0% found this document useful (0 votes)
229 views18 pages

SLG 425I Operating Instructions Safety Light Grid

This document contains operating instructions for a safety light grid (SLG 425I). It describes the product's intended use, safety considerations, and instructions for electrical connection, setup, maintenance, diagnostics, disassembly and disposal. The instructions are intended for authorized qualified personnel to ensure the safe operation and maintenance of the safety equipment.

Uploaded by

Johnny Sá Dias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
229 views18 pages

SLG 425I Operating Instructions Safety Light Grid

This document contains operating instructions for a safety light grid (SLG 425I). It describes the product's intended use, safety considerations, and instructions for electrical connection, setup, maintenance, diagnostics, disassembly and disposal. The instructions are intended for authorized qualified personnel to ensure the safe operation and maintenance of the safety equipment.

Uploaded by

Johnny Sá Dias
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Operating instructions

Safety light grid SLG 425I


4 Electrical connection
4.1 Wiring example Muting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2 Connector configuration Receiver, Emitter & Cable . . . . . . . . . 14

5 Set-up and maintenance


5.1 Check before start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
EN Operating instructions����������������������pages 1 to 18 5.3 Regular check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Translation of the original operating instructions 5.4 Half-yearly inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.5 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

6 Diagnostic
6.1 LED status information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.2 Fault diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Vous trouverez la version Encontrará el manual de
FR ES 6.3 Extended diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
actuelle du mode d’emploi dans instrucciones actual en su
votre langue nationale officielle idioma oficial de la UE en
sur l’Internet, nuestra página de Internet 7 Disassembly and disposal
www.schmersal.net. www.schmersal.net.
7.1 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
NL
U vindt de huidige versie van de
IT
Il manuale d‘istruzioni aggior- 7.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
gebruikshandleiding in uw nato nella vostra lingua (lingua
officiële landstaal op het Inter- ufficiale UE) è scaricabile in
net, www.schmersal.net. Internet all‘indirizzo 8 Appendix
www.schmersal.net. 8.1 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
JP
EU公用語で書かれた最新の取扱 8.2 EC Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . 18
説明書は,インターネッ
(www.schmersal.net) からダウ
ンロードできます。

Content 1. About this document

1 About this document 1.1 Function


1.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 This operating instructions manual provides all the information you
1.2 Target group: authorised qualified personnel . . . . . . . . . . . . . . . 1 need for the mounting, set-up and commissioning to ensure the safe
1.3 Explanation of the symbols used . . . . . . . . . . . . . . . . . . . . . . . . 1 operation and disassembly of the safety switchgear. The operating
1.4 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 instructions must be available in a legible condition and a complete ver-
1.5 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 sion in the vicinity of the device.
1.6 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.7 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.2 Target group: authorised qualified personnel
All operations described in this operating instructions manual must
2 Product description be carried out by trained specialist personnel, authorised by the plant
2.1 Destination and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 operator only.
2.2 Ordering code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Special versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Please make sure that you have read and understood these operat-
2.4 Scope of delivery and accessories . . . . . . . . . . . . . . . . . . . . . . . 2 ing instructions and that you know all applicable legislations regarding
2.4.1 Accessories included in delivery . . . . . . . . . . . . . . . . . . . . . . . . . 2 occupational safety and accident prevention prior to installation and
2.4.2 Optional accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 putting the component into operation.
2.5 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.6 Response time (reaction time) . . . . . . . . . . . . . . . . . . . . . . . . . . 3 The machine builder must carefully select the harmonised standards to
2.7 Safety classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 be complied with as well as other technical specifications for the selec-
2.8 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 tion, mounting and integration of the components.
2.8.1 Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.8.2 Restart interlock (manual reset) . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Explanation of the symbols used
2.8.3 Start interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.8.4 Beam coding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Information, hint, note:
2.8.5 Fixed blanking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 This symbol is used for identifying useful additional informa-
2.8.6 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 tion.
2.9 Operating mode muting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.9.1 Adequate and appropriate application . . . . . . . . . . . . . . . . . . . . 4
x.000 / Juli 2012 / v.A. - 101214175-EN / C / 2012-07-06 / AE-Nr. 1648

2.9.2 Muting sensors MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Caution: Failure to comply with this warning notice could
2.9.3 Muting lamp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 lead to failures or malfunctions.
2.9.4 Signal sequence muting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Warning: Failure to comply with this warning notice could
2.9.5 Configuration of the muting function . . . . . . . . . . . . . . . . . . . . . . 6 lead to physical injury and/or damage to the machine.
2.9.6 Saving the data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.9.7 Muting applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.4 Appropriate use
The products described in these operating instructions are developed to
3 Mounting execute safety-related functions as part of an entire plant or machine. It
3.1 General conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 is the responsibility of the manufacturer of a machine or plant to ensure
3.2 Protection field and approach . . . . . . . . . . . . . . . . . . . . . . . . . . 10 the correct functionality of the entire machinery or plant.
3.3 Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Safety distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4.1 Minimum distance to reflecting surfaces . . . . . . . . . . . . . . . . . . 11
3.5 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

EN 1
Operating instructions
Safety light grid SLG 425I
The safety switchgear must be exclusively used in accordance with the 2.2 Ordering code
versions listed below or for the applications authorised by the manufac- This operating instructions manual applies to the following types:
turer. Detailed information regarding the range of applications can be
found in the chapter "Product description".
SLG425I-ER-➀-RF
1.5 General safety instructions No. Option Description
The user must observe the safety instructions in this operating instruc-
tions manual, the country-specific installation standards as well as all ➀ Distance between outermost beams:
prevailing safety regulations and accident prevention rules. 0500-02 500 mm, 2-beam
0800-03 800 mm, 3-beam
Further technical information can be found in the Schmersal 0900-04 900 mm, 4-beam
catalogues or in the online catalogue on the Internet: www.
schmersal.net. Only if the information described in this operating instruc-
tions manual are realised correctly, the safety function and
The information contained in this operating instructions manual is pro- therefore the compliance with the Machinery Directive is
vided without liability and is subject to technical modifications maintained.

