C1866-101 - Drainage Details

This drainage construction note document contains general notes for drainage construction including: 1. Concrete mixes to be used including a sulphate resisting mix for all insitu and precast concrete. 2. Trench widths for pipes ranging from 100mm to 450mm in diameter. 3. Backfill details for trenches under buildings and roads including maintaining 150mm clearance under foundations.

Uploaded by

Paqui Morent
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
175 views1 page

C1866-101 - Drainage Details

This drainage construction note document contains general notes for drainage construction including: 1. Concrete mixes to be used including a sulphate resisting mix for all insitu and precast concrete. 2. Trench widths for pipes ranging from 100mm to 450mm in diameter. 3. Backfill details for trenches under buildings and roads including maintaining 150mm clearance under foundations.

Uploaded by

Paqui Morent
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Drainage Construction Notes Continued: General Notes

Road formation, sub-formation 18. The following concrete mixes are to be used (all in
or underside of topsoil 1. Do not scale.
Wall accordance with BS 8500):-
Ground Level Trench Widths
2. This drawing is to be read in conjunction with all other
Width (mm) relevant drawings.
Backfill to Clause
Backfill as Class Z pipe 100 550 505 of Specification
'A' bedding detail 150 600 for Highway Works 3. Should there be any discrepancy between details
225 700 indicated on this drawing and those indicated on other
Underside of Where 'A' is less than 1.0m, 300 750 drawings the Engineer should be informed PRIOR to
foundation concrete fill to level of underside 375 1050 construction on site.
of foundation 450 1150
4. Until technical approval has been obtained from the
Strip or raft relevant Authorities it should be understood that all drawings

300
Note. issued are preliminary and NOT for construction. Should the
foundation
1) No mechanical compaction to occur contractor start site work prior to approval been given, it is

150
within 300mm of crown of pipe.
19. All insitu concrete to be sulphate resisting. entirely at his own risk.
2) Where pipes are laid under buildings,

50
'A' less 150mm Max.
refer to Engineer for further details.
All precast concrete products (ie pipes, manholes, etc) are 5. All dimensions shown are in millimetres unless noted
to be sulphate resisting. otherwise.

bc

bc
Pipe bedding for socketed pipes a =
Where 'A' is 1.0m or 100mm or bc/6min whichever is greater
more concrete 20. Granolithic concrete benching to be steel trowelled to a Drainage Construction Notes:
under barrels but not less than 50mm
surround to this level dense smooth face neatly shaped and finished to all branch
under sockets.
connections and laid in accordance with the specification
(min thk. 20mm). 1. All pipework shall be 100mm unless otherwise stated.

100 min.

a = bc/6 or
bc/4 or

100 min.
Legend:
Pre-formed channels are to be used in all manholes with 2. Concrete pipes and fittings with flexible joints to comply
Notes: Single size granular material 300mm dia pipes or less.

bc
with BS5911.
1) Flexible joints shall be provided in concrete, Applicable under footpaths, verges and
Grade C20 Concrete Applicable under trafficked areas where Pre-cast concrete seating rings shall NOT be used on
by inserting compressible board at intervals not other non-trafficked areas where drains 3. Clayware pipes and fittings shall comply with BS EN
drains have cover not less than 1200mm Adoptable Manholes.

