MINI Embedded DC power supply system-Technical data
MINI DC Power
Supply System
User manual
MINI Embedded DC power supply system-Technical data
Contents
Chapter1 System overview................................................................3
1. Model description...................................................................... 3
2. System structure and the standard............................................. 3
3. System Feature........................................................................... 4
Chapter2 Rectifier module.................................................................5
1. Introduction................................................................................ 5
2. Function.......................................................................................................................... 5
3. Specification................................................................................................................ 7
Chapter3 Monitor module............................................................... 10
1. Appearance...............................................................................10
2. Features and Funtion................................................................10
Chapter4 Rack system..................................................................... 18
1. Front panel............................................................................... 18
2. Back panel................................................................................19
3. Communication Dry Contact................................................... 20
Chapter5 Warranty card................................................................... 21
Page 2 Totally 22 pages
MINI Embedded DC power supply system-Technical data
Chapter1 System overview
1. Model description
System Model
MINI
MINI: mini system, high Power density
Rectifier Model
3048
30: Power, Unit is hundred, that is 3000W
48: Output voltage 48Vdc
Monitor Model
M30
M: Monitor
30: match with 3048 module etc.
2. System structure
The system configuration is flexible. All the functional modules are easy to embed into
the system.
3. System Feature
MINI embedded DC power systems advanced modular design makes the whole system
are small, but it can provide enough power to meet the requirements of communication
Page 3 Totally 22 pages
MINI Embedded DC power supply system-Technical data
systems, consistent with the characteristics of the rack-mounted. The system is suitable
for all sizes of exchange room, base stations, satellite communications, data
communications, railways and power systems. MINI DC power system is easy to operate,
install and maintain. Module subrack adopts inset-box installation for flexible expansion
capacity and replacement controller.
Features:
●With active power factor compensation technology power factor of rectifier
is up to 0.99
●Standard height 2U,the weight of each module is 2.6kg and output current is
Max 50A , with high power density.
★Rectifier modules adopted soft switch technology. When load rate
is 10%, efficiency can be 91%; 50% load rate ,the efficiency
can be above 97%
●Complete battery protection and load disconnect management. It has LVD
function, which maximizes to protect battery.
●Rectifier and monitor modules adopt hot swap technology, Plug and play;
●Standard RS232 communication interface, support SNMP; 3-class alarm dry
contact: Emergency alarm, main alarm and minor alarm.
●Complete fault protection, alarm function;
●Low radicalization: Advanced EMC rectifier design can meet the
communication power rectifier equipment electromagnetic compatibility
limits and measurement methods in the PRC telecommunications industry and
standard YD/T983 conducted and radiated interference requirements.
●System configuration is flexible and easy to expand; N +1 redundant power
supply. It can be configured according to customer demand;
★ Products have passed the inspection of the Ministry of Information
Industry Quality Supervision and Inspection Center.
Page 4 Totally 22 pages
MINI Embedded DC power supply system-Technical data
Chapter 2 Rectifier Modules
1.Introduction
Our rectifier modules adopt pure resonant soft-switching technology and Plug and play.
Each module is equipped with advanced microprocessors. On the front panel, each
rectifier modules has 3 Led indicators: power supply indicator, communication indicator
and failure indicator.
Abnormal
Indicators Normal state Reasons
states
No AC input or
Power supply
On Off input fuse is
Indicators
damaged
Communication Communication
Off Twinkling
Indicators fail
Failure There is a damage
Off On
Indicators inside the module
2.Functions:
●Soft switch
Rectifier power circuit is divided into active PFC and DC to DC converter which can
make the wide input voltage range (75V-300V) and high efficiency (above 97%). High
power density has reached the international advanced level. Efficiency curve is shown as
below.
Page 5 Totally 22 pages
MINI Embedded DC power supply system-Technical data
● Forced wind cooling
Advanced design of Circuit makes for low-heating with heat sink.
● Hot swappable
The monitoring module is hot-pluggable. When the module is plugged into the system, it
will not cause the system output voltage fluctuations. Damaged modules can be replaced
in less than 1min without stopping the system operation.
●Protection & failure alarm
In different protection / fault types rectifier has different reaction / action mode.
●Auto equalized output in low-gap voltage of modules
Adopted auto equalized output in low-gap voltage of modules technology. When the
monitor module or individual rectifier is failure the other modules can maintain current
sharing.
● Stepless limiting technology
With stepless limiting technology, it can be continuously adjusted between rated current
0~110%
Page 6 Totally 22 pages
MINI Embedded DC power supply system-Technical data
● Monitor
Monitor has built-in CPU, monitoring the operation status of modules, and is responsible
for the communication. The rectifier module receive ON/OFF current limit point and
voltage setting sending by monitor through RS485, and send back the voltage, current,
temperature limiting point ON/OFF status and alarm in real time to the monitor module.
●Fan control and dust-proof
Stepless temperature control fan speed, and change with the output power of module,
which minimize noise and extend fan life.
3. Specification
Specification SET0848 SET1048 SET1648 SET3048
Input voltage (AC) 75V-300V
Output voltage (DC) 48V (42V-59V Continuously adjustable)
Output current (A) 15A 20A 30A 50A
Power (W) 800W 1000W 1600W 3000W
Operating temperature -25℃ ~ 45℃
Relative Humidity ≤97%RH
Load regulation ≤0.5%
Voltage regulation ≤0.10%
Dimension 103mm(W)*261mm(D)*88mm(H)
Weight 2.6kg
1. Environment
Work temperature: -25℃ ~ 45℃
Storage temperature: -40℃ ~ 70℃
Relative humidity:≤97%RH
Page 7 Totally 22 pages
MINI Embedded DC power supply system-Technical data
Height above sea level:≤3000m
2. Input properties
Input 175~300VAC normal output
Input 75~175VAC reduce output
3. Output properties
48VDC output,maximum output power 3000W
DC output voltage 42V ~ 59V, It can be continuously adjusted by monitoring module
DC output current 0A ~ 50A
Voltage regulation precision: ≤ 0.6%
Load regulation:≤ 0.5%
Voltage regulation:≤ 0.1%
4. Output current-limiting properties
In the range of 0 ~ 110% rated current can be continuously adjusted.
5. Power factor: ≥ 0.99
6. Efficiency: ≥ 97%
7. equalized-current imbalance: ≤ 3%
8. Temperature compensation coefficient:Can be set manually,unit (mV/℃)
9. Dc output noise:
Peak noise voltage:≤200mV 0 ~ 20MHz
Weighted psophometric noise voltage: ≤ 2mV
Wide frequency noise voltage: ≤50mV 3.4kHz ~ 150kHz
≤20mV 0.15 MHz 30MHz
Discrete noise voltage: ≤5mV 3.4kHz ~ 150kHz
Page 8 Totally 22 pages
MINI Embedded DC power supply system-Technical data
≤3mV 150kHz ~ 200kHz
≤2mV 200kHz ~ 500kHz
≤1mV 0.5MHz ~ 30MHz
10. Noise:≤45dB(A)
11. Alarm & Protection
1)Over-current protection
Over-current protection of input (use fuse)
Over-current protection of output (use fuse)
Over-current protection of PFC (use diverter)
Short circuit protection (reduce input current to protect)
2)Over-voltage & low-voltage protection (The following parameters can be adjusted by
hardware.)
Input low-voltage protection: 75±5V, hysteresis:10V ~ 20V
Input over-voltage protection: 300±5V,hysteresis:5 ~ 20V
Output over-voltage protection:59 ±1V
3) Other protection
Over- temperature protection (default value 80℃, hysteresis:10℃)
12. Size of the module:
88mm(H)×103mm(W)×261mm(D)
13.Weight:≤2.6Kg
Page 9 Totally 22 pages
MINI Embedded DC power supply system-Technical data
Chapter3 Monitor module
1. Appearance
M16 monitoring module has LCD screen (128*64 Blue background white text), key and
indicators. It can display data of the system in real time and setup by keys.