The entire concept of the control system, in which the safety 2.3 Special versions
component is integrated, must be validated to EN ISO 13849-2. For special versions, which are not listed in the order code, these
specifications apply accordingly, provided that they correspond to the
There are no residual risks, provided that the safety instructions as well standard version.
as the instructions regarding mounting, commissioning, operation and
maintenance are observed. 2.4 Scope of delivery and accessories

Additional measures could be required to ensure that the electro-sensi- 2.4.1 Accessories included in delivery
tive device does not present a dangerous breakdown, when other forms Mounting kit MS-1030
of light beams are available in a special application (e.g. use of wireless The kit comprises 4 rotating mounting angles and 16 mounting screws
control devices on cranes, radiation of welding sparks or effects of for fixing to the end caps.
stroboscopic lights).
2.4.2 Optional accessories
1.6 Warning about misuse Centre fixing MS-1051
Consisting of 2 steel angles, 4 fixing screws and 4 T-slot nuts
In case of inadequate or improper use or manipulations of the
safety switchgear, personal hazards or damage to machin- Connecting cable for transmitter
ery or plant components cannot be excluded. The relevant Item number Designation Description Length
requirements of the standards EN ISO 13855 (successor of 101207741 KA-0804 Female connector M12, 4-pole 5m
EN 999) and EN ISO 13857 must be observed. 101207742 KA-0805 Female connector M12, 4-pole 10 m
101207743 KA-0808 Female connector M12, 4-pole 20 m
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from Connecting cable for receiver
defective mounting or failure to comply with this operating instructions Item number Designation Description Length
manual. The manufacturer shall accept no liability for damages result- 101207728 KA-0904 Female connector M12, 8-pole 5m
ing from the use of unauthorised spare parts or accessories. 101207729 KA-0905 Female connector M12, 8-pole 10 m
101207730 KA-0908 Female connector M12, 8-pole 20 m
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden; BUS converter NSR-0801
the manufacturer shall accept no liability for damages resulting from Converter for parametrization and diagnostics. Detailled information can
such invasive work, arbitrary repairs, conversions and/or modifications be found in the operating instructions manual of the NSR-0801.
to the device. Included in delivery: integrated connecting cable, PC-software USB
2.0 connection (L x W x H, 122 x 60 x 35 mm), indications of measure-
ments without cable
2. Product description
MSD4 Vibration damper
2.1 Destination and use Kit consisting of: 8 vibration dampers 15 x 20 mm, 8 M5 cylinder head
The SLC 425I is a non-contact, self-testing safety guard, which is used screws with hexagon socket, 8 spring washers
for the protection of hazardous points, hazardous areas and machine
accesses. If one or more light beams are interrupted, the hazardous The MSD4 vibration damper kit must be used for damping vibrations
movement must be stopped. and oscillations on the SLG 425I. For applications with higher mechani-
cal stresses, e.g. presses, punching machines, we recommend the
The user must evaluate and design the safety chain in ac- MSD4 kit. In this way, the availability of the SLG 425I is increased.
cordance with the relevant standards and the required safety
level.
2.5 Technical data
Standards: EN 61496-1; CLC/TS 61496-2;
EN ISO 13849; EN 62061
Material of the enclosure: Aluminium
Number of beams: 2, 3, 4 beams
Protection field heights: 500 mm, 800 mm, 900 mm
Detection ability for test bodies:
2 beams with resolution 500 mm *3
3 beams with resolution 400 mm *3
4 beams with resolution 300 mm *3

2 EN
Operating instructions
Safety light grid SLG 425I
Response time: 2 - 4 beams: 2.8 Functions
15 ms (Standard) The system consists of a receiver and a transmitter. For the described
2 - 4 beams: 20 ms functions, no further switching elements are required. For the diagnos-
(beam coding A) tics and function selection, a user-friendly PC-software is offered as
Range of the protection field: 0,3 m - 18 m accessory. For the connection to a PC, the NSR-0801 BUS converter is
Rated operating voltage:24 VDC ±10% (PELV) supply unit to EN 60204 required (not included in delivery).
(power drop > 20 ms)
Operating current: 400 mA max. + 0.5 A The system has the following features:
(OSSD load + output signal quality load) • Start interlock
Wave length of the sensor: 860 nm • Restart interlock (manual reset)
Safety outputs (OSSD1, OSSD2): 2 x PNP-type semi-conductor, • Beam coding
short-circuit proof • Blanking of fixed protection field areas
Switching voltage HIGH¹: 15 … 28,8 V • Muting
Switching voltage LOW¹: 0…2V
Switching current: 0 … 500 mA 2.8.1 Factory setting
Leakage current²: 1 mA The system features many functions without needing any additional
Load capacity: 2 µF devices. The following table gives an overview of the possible functions
Load inductance: 2H and the factory settings configuration.
Admissible conduction resistance between OSSD and load: 2.5 Ω
Supply cable: 1Ω Function Factory setting Configuration
Input restart interlock (manual reset)
Input voltage HIGH (active): 17 … 29 V Restart interlock not active External wiring
Input voltage LOW (inactive): 0 … 2.5 V (manual reset)
Input current HIGH: 3 … 10 mA Fixed blanking not active With BUS converter NSR-0801
Input current LOW: 0 … 3 mA and PC-software
Function: Start and restart interlock (manual reset),
Muting active With BUS converter NSR-0801
fixed beam blanking and muting
and PC-software
Voltage: 24 VDC
Current: 500 mA Start interlock not active With BUS converter NSR-0801
Signal times and PC-software
Restart interlock (manual reset): 50 ms … 1.0 s signal transmission in Beam coding not active With BUS converter NSR-0801
case of trailing edge and PC-software
Start interlock: 250 … 1500 ms, adjustable
LED indications transmitter: Transmitting, status 2.8.2 Restart interlock (manual reset)
LED indications receiver: OSSD ON, OSSD OFF, restart, signal The restart interlock (manual reset) prevents an automatic enabling of
reception, blanking, multifunction the outputs (OSSD's ON state) after switch-on of the operating voltage
Connection: M12 Connector plug with metal thread, or an interruption of the protection field.
receiver 8-pole, transmitter, 4-pole (male), The system switches the outputs only to ON state, when an external
Muting sensors 2 pc. M8 3-pole, command device (restart button) generates an enabling signal at the
Muting lamp M8 3 pole restart input (receiver).
Ambient temperature: −10° C … +50° C
Storage temperature: −25° C … +70° C The command devices (enabling button) must be installed
Interface: Diagnostics and function setting outside of the hazardous area. The operator must have a
Protection class: IP67 (IEC 60529) clear view on the hazardous area when actuating the ena-
Resistance to vibrations: 10 - 55 Hz to IEC 60068-2-6 bling button.
Resistance to shock: 10 g; 16 ms; to IEC 60068-2-29
Year of construction: as of 2010 version 1.0
In supply condition, the restart interlock (manual reset) is
¹) To IEC 61131-2 not active. You must select an operating mode in order for
²) In case of failure, the leakage current at the most flows to the OSSD the outputs OSSD's to be enabled. If no type of protection is
cable. The downstream control element must recognise this state as selected, you will obtain the following signalisation through
LOW. A safety PLC must detect this state. the LED status indication in the receiver:
3
) resolution = beam distance + beam diameter 10 mm LED OSSD OFF (red) + LED restart (yellow) flashing

2.6 Response time (reaction time) 2.8.3 Start interlock


The response time depends on the hight of the protected field, the The start interlock prevents an automatic start of the machine when the
resolution, the number of light beams and the beam coding. supply voltage is switched on. After enabling of the start interlock - by
the one-time interruption of the protection field -, this protective function
Beam Beams Response Response time with Weight
is deactivated until the next power reset.
distance time beam coding A
[mm] [Number] [ms] [ms] [kg]
500 2 15 20 2.6 The start interlock is not activated upon delivery. This function
400 3 15 20 3.6 is activated by means of the NSR-0801 BUS converter and a
300 4 15 20 3.7 PC or laptop.