Y
exceeding 5m. Pre-cut to diameter, height and have less than 600mm cover, or trafficked 295:1991
Selected fill from excavated material
width equal to the concrete cross section. Filler areas with cover of less than 1200mm
to be 18mm thick min. Manholes 4. Rubber joint rings shall be Type D to BS EN 681-1 1996
Pipe runs Near Buildings Topsoil
2) For values of Y refer to pipe bedding details. Class Z Bedding For Class S Bedding For and shall be obtained from pipe manufacturer.
Scale 1:10
Rigid Pipes Rigid Pipes 1. Precast concrete manholes, cover slab and seating rings
(Bedding Factor = 2.5) to comply with BS 5911 PT200. 5. Drainage to BS EN 752 with pipes of approved type
Scale 1:10
Scale 1:10 drainage system on granular bed and surround and all in strict
2. Brick manholes to be constructed in flush pointed English accordance with manufactures instructions.
bond Class B solid engineering bricks to BS3921 in
sand/cement mortar. 6. Pipes with cover less than :- 600mm under building and
gardens, 900mm under car parking areas, 1200mm under
3. Manhole step irons to comply with BS EN 13101:2002. roads to be surrounded in minimum 150mm thk concrete
(class Z). Pipe bends within manholes shall suit direction of
4. Manhole covers and frames to be ductile iron heavy duty flow.
Flexible Joints grade D400 double triangular to BS EN 124 in carriagways
A B
Notes and heavy vehicular trafficked areas (150mm thick). 7. All Pipes entering & exiting manholes are to be connected
with soffits level.
1. Concrete bed and surround shall be provided as 5. Manhole covers and frames to be ductile iron medium duty
Floor Slab section A-A where distance between underside of slab grade B125 circular or rectangular to BS EN 124 in non 8. First flexible joint in pipes adjacent to a manhole shall be a
and pipe soffit is less than or equal to 300mm. Cover and frame of trafficked areas. max. 600mm from inside face of manhole, connecting to
Backfill Type 1
300

Sub-Bse appropriate load class rocker pipe. For pipes of 150-450mm, the rocker pipe length
2. Where pipes with flexible joints are used the to BS EN 124 shall be 500mm-750mm and for pipe diameters 451-750
6. All cement used in the construction of manholes shall be
concrete protection shall be interrupted over it's full
minimum class 2 sulphate resisting Portland (SRPC) to the rocker pipe shall be 750mm-1000mm.
cross section at each joint by a shaped compressible
relevant provisions of BS 4027:1996 CESWI spec CL 2.15.
Granular Bed filler.
9. Pipes shall be laid to their true line and level by laser or by
& Surround
3. If pipes are surrounded in concrete, the joints shall Hepworth polypropylene 7. Refer to CESWI specification CL 2.20 for sand/cement boning each end and middle.
Concrete Bed 150
A B be protected from the ingress of conrete by wrapping 475mm dia. inspection mortar grades.
& Surround
them with two coats of mastic bandage tape. chamber or similar approved 10. All soft spots within pipe trenches shall be removed.
installed fully in accordance 8. High strength granolithic concrete topping to benching to
Section Through Drains with manufacturers be steel trowelled to a dens smooth face neatly shaped and 11. No water shall be allowed to accumulate in pipe trenches
requirements. during construction.
finished to all branch connections in accordance with CESWI
specification CL. 4.30.
Not less than 150mm grade C20 concrete 12. All fill material shall be consolidated in layers not
Floor Slab 300mm surround to manhole. 9. Pre-formed channels shall be used at manholes where exceeding 225mm.
possible.
Not to exceed Backfill Type 1 Sub-Base to Rocker pipe
13. P.C concrete lintels to be used over pipes and ducts
300mm Clause 803 to extend to passing through walls.
Concrete bed and surround underside of structural slab 150mm grade GEN3
as Class Z bedding detail. concrete base.
Granular bed and surround 14. All insitu concrete used in pipe protection to be min. grade
Concrete to extend to
as Class S bedding detail ST4.
underside of structural slab
Section A-A Section B-B
External PPIC Manhole
Scale 1:20 15. Compressible filler for interruption of concrete pipe
protection shall consist of bitumen impregnated insulating
board to BS 1142 at each pipe joint: thickness in accordance
Drains Under Buildings with CESWI clause 2.52.
Scale 1:20
16. All redundant drains shall be removed or concrete sealed.

17. All pipe runs to be laid with flexible joints.

All pipes entering and exiting manholes are to be connected


with pipe soffits level unless noted otherwise.

Rev. By Date Details Chkd

Drawing Status
PRELIMINARY

Linear drain set 3mm (min) below


finished surface level
Bituminous joint strip
hsp
c onsulting
150-250

Lawrence House, Meadowbank Way, Eastwood, Nottingham, NG16 3SB


Tel: 0870 600 6090 www.hspconsulting.com

Client

Central Site Accommodation Ltd

150 150 GEN3 concrete surround,


min 150mm thick
Project

Typical Linear Drain Forest Town School


Scale 1:10
Proposed Extension

Title

Drainage Details

Scale (A1) Drawn by. Drg. No. Rev.


As shown DG
Date. Checked by. C1866-101 -
27.05.2014 RH