Indicators Normal Abnormal Reasons
Power supply On Off No AC input or input fuse is
indicator damaged
Equalized &float Off On Equalized charging(On)
charging indicator Float charging(Off)
Failure Off On There is a damage inside the
indicators system
Advanced microprocessors make accurate, reliable and fast.
It has local control and remote monitoring, truly intelligent system.
2. Features and Functions
2.1. Input specification
Rating DC input voltage:48VDC
Range of voltage: 42V~59VDC
Work temperature: -25℃~ 45℃
Page 10 Totally 22 pages
MINI Embedded DC power supply system-Technical data
2.2. Display and setting
Monitor module will display: operating parameter, states, warning, setting parameter and
control parameters.
Key Description: There are 4 bottoms on the monitor panel: “ ”, “↑”, “↓”, “ ┛ ”.
Press“┛” to change the parameter. Press “↑”, “↓” to change its data, and “┛” to save.
keys: “ ” “↑” “↓” “┛ ”. Press the keys to change the data, and save the change.
Operation process and instruction
1.Screensaver:
Power supply Display the current time and date.
17:04:05 Press “ ┛ ” to enter system
2015Y04M29D information menu.
2. System information menu:
Display the current system voltage
System V: 53.5 V (online voltage), load current,
Load I: 2005 A
10.1 年 11 月 09 日
battery current and module current.
Bat I1: 20.2 A Press “ ┛ ” to enter the password
Bat I2 : 30.3 A2005 年 menu .
3. System information menu Display AC input voltage, AC input
Ret I : 0.1 A on
current and AC input frequency.
Input-V : 215 V Press “ ┛” to enter the password input
Input-I: 0.0 A menu
Input-F: 50 Hz
4. System information menu
LVD 1 Status Display LVD Status.
Close Press “ ┛ ” to enter the password
LVD 2 status input menu
Close
5. System information menu:
Bat temp :32.1℃ 2005 年 Display battery temperature, charge mode
Chg mode:Float (Equalized/Float charging) and the alarms
Now has 0 Alarms event.
Page 11Look >>22 pages
Totally
Press“┛”to view more alarms content
MINI Embedded DC power supply system-Technical data
6. Modules information:
Display module 1-N info。
Ret 1 com OK Press “↑” “↓” to check the other
2005 年 11 月
Output V : 53.58 V modules information. Press “ ┛ ”
Output I: 0.07 A to enter the password input menu
年
7. Input password:
Input password
The default password is 0000. The
2005 年 11 月 09 日
user can enter the system menu to
0000
change your password.
2005年
8. Main menu:
System menu Press “↑” “↓” to choose the
1. System V
2005 年 11 月 09item, and press “ ┛ ” to view
2. Chg Manager the details.
3. Alarm Val Set
9. Main menu:
System menu Press “↑” “↓” to choose the
4. LVD Set item, and press “ ┛ ” to view
5. Time Setting the details.
6. Change password
10. Main menu:
System menu Press “↑” “↓” to choose the
2005 年 11 月
7. Language item, and press “ ┛ ” to view
8. Version the details.
9. System Set
2005年
11. System voltage setup:
System V Set System float voltage.
2005 年 11 月 09 Press “↑” “↓” to change the
53.5 V value, and press “┛” to confirm.
12. Charge management:
Charge
Press “↑” “↓” to choose the
1. Bat I Limit
item, and press “ ┛ ” to view
2. Equ VoltagePage 12 Totally 22 pages
the details.