2.7 Safety classification


Standards: EN ISO 13849-1, EN 62061
PL: up to e
Control category: up to 4
PFH value: 7.42 x 10-9 / h
SIL: up to 3
Service life: 20 years

EN 3
Operating instructions
Safety light grid SLG 425I
2.8.4 Beam coding •T  he blanking of beams is not authorised for an SLG 425I
The beam coding of the safety light grid must be adjusted, when with 2 beams!
systems operating in each other's vicinity and a set-up as shown in the • The blanking of one beam at the most in the SLG 425I
image below (no interference) is impossible. When supplied, the beam 3-beam version or the SLG 425I 4-beam version is au-
coding is not active. With beam coding A, a receiver can distinguish the thorised, provided that the protective function is taken into
beams of the transmitter with the same beam coding A, which are des- account.
tined to this particular receiver, from foreign beams. The beam coding A • The blanking of multiple beams is not authorised.
must be set for each sensor (receiver and transmitter) individually. The • The remaining lateral areas must be protected against intru-
function is activated by means of the NSR-0801 BUS converter and a sion by means of mechanical covers.
PC or laptop. • The lateral covers must be fixed with the object. Partial cov-
ers are not authorised.
If adjacent systems are operated without beam coding, the user is at risk. • The restart interlock (manual reset) function of the safety
light grid or the machine must be activated.
no interference
E R R E The function is activated by means of the NSR-0801 BUS
converter and a PC or laptop. The activation of the function
is signaled by the blanking LED flashing in the diagnostic
window of the receiver.

2.8.6 Testing
Interference: beam coding required! The system performs a complete self-test and safety test within 2 sec-
onds after the operating voltage has been switched on. If the protection
E R E R field is not interrupted, the system switches to the ON condition.
In case of an error, the outputs at the receiver do not switch to the ON
state. The LED OSSD OFF starts flashing, thus emitting an error mes-
sage. Further indications can be found in the chapter Fault diagnostic.
During operation, the system continuously executes a self-test. Safety-
relevant faults are detected within the cycle time and cause the outputs
• The beam coding increases the safety and avoids mutual interference to be switched off.
of adjacent systems.
• The beam coding increases the immunity against optical interference 2.9 Operating mode muting
(e.g. sun light, welding sparks). 2.9.1 Adequate and appropriate application
• The beam coding A is permanently shown by the transmitter and the The objective of the by-pass function is the safe distinction between
receiver by means of flashing LED's (refer to LED status information). material and the presence of a person in front of the hazardous area. To
this effect, (2 or 4) additional sensors must be connected to provide for
On adjacent systems, the beam coding A must be used. a safe distinction between persons and the material to be transported.
The response time of the system is increased when beam
coding A is used. To this end, the safety distance must be To activate and parameterise the muting function, the
adjusted to the hazardous movement. Refer to chapter NSR-0801 BUS converter and the SLC4 PC software is
Response time. required.

2.8.5 Fixed blanking Special mounting instructions for muting


The SLC 425I can blank stationary parts in the protection field. All components must only be connected, wired and fitted by a special-
ist, who has sufficient electrical professional training and knowledge of
The fixed blanking range is authorised for individual beams in case of the harmonised safety regulations.
obstacles, taking the protective function into account. Testing and start-up by a qualified person, who has professional knowl-
edge as well as in particular knowledge of the harmonised legal and
governmental regulations.
Instruction and training of the operators by an expert on the application.
4 Fixed blanking area

3
2
1
E1 R1

Access to lateral areas must be prevented by means of


mechanical covers!

The first beam line, which realises the optical synchronisation and is
located immediately behind the diagnostic window, cannot be blanked.

The area of the fixed blanking must not be modified after the teach-in
process. Any change of the area or removal of the part from the protec-
tion field will be detected by the system. As a result, the outputs are
disabled (locked). This locking can be neutralised by executing a new
teach-in process in accordance with the actual beam interruptions.

4 EN
Operating instructions
Safety light grid SLG 425I
After connection and fitting by an expert, the following instructions must A new muting process can only be started when the previous is termi-
be respected and observed: nated (all sensors not actuated). A safety distance of at least 50 mm
• Set-up of the sensors to the operating instructions SLG 425I. The mut- (belt speed V < 2.0 m/s) must be observed with regard to the protection
ing function must not be started by a person unintentionally accessing field, in order to ensure a safe signal evaluation by the control system.
the hazardous area. The sensors must be set up so that a normal
approach by a body part, e.g. foot, leg, hand, arm movement does not Installation of the muting sensors
activate the muting mode. If 4 muting sensors are used, the switching outputs of the muting
• The selection of the operating parameters, e.g. simultaneity, muting sensors MS 1 and MS 3 as well as MS 2 and MS 4 must be wired in
time, operating mode, special functions, etc. must be adjusted to the parallel. MS 1 and MS 3 are connected to the MS1/MC female connec-
application, e.g. termination of the muting cycle after passing through tor on the sensor connection plate. MS 2 and MS 4 to the MS 2 female
the protection field. connector.
• The muting cycle must be started automatically after the command de-
vice is enabled and be controlled by at least two independent signals
(sensors). Sensor connection:
• The command device for the enabling and override function must be with 2 + 24VDC
set up so that the operator has a clear view on the entire hazardous muting sensors MS 1 MS 2
area. The mounting position must be selected so that the device can-
not be actuated at the hazardous point.
• The muting state can be signalled through a muting lamp.

