAR SIZING CALCULATION
Revision : 01
Date : 24-05-2012
No. of Sheet - 4
1004.1975
800
35
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )1.64
24.11
OK
r is 24.11 Deg. C, which is within the design Specified Temp. 35 Deg. C and it is safe for the
hecked By : Kamlakar D.
Approved By : A.B.H