3. Equ time
↑↓
MINI Embedded DC power supply system-Technical data
13. Charge management:
Charge
Press “↑” “↓” to choose the
4. Equ Period
item, and press “ ┛ ” to view
5. Equ Time
the details.
6. Chg Manual
↑↓
14. Charge management:
Charge Press “↑” “↓” to choose the
7. Temp Compensate item, and press “ ┛ ” to view
the details.
↑
15. Battery charge current limit value:
Bat I Limit
Set battery charge limit
value
010.0 A
;
16. Value of Equalized Charging voltage:
Equ voltage Set value of Equalized
Charging
56.5 V
17. Value of Equalized charge time:
Equ time Value of Equalized charging
time
010 hours
18. Value of Equalized charge period
Equ Period Value of Equalized charge
interval
05000 hours
19. Equalized charging in specified time:
Set the specified charging time. When the
Page 13 Totally 22 pages time reaches the specified time, the
charging status will change to Equalized
charge, and the output of system is also
Equalized voltage
MINI Embedded DC power supply system-Technical data
Equ time
17:26:26
12 – 04- 30
20. Manual set Equalized /Float charging:
Chg Manual The user can change the
1.manual Float charging model manually.
2.manual Equ When set OK, the charge time
will start from 0.
21. Temperature compensates:
It can set compensation coefficient
Temp compensate the starting point. For example, the
Coeffi: 000 mV coefficient is 2mV, and the starting
Compen start:0 ℃ point 40℃, the output voltage should
minus 20mV at 50℃.
\
22. Set alarm limit value:
Alarm Val Set Here, it can set the values of
1. Bat High-V Set battery high/low voltage and
2. Bat Low-V Set AC over voltage alarm value.
3. Input Over-Vol
23. Set alarm limit value:
Alarm Val Set Set AC under voltage value, AC
4. Input under-Vol over current value and AC frequency
5. Input Over-Cur range value
6. Freq Range Set
24. Set alarm limit value
232323
Alarm Val Set Set battery temperature alarm value
7. Temp High Set Alarm Val Set and alarm sound control (ON/OFF).
8. Sound Set
25. Set over voltage alarm value:
Bat High-V Set Set overvoltage value. When the
system voltage exceeds this value, the
59.0 V
system will shut down the module and
not recoverable.
26. Set under voltage alarm value:
Bat Low-V Set
Set under voltage alarm value. When the
42.0 V system voltage is below this value, the
system will sound single audible alarms.
Page 14 Totally 22 pages
MINI Embedded DC power supply system-Technical data
27. Set AC over voltage alarm value
Input Over-Vol
300 V
28. Set AC under voltage alarm value
Input Under-Vol AC under voltage setting. When AC
voltage is below this value, the system
085 V will sound single audible alarms.
29. Set AC over current value
Input Over-Cur AC over current setting. When AC
current is over this value, the system
020A will sound single audible alarms.
30. Set AC frequency range
AC frequency range setting. When
Freq Range Set
AC frequency is over this range, the
20% system will sound single audible
alarms.
31. Set temperature alarm value
Temp High Set Set the battery temperature alarm
value. When the battery temperature
40.0℃ is over this value, the system will
sound single audible alarms.
32. Audible alarm setting
Sound Set
The user can set if the system will
1. ON
sound alarm or not. The default is ON.
2. OFF
33. Low voltage disconnection set
LVD Set
1. LVD 1 Setup 2-class LVD.
2. LVD2 Setup press “┛” to view the details.
Page 15 Totally 22 pages
MINI Embedded DC power supply system-Technical data
34. LVD 1
Low voltage disconnection 1 connects
LVD 1 Setup the main load. When the battery voltage
Open V 43.0 V is shortage, the main load disconnected.
Close V 45.0 V When the battery voltage is recovery to
the working voltage, it will automatically
work.
35. LVD 2
Low voltage disconnection 2 connects the
LVD 2 Set
main load. When the battery voltage is
Open V 45.0 V
shortage, the main load disconnected.