The muting function must only be used for automatic material


transport to protect the accesses to the hazardous area. In
this way, the material passes through the accesses and the MS 1 MS 2
protection field of the SLG 425I without disabling the outputs. SLG 425I sensor connection
This function is only authorised for the above-described ap-
plication. For other applications, no warranty claims shall be with 4 + 24VDC
accepted. muting sensors
MS 1 MS 3 MS 2 MS 4
This document includes information for the adequate and
proper by-passing of the protection field of an ESD and is
reserved to persons, who have the necessary expertise and
technical know-how. The users of this document must be able
to adequately and correctly evaluate the risks involved in this
operating mode.
MS 1 MS 2
This document does not provide all technical know-how, SLG 425I sensor connection
which is required in conjunction with this operating mode.
To this effect, the harmonised governmental and legal provi-
sions regarding the technical know-how must be obeserved. The muting sensors must be arranged so that any uninten-
tional access or penetration of a person into the hazardous
area is prevented. When positioning the muting sensors,
Definitions: the distance and the height must be choses so that a clear
Muting: specific intended brief by-passing of the outputs of an distinction is made between material and a person!
ESD in case of automatic material transport
2.9.3 Muting lamp
Muting sen- sensor for the uniform recognition of material
The operating mode "muting" can be signalled through an external mut-
sor: ing lamp. This lamp must be connected to the sensor connection plate
Muting lamp: the muting lamp signals the muting state (ML) through a connection with a 3-pole connector socket. The muting
Override: the function enables the material transport after an lamp is not monitored! I.e. the electrical connection and the included
exceptional stop of the muting cycle. illuminant are not checked by the control system of the SLG 425I.
Belt speed: the muting running time is stopped as long as the
"belt stop" signal is active The muting lamp signals the following operating modes:

Muting lamp Signal Note


2.9.2 Muting sensors MS ON Continuous signal Muting cycle active
The MS muting sensor can be a mechanical, capacitive, inductive or OFF Muting cycle not active
optoelectronic sensor. They have no particular requirements as fail- Flashing 2 Hz Muting cycle error or over-
safety is regarded. The set-up must be executed tamper-proof. When
ride mode
reflexion light barriers are used, the sensors and reflectors must be
arranged alternately to avoid mutual interference. When optoelectronic
sensors are used, the switching outputs must be set to dark operation If the muting lamps are flashing, the following failures can be present:
(sensor actuated = 24 VDC). • Muting cycle time exceeded
The sensors must be arranged so that the transported material part is • Belt stopping time exceeded
detected without any interruption over the entire length. The sensors • Sequence or simultaneity of the signal conditions of the muting sen-
must detect the material, not the carrier. sors not observed
The distance of the sensors must not be too large, so that all acti-
vated muting sensors are actuated by the travelling material during a
cycle. The simultaneity (max. 3 sec.) of the switching outputs must be
observed.

EN 5
Operating instructions
Safety light grid SLG 425I
Illuminant Operating mode set-up for muting mode:
For the muting lamp, a LED block with a lifetime of approx. 50 000 After the correct connection of the muting sensors and the NSR-0801,
operating hours must be used as admissible illuminant. The utilisation the following parameters must be set by means of the PC software in
of MK2 type muting lamps is recommended. the "muting function" menu field in accordance with your application.

2.9.4 Signal sequence muting

*1
MS 1 *2

MS 2 *1
*2
ML *1
*2

Muting*1
*2

t
t<3s t<3s

*1: active
*2: inactive

MS1 MS3 MS2 MS4


Operating mode and transport direction
First choose the operating mode and the transport direction (set-up and
number of the muting sensors).

MS1 MS2 Muting with 2 sensors, diagonal arrangement


• Muting variante with 2 crosswise arranged muting sensors
Sensor group 1 Sensor group 2 • Transport direction: material transport in both directions (factory set-
ting)
Parameter setting: muting mode with 2 sensor groupes (4 muting sen- • Selectable options: belt stop, reduced muting cycle, override, protec-
sors), direction detection 1, premature termination not active tion field area

The muting function is activated after first MS 1 (first sensor group) and
subsequently MS 2 (second sensor group) is actuated by the material
(direction detection 1). The material first actuates the proteciton field
of the SLG 425I, after that MS 3 (first sensor group) and finally the MS
4 (second sensor group). The muting cycle is cancelled, when MS 3
(second sensor group) is no longer actuated.

2.9.5 Configuration of the muting function


The parameters for the muting mode are set by means of the PC soft-
ware: SLC 4 Kunde.exe

To this effect, the NSR-0801 BUS converter must be connected to the


SLG 425I and a PC or laptop. Please use the NSR-0801 BUS converter
manual for the connection.

6 EN
Operating instructions
Safety light grid SLG 425I
Muting with 2 sensors, parallel arrangement Simultaneity of the sensors
• Muting variante with 2 muting sensors The timeframe between the first and the second muting sensor is
• Transport direction: out of the hazardous area, reduced muting cycle monitored. In this way, a uniformly-shaped transport good can be distin-
(factory setting) guished from other switching times (passing by of a person) in case of
• Selectable options: belt stop, override, protection field area an adequate arrangement of the muting sensors.
The simultaneity setting must take variations in the belt speed, as well
The use of 2 parallel arranged sensors is only authorised for as the position and length tolerances of the material into consideration.
outward material transport, i.e. the transport of material out
of the hazardous area. The muting sensors must be installed The simultaneity of the sensors can be set between 1 to 3 seconds.
inside the hazardous area.
Setting the special functions is recommended. In this way, the
Muting with 4 sensors, parallel arrangement protective function and the availability of the muting application is
• Muting with each time 2 symmetrically arranged sensors before and increased.
after the protection field of the SLG 425I.
• Transport direction: material transport in both directions selectable Restart interlock (manual reset)
• Selectable options: belt stop, reduced muting cycle, override, protec- The restart interlock (manual reset) prevents an automatic belt start
tion field area after voltage interruption or material jamming.
The restart interlock (manual reset) must be wired as shown in the wir-
Muting cycle time ing diagram (chapter 4). The function is active upon delivery.
The muting cycle time is the time expiring between the moment of The command device must be installed outside of the hazardous area,
activation of the muting until the inward or outward material transport in so that the operator has a clear view on the area.
the hazardous area is completely terminated. The command device must be actuated after any interruption of the
The muting cycle time depends on the length of the material, the belt voltage or the protection field or fault of the muting cycle. Enabling is
speed and the sensor arrangement. only possible, when all muting sensors are not actuated. The signalling
The time must be defined so that the material can travel by all sensors for the actuation of the command device is realised by a status LED on
within the muting cycle time (enabling of all muting sensors). Before a the receiver.
new muting cycle can be initiated, all sensors must be clear (no actua- The function can be deactivated by removing the check mark in the
tion). software. By doing this the following operating condition is created:
the outputs OSSD's are released, when all light beams and the muting
The muting cycle time can be set from a few seconds up to multiple sensors are not interrupted (light path clear). The same applies after an
hours. Longer muting cycle times can result in hazardous operating interruption of the voltage supply. A release through the command de-
conditions. The muting cycle time must take variations in the belt speed vice is only required after a malfunction (muting cycle fault). The owner
as well as position and length tolerances of the material into considera- then must secure this function through the application.
tion.
The deactivation of the "restart interlock (manual reset)" func-
Reduced muting cycle tion can trigger an automatic muting cycle. In this way, per-
A normal muting cycle is terminated by a muting sensor in the following sons can access/penetrate into the hazardous area. Persons
way: within the hazardous area are exposed to severe injuries.
• Muting with 2 sensors, diagonal arrangement after enabling of muting
sensor MS 2 Belt stop
• Muting with 4 sensors, parallel arrangement after enabling of muting The function can extend the muting cycle time in case of a belt stop or
sensor MS 3 material jamming, thus preventing a premature shutdown. In this way,
the muting function can be extended until the failure/belt stop is recti-
For very long muting cycle times, this results in a time window with fied. After that, the normal muting cycle can be completed.
bridged protection field, as long as the material is located between the
protection field and the muting sensor MS 2/MS 3. The machine control makes the belt stop input available as signal. The
function is activated by switching on 24 VDC at pin 8 of the receiver. A
By activating the function "reduced muting time", the muting cycle is status change of the muting sensors (switching output) when the func-
shortened/reduced. The muting cycle is terminated, when the material tion is active, causes the muting function to be switched off.
has travelled by the protection field of the SLG 425I (protection field
clear). The function is deactivated upon delivery. The belt stop time can be set
from 1 to 30 minutes.
This field is always activated when applied with 2 parallel arranged
muting sensors. For applications with 2 diagonally arranged MS or 4 Override
parallel arranged MS, the function can be activated by means of the This function enables bridging the outputs of the SLG 425I in case of
software. failure (voltage interruption, material jamming). The function is limited in
time and exclusively reserved to the elimination of the material jamming
A new muting cycle can only be started, when all muting sensors are no (muting sensor or protection field actuated).
longer actuated.
The function is activated by means of the command device (restart
interlock enabling). The command device must be actuated in the se-
quence ON-OFF-ON. The time-related sequence for the start (ON-OFF-
ON) with a minimum duration of 100 ms up to the maximum duration of
1.5 sec. must be observed. If the material jamming is eliminated (pro-
tection field and muting sensors no longer actuated), the outputs of the
SLG 425I are locked. To start a new muting cycle, the command device
(enabling of the restart interlock) must be actuated one time (ON-OFF).
The muting lamp starts flashing (2 Hz) to signal the interruption of the
muting cycle. The function is not activated upon delivery.

EN 7
Operating instructions
Safety light grid SLG 425I
Multiple interruption of the protection field during the muting cycle
This function increases the availability of the system in case of different
material qualities on one pallet.

Without the function "multiple interruption of the protection field", the


protection field is monitored during the active muting cycle and any non-
actuation (no beam interrupted) immediately cancels the muting cycle.
This error function is triggered when all active beams of the protec- This saving procedure is recommended so that configuration changes
tion field are not actuated for a period of time of over 20 ms e.g. due can be reproduced at a later moment. Click the (yes) button with your
to an irregular loading of the material on the carrier. If the function is mouse to confirm.
activated, no shutdown is triggered if the beams are not actuated during
the muting cycle. The correct termination is realised by the configura- You now can save the configuration setting onto your PC or laptop.
tion or the muting sensors. The combination with the parameter setting
"reduced muting cycle" is not possible. These restrictions are marked in 2.9.7 Muting applications
the software and must be observed.
Arrangement of the muting sensors
Activating the protection field
During a muting cycle, the entire protection field height of the SLG 425I
is bridged. This causes the risk that persons located on or beside the
material can get into the hazardous area. Muting lamp
The risk can be avoided by activating the remainder of the protection
MS2 MS3
field, if the conveyed material has a throughout identical height. In this
way, the presence of persons within the active protection field height is
detected!
Material MS1

Procedure: MS4
Position the material onto the carrier so that the protection field of
Belt
the SLG 425I is actuated. If the material height is slightly varying, the
carrier can be slightly increased during the teaching process to avoid
false triggering. Now activate the teach sample field in the software. Reflector
Reflektor
The menu automatically switches to the beam view. The beams inter-
Muting
Mutingsensor
Sensor
rupted by the material are represented in red. The teaching process is
terminated with a mouse click on the "teach" field. You will return to the SLG
SLC425I-E/R
425I-E/R
main menu "muting".
Carrier
MS1 MS2 S MS3 MS4
Changing the protection field area
If the protection field height parameterised by means of the teach
process needs to be changed, the saved value must be deleted and Belt
reparameterised.
Material
Procedure:
Activating the entire protection field (the previous value is deleted)
Activating the teach sample (change to beam view)
Saving the new value (teach process) with teach
S3 E
Mounting:
The first light beam (near the diagnostic window) must not be S2 S1 S1 S2
interrupted! I.e. observe the downward cable connection.

2.9.6 Saving the data SF = Protection field


After the reconfiguration, the data to be saved are prepared by select- S1 = distance of the inner MS to SF
ing the button "Save settings". To avoid any unintentional saving of S2 = distance between two MS
data, every intentional saving process must be confirmed within 10 S3 = material length
seconds by clicking on the button "Confirm with this button within 10 MS 1 = Muting sensor 1
seconds". MS 2 = Muting sensor 2
If it is not confirmed within this timeframe, the settings that were saved MS 3 = Muting sensor 3
before the change was made will be maintained without any change. MS 4 = Muting sensor 4
S = Transmitter
After the data transmission, the following confirmation is displayed. You E = Receiver
are simultaneously asked to save the configuration data in the form of
a text file. Minimum distances muting sensors
For the evaluation of the signals (MS) in the control system, a minimum
distance is required for the muting sensors.

The minimum signal length between the sensors, which are fitted
closest to the SLG 425I, must be at least 50 ms. This corresponds to a
minimum distance of 100 mm at a belt speed of 2.0 m/s.

The minimum signal length of the outer sensors must exceed 50 ms.
The signal running time between the muting sensors must be 3 sec-
onds at the most (depending on the chosen setting).

8 EN
Operating instructions
Safety light grid SLG 425I
The mounting distance of the inner sensors to the protection field of the Muting with 2 sensors, diagonal arrangement
SLG 425I must be chosen as small as possible. The arrangement shows the muting application with two diagonally
(crosswise) arranged muting sensors. This arrangement enables the
The sensors (transmitter/receiver) of the SLG 425I must be fixed as material to be transported in both directions.
close as possible to the conveyed material to avoid the creation of
gaps. Otherwise, there is a risk that persons can slip between the mate- Schematic representation
rial and the MS arrangement into the hazardous area during the muting Additional safety guard
Hazardous point
cycle. Carrier
S
In case of different material widths, the gap between the sensors (trans-
mitter/receiver) of the SLG 425I and the material must be protected with Belt
an additional cover.
Material
Muting with 2 sensors, parallel arrangement
The arrangement shows the muting application with two parallel ar-
ranged muting sensors. This arrangement enables the material to be
transported in only one direction, out of the hazardous area.
MS2 E MS1
Schematic representation
Additional safety guard
Hazardous point
S3 S1 S2
Carrier MS2 MS1 S S1 = distance MS 1 to SF
S2 = distance MS 2 to SF
Belt S3 = material length
MS 1 = Muting sensor 1
Material
MS 2 = Muting sensor 2
S = Transmitter
E = Receiver
VB = belt speed (m/s)
S3 SF = Protection field
E
S2 S1
The intersection of the muting sensors must always be within
the hazardous area!
S1 = distance MS 1 to SF
S2 = distance MS 1 to MS 2 S3 > S1 + S2
S3 = material length S1 = belt speed VB (m/s) x 0,05 s
MS 1 = Muting sensor 1
MS 2 = Muting sensor 2 In the schematic diagram, the arrangement of the muting sensors is
S = Transmitter represented with a larger distance to enable a uniform identification of
E = Receiver the sensor sequence. Please observe the smallest possible distance
VB = belt speed (m/s) of the MS to the transported material. The distance of MS 1 and MS
SF = Protection field 2 to the protection field of the SLG 425I must be chosen as small as
possible as well.
S3 > S1+S2
S1 = belt speed VB (m/s) x 0,05 s The muting cycle is as follows: MS1 - MS2 - SF - MS2 - end
Selectable options: belt stop, reduced muting cycle, override, protection
The muting cycle is as follows: MS2 - MS1 - SF - end field area
Factory setting: material transport in both directions
Selectable options: belt stop, override, protection field area
Factory setting:reduced muting cycle, i.e. the muting cycle is terminated The muting sensors must be arranged so that a uniform sequence of
when the protection field is released. the muting sensors is ensured.

This arrangement is only authorised when the muting sensors


are installed inside the hazardous area.

EN 9
Operating instructions
Safety light grid SLG 425I
Muting with 4 sensors, parallel arrangement 3. Mounting
The arrangement shows the muting application with four parallel ar-
ranged muting sensors. This arrangement enables the material to be 3.1 General conditions
transported in both directions. The following guidelines are provided as preventive warning notices
to ensure a safe and appropriate handling. These guidelines are an
Carrier essential part of the safety instructions and therefore must always be
MS1 MS2 S MS3 MS4 observed and respected.

Belt • The SLG must not be used on machines, which can be


stopped electrically in case of emergency.
Material • The safety distance between the SLG and a hazardous ma-
chine movement must always be observed and respected.
• Additional mechanical safety guards must be installed so that
the operator has to pass by the protection field to reach the
hazardous machine parts.
S3 E • The SLG must be installed so that the personnel always
must be within the detection zone when operating the ma-
S2 S1 S1 S2 chine. An incorrect installation can lead to serious injuries.
• Never connect the outputs to +24VDC. If the outputs are
wired to +24VDC, they are in ON state, as a result of which
S1 = distance of the inner MS to SF they are unable to stop a hazardous situation occuring on the
S2 = distance between two MS application/machine.
S3 = material length • The safety inspections must be conducted regularly.
MS 1 = Muting sensor 1 • The SLG must not be exposed to inflammable or explosive
MS 2 = Muting sensor 2 gasses.
MS 3 = Muting sensor 3 • The connecting cables must be connected in accordance
MS 4 = Muting sensor 4 with the installation instructions.
S = Transmitter • The fixing screws of the end caps and the mounting angle
E = Receiver must be firmly tightened.
VB = belt speed (m/s) • Additional measures could be required to ensure that the
SF = Protection field electro-sensitive device does not present a dangerous
breakdown, when other forms of light beams are available in
S3 > 2(S1 + S2) a special application (e.g. use of wireless control devices on
S1 = belt speed VB (m/s) x 0,05 s cranes, radiation of welding sparks or effects of stroboscopic
lights).
The muting cycle is as follows: MS1 - MS2 - SF - MS3 end
MS4 - MS3 - SF - MS2 end 3.2 Protection field and approach
Selectable options: belt stop, reduced muting cycle, override, protection The protection field consists only of the available individual beams with
field area a distance of 300, 400 or 500 mm. Additional protective devices must
Factory setting: material transport in both directions ensure that hazardous machine movements can only be reached after
passing through the protection field.
The muting figure with each time 2 muting sensors shows a symmetri-
cal arrangement before and after the protection field of the SLG 425I. The SLG must be installed to so that the hazardous area is completely
protected, if necessary by means of additional safety guards.

The safety distance before the hazardous point to the SLG safety
guard must be imperatively respected. The safety distance enables the
presence of persons within the hazardous area. Therefore, it must be
ensured that the hazardous movement can only take place, when no
persons are inside the hazardous area anymore. The legal and govern-
mental provisions must be observed for the operation and use. These
provisions are usually region- and country-dependent.

The command devices (enabling button) must be installed


outside of the hazardous area sot hat any operation from
within the hazardous area is prevented. The operator must
have a clear view on the hazardous area, when actuating the
command device (enabling button).

3.3 Alignment

Procedure:
1. The transmitter and the receiver must be fitted parallel to each other
and at the same height.
2. Turn the transmitter and monitor the diagnostic window of the re-
ceiver. Fix the light grid, when the LED OSSD ON (green) is on and
the LED signal reception (orange) is off.
3. Determine the max. rotating angle to the left and to the right, at which
the LED OSSD ON (green) is on and tighten the mounting screws in
central position. Make sure that the LED signal reception (orange) is
not on or flashing.

10 EN
Operating instructions
Safety light grid SLG 425I
3.4 Safety distance To calculate the minimum distances of the safety guards with
The safety distance is the minimum distance between the SLG 425I regard to the hazardous point, the EN ISO 13855 and EN
and the hazardous point, which must be observed in order to ensure ISO 13857 must be observed.
that the hazardous point can only be reached after the hazardous If an overlap of the protection field is possible, take care to
movement has come to standstill. the calculation of the safety distanca refering to additional
CRO according to the table A1 as per norm EN ISO 13855.
The protection using individual beams must be chosen so
that bodies or body parts larger than the selected resolution 3.4.1 Minimum distance to reflecting surfaces
(beam distance + beam diameter 10 mm) of the SLG 425I are During the installation, the effects of reflecting surfaces must be taken
detected. into account. In case of an incorrect installation, interruptions of the
protection field could possibly not be detected, which could lead to
Calculation of the safety distance to EN ISO 13855 and serious injuries. The hereafter-specified minimum distances with regard
EN ISO 13857 to reflecting surfaces (metal walls, floors, ceilings or parts) must be
imperatively observed.
The safety distance depends on the following elements:
•R
 un-on time of the machine (calculation by run-on time measurement) Access direction
•R
 esponse time of the machine and the safety light grid and the down-
stream relay (entire safety guard) Transmitter Receiver
Obstacle
•A
 pproach speed
•R
 esolution of the safety light grid
optical axis

8° 5°

Calculation of the safety distance for the safety light grid: a=130mm
a= 262 mm
S = (K 1600 mm/s x T ) + C
reflecting body
S=S  afety distance [mm] (e.g. Material container)
T=R  un-on time of the machine + reaction time of the safety light grid Limit of the hazardous point
K = Approach speed 1600 mm/s
C=S  afety supplement 850 mm

Example:
Reaction time of the SLG 425I = 10 ms Table: Safety distance to reflecting surfaces a depending on the aper-
Run-on time of the machine T = 170 ms ture angle

S = 1600 mm/s * (170 ms + 10 ms) + 850 mm a [mm]


S = 1138 mm
1000
900
The following mounting heights must be observed: 800
700
600
500
Number of beams Mounting height above reference floor in
400
300
mm 200
100
2 400, 900 D [m]
0 3 5 10 15 20
3 300, 700, 1100
4 300, 600, 900, 1200
 Calculate the minimum distance to reflecting surfaces as a function of
the distance with an aperture angles of ± 2.5° degrees or use the value
from the table below:
The safety distance between the safety light grid and the
hazardous point must always be respected and observed. If Distance [m] between Minimum distance a
a person reaches the hazardous point before the hazardous transmitter and receiver [mm]
movement has come to standstill, he/she is exposed to seri- 0.2 … 3.0 130
ous injuries. 4 175
5 220
7 310
Safety distance to the hazardous area
10 440
15 660
Transmitter
Formula: a = tan 2.5° x L [mm]
Direction from which the
hazardous area is accessed
S a = Minimum distance to reflecting surfaces
Hazardous
L = Distance between transmitter and receiver
point

Receiver
Command device
Authorised operation

Mechanical protection

The formulae and calculation examples are related to the vertical set-up
(refer to drawing) of the safety light grid with regard to the hazardous
point. Please observe the applicable harmonised EN standards and
possible applicable national regulations.

EN 11
Operating instructions
Safety light grid SLG 425I
3.5 Dimensions SLG425I-ER-0800-03-RF (3-beam version)
All measurements in mm.
A B C L2 L1
SLG425I-ER-0500-02-RF (2-beam version) Trans- Re- Trans- Re- Trans- Re-
mitter ceiver mitter ceiver mitter ceiver
A B C L2 L1
400 948 1012 948 1048 203 139 249
Trans- Re- Trans- Re- Trans- Re-
mitter ceiver mitter ceiver mitter ceiver
500 648 712 684 748 303 239 349

L2
80
6.05
L2
80

6.05

86
Receiver 161 /97Transmitter 97

Receiver 150 / Transmitter


Receiver 150 / Transmitter 86

86
Receiver 161 / Transmitter 97

49.6 48.7
A
B
C

49.6 48.7
B
C

A
51
31.5

42
51

L1
31.5

42

Legend
L1

A = Beam distance
B = Mounting dimension
Legend C = Total length
A = Beam distance L1 = Mounting distance (mm) between floor and slotted hole centre
B = Mounting dimension (short end cap)
C = Total length L2 = Mounting distance (mm) between floor and slotted hole centre
L1 = M ounting distance (mm) between floor and slotted hole centre (diagnostic window)
(short end cap) *All measurements ± 1 mm
L2 = M ounting distance (mm) between floor and slotted hole centre
(diagnostic window)
*All measurements ± 1 mm

12 EN
Operating instructions
Safety light grid SLG 425I
SLG425I-ER-0900-04-RF (4-beam version) Accessories
A B C L2 L1
Fixing kit MS-1030
Trans- Re- Trans- Re- Trans- Re- The fixing kit consists of 4 steel angles and 16 fixing screws.
mitter ceiver mitter ceiver mitter ceiver 20
300 1088 1152 1124 1188 203 139 209

6,5

18,9

42
L2

14,5
80
6.05
40

32
86
Receiver 161 / 97Transmitter 97

Receiver 150 / Transmitter

52
86

Centre fixing MS-1051 (optional accessory)


Mounting kit consists of 2 steel angles, 4 screws and 4 T-slot nuts for
central fixing
40
20
49.6 48.7
A
B
C

18,9

42
14,5
A

32
38
A

20
51
31.5

42

L1

Legend
A = Beam distance
B = Mounting dimension
C = Total length
L1 = Mounting distance (mm) between floor and slotted hole centre
(short end cap)
L2 = Mounting distance (mm) between floor and slotted hole centre
(diagnostic window)
*All measurements ± 1 mm

EN 13
Operating instructions
Safety light grid SLG 425I
4. Electrical connection

4.1 Wiring example Muting

+ 24VDC Sensor connection:


MS 1 MS 2 with 2 muting sensors

MS 1 MS 2
+ 24VDC with 4 muting sensors
MS 1 MS 3 MS 2 MS 4

MS 1 MS 2
(WH)

2 4 1 3 5 6 1 8 2 7 3 4
(BK) (BK)

(PK) (PK)

Freigabe/Override (WH)
(BN) (BN)

(BN) (BN)
IN (WH)

(RD)(RD)
IN (GY)

OSSD 1 (GN)1 (GN)

OSSD 2 (YE)2 (YE)


Release/Override
(BU) (BU)

(BU) (BU)
DIAG OUTOUT

DIAG OUTOUT
+24 VDCVDC

+24 VDCVDC
stop
DIAG IN (WH)

DIAG IN (GY)

Bandstopp
VDC

VDC

OSSD

OSSD
DIAG

DIAG

DIAG

DIAG

Belt
+24

+24
0 VDC

0 VDC
0

Bridge
Brücke 11
für Diagnose
diagnostic

S1 MK
K1 K2
Only forNur

E1

Earth
Erdung connection

Bridge 1: Restart interlock (manual reset) active (bridge between DIAG 4.2 Connector configuration Receiver, Emitter & Cable
OUT and DIAG IN) RECEIVER Signal
Legend SLG: connector Designation Description
K1, K2: Relay for processing the switching outputs OSSD 1,OSSD 2 M12 / 8 pole male
MK: Machine contact belt stop (optional)
S1: Command device button for enabling restart/override 5 1 WH Release/Override Input

E1: Power supply 24 VDC ± 10% 6 4 2 BN


3 GN
24 VDC
OSSD 1
Power supply
Safety output 1
4 YE OSSD 2 Safety output 2
7 3 5 GY Diagnostic IN Input diagnostic data
6 PK Diagnostic OUT Output diagnostic data
1 8 2 7 BU 0 VDC Power supply
8 RD Belt stop Input
Cable: Connector
M12 / 8 pole female
5
4 6
3 7
2 8 1

14 EN
Operating instructions
Safety light grid SLG 425I
TRANSMITTER Signal 4. The double insulation between the light grid output and an external
SLG: connector Designation Description potential is guaranteed.
M12 / 4 pole male 5. The outputs OSSD1 and OSSD2 are not connected to +24 VDC.
1 BN 24 VDC Power supply 6. The connected switching elements (load) are not connected to +24
4 3 2 WH Diagnostic IN Input diagnostic data VDC.
3 BU 0 VDC Power supply 7. If two or more SLG are used within close range compared to each
4 BK Diagnostic OUT Output diagnostic data
other, an alternating arrangement must be observed. Any mutual
interference of the systems must be prevented.
1 2
Switch the SLG on and check the operation in the following way:
The component performs a system test during approx. 2 seconds after
Cable: Connector
the operating voltage has been switched on. After that, the outputs are
M12 / 4 pole female enabled (if the protection field is not interrupted). The LED "OSSD ON"
of the receiver is on.
3 4
In case of incorrect functioning, please follow the instructions
listed in the chapter Fault diagnostic.

2 1
5.2 Maintenance

Do not use the SLG before the next inspection is terminated.


The colour codes are only valid for the cable types mentioned An incorrect inspection can lead to serious and mortal inju-
below "optional accessories". ries.

Sensor connection field Conditions


For safety reasons, all inspection results must be archived. The operat-
ing principle of the SLG and the machine must be known in order to
MS1 / MC MS2 ML be able conducting an inspection. If the fitter, the planning technician
and the operator are different persons, please make sure that the user
has the necessary information at his disposal to be able conducting the
maintenance.

5.3 Regular check


A regular visual inspection and functional test, including the following
steps, is recommended:
MS1/MC = Muting sensor 1/machine contact MC 1. The component does not have any visible damages.
MS 2 = muting sensor 2 2. The optics cover is not scratched or soiled.
ML = Muting lamp 3. H azardous machinery parts can only be accessed by passing
through the protection field of the SLG.
Muting sensors PIN No. Signal Description 4. The staff remains within the detection area, when works are con-
ducted on hazardous machinery parts.
4 1 +24 VDC Power supply 5. The safety distance of the application exceed the mathematically
calculated one.
3 1 3 0V Power supply
Operate the machine and check whether the hazardous movement
4 +24 VDC Switching output sensor stops under the hereafter-mentioned circumstances.
6. H azardous machine parts do not move when the protection field is
interrupted.
Muting lamp PIN No. Signal Description 7. The hazardous machine movement is immediately stopped, when
the protection field is interrupted with the test rod immediately before
4 3 0V Power supply the transmitter, immediately before the receiver and in the middle
between the transmitter and the receiver.
3 4 +24 VDC Switching output muting 8.No hazardous machine movement when the test rod is within the
lamp protection field.
9 The hazardous machine movement comes to standstill, when the volt-
age supply of the SLG 425I is switched off.

5. Set-up and maintenance 5.4 Half-yearly inspection


The following items must be checked every six months or when a ma-
5.1 Check before start-up chine setting is changed.
Prior to start-up, the following items must be checked by the responsi-
ble person. 1. M achine stops or does not inhibit any safety function.
2. N o machine modification or connection change, which affects the
Wiring check prior to start-up safety system, has taken place.
1. The voltage supply is a 24V direct current power supply, which meets 3. The outputs of the SLG are correctly connected to the machine.
the CE Directives, Low Voltage Directives. A power downtime of 20 4. The total response time of the machine does not exceed the re-
ms must be bridged. sponse time calculated during the first putting into operation.
2. Presence of a voltage supply with correct polarity at the SLG. 5. The cables, the connectors, the caps and the mounting angles are in
3. The connecting cable of the transmitter is correctly connected to the perfect condition.
transmitter and the connecting cable of the receiver correctly to the
receiver.

EN 15
Operating instructions
Safety light grid SLG 425I
5.5 Cleaning
If the optics cover of the sensors is extremely soiled, the OSSD outputs
can be disabled. Clean with a soft cloth without exercising pressure.
The use of agressive, abrasive or scratching cleaning agents, which
could attack the surface, is prohibited.

6. Diagnostic

6.1 LED status information

Receiver Function LED colour Description


Multifunction green Function display, beam coding
Multifunction Restart
Blanking blue Protection field(s) inactive (blanking)
Blanking OSSD OFF
Signal reception OSSD ON Signal reception orange Evaluation of the signal reception
Restart yellow Input for command device
OSSD OFF red Safety outputs signal condition OFF
Protection field OSSD ON green Safety outputs signal condition ON

Transmitter Function LED colour Description


Transmitting orange Transmitter active
Status green Function display, beam coding
Transmitting Status

Protection field

Receiver
LED Status LED Description
OSSD ON ON Protection field clear
Flashing Diagnostic mode active
OSSD OFF ON Protection field interrupted, system or configuration error
Flashing Diagnostic mode active, error output refer to Fault diagnostic table
Restart ON Start or restart interlock (manual reset) active, signal expected at output WA
Signal reception ON/flashing Signal reception too low, check alignment and installation height between
transmitter and receiver
Cleaning the black profile cover
OFF Alignment between transmitter and receiver OK
Blanking 1 flashes Fixed blanking of the protection field(s)
Multifunction 1 flashes Muting (complete protection field)
2 flashes Muting (only teached protection field)
3 flashes Muting through BUS control
4 flashes reserved
5 flashes Beam coding A is active

Transmitter
LED Status LED Description
Transmitting ON Standard operation, transmitter active
Flashing Configuration error
Status Flashing Beam coding A is active

16 EN
Operating instructions
Safety light grid SLG 425I
6.2 Fault diagnostic
The light grid performs an internal self-test after the operating voltage is switched on and the protection field is enabled. When a fault is detected, a
corresponding flashing pattern is emitted at the receiver through the LED OSSD OFF (red). Every fault emission is followed by a one-second pause.

LED OSSD OFF Fault feature Action


OSSD OFF and LED restart Wiring error for function selection Check connection at the receiver, bridge 1 or
continuous flashing (Restart interlock (manual reset), automatic bridge 2 must be wired (refer to Wiring)
mode)
1 flashes Error at sensor receiver Replace receiver

2 flashes Error contactor control OFF Check connections at contactor control input, refer to
Wiring, check wiring of the auxiliary contacts
3 flashes Error contactor control ON Check wiring at contactor control input, short-circuit at +UB and
mass. Power reset after fault rectification.
4 flashes Errors at the OSSD outputs Check the wiring of the outputs, OSSD for short-circuit at +UB and
mass
5 flashes Error configuration data Check the configuration settings by means of the NSR-0801 BUS