Close V 47.0 V
When the battery voltage is recovery to the
working voltage, it will automatically
36. Set time work.
Time Setting
18:51:56 Set system time and date.
15-4-29
37. Reset password
Input New Here to change the new
password. Input new
0000 password, and press “┛”.
38. Language
Language
1.Chinese Select the language.
2. English
39. Version
Version Monitor device version.
1. 00d bulid 404A
40. System Set configuration
System Set Configure the number of
1. Ret Sum: 02 modules of the current system.
2. Address: 01 Page 16 Totally 22 pages
MINI Embedded DC power supply system-Technical data
2.3 Control functions
The MINI System can release control signals according to the operation of the system.
Monitor module supports both automatic and manual battery management. Manual mode
includes: equalized/float charging of battery groups, adjust rectifier modules voltage (it
can change the system voltage), and set battery charging time. In automatic mode, the
device will automatically complete the battery charge management according to charge
interval and the specified date. When the system works, it can also change the charge
mode (equalized or float charging). That is manual mode. In manual mode, all timing
starts from zero, and continue to timing by the automatic mode, which can effectively
prevent human operational errors to result in losses.
2.4 Complete communication functions
Host can monitor and control all the parameters, the status of the lower machine. At the
same time, for safety and reliable, the host and the lower machine not only install the
communication protocol to constrain each other, but also must know the monitor
password of the lower machine, and sent it to the lower machine, when the host wanted
to get the all parameters of the lower machines or monitor the lower machine. After the
lower machine checked correctly, it can monitor and control. This is to ensure the
stability of the power and avoid unnecessary losses caused by human.
2.5 Alarm & Record
Monitoring module has sound and light alarm function according to collect data and a
corresponding action. The main alarms are emergency, main and minor.
2.6 Automatic battery management
Monitor module can implement various conservation measures to protect the battery,
such as charging current limit, temperature compensation according to user set data, and
charging current limit, average and float charge conversion time, average and float charge
voltage etc. battery charging methods.
Page 17 Totally 22 pages
MINI Embedded DC power supply system-Technical data
2.7 Communication
Monitor module has the host and the lower device communication functions. It
communicates with the host by RS232; communication with the lower device by RS485.
2.8 Dry contact output
There are 3 dry contact outputs.
Emergency dry contact: Mains failure, LVD1, LVD2, over-voltage module, module fan
failure.
Main dry contact: Battery fuse alarm, MCB alarm.
Minor dry contact: battery temperature alarm, communication failure.
Chapter4 Rack system
1. Front panel
1pcs AC/DC Distribution unit,1pcs module, 1pcs fake module,1pcs monitor (From left to
right place)
Page 18 Totally 22 pages
MINI Embedded DC power supply system-Technical data
2 Back panel
Single phase input
Page 19 Totally 22 pages
MINI Embedded DC power supply system-Technical data
3 phase input
Page 20 Totally 22 pages
MINI Embedded DC power supply system-Technical data
3. Communication Dry Contact
SNMP
Level 1 alarm
Level 2 alarm
Level 3 alarm
RS232 series port
About dry contact:
Level 1:line lack of phase、low-vol break away、modules over-vol、failure
of modules fan
Level 2:loads switch alarm、batteries switch alarm
Level 3:batteries over-tem,modules communications
Page 21 Totally 22 pages
MINI Embedded DC power supply system-Technical data
Warranty Card
To ensure good quality product, the MINI power supply system was thoroughly
checked before leaving the factory. The manufacturer guarantees to the user that
the system is in good condition. The manufacturer provides 1-year warranty
service from date of delivery to the original purchaser
Please refer to the warranty statement.
User’s Information
User Company: Contact person:
Address: Phone:
Dealer company: Post code:
Model: Serial number:
Purchase date: Handling person:
Repair Record
Date Record Abstract Technician Signature
Page 22 Totally 22 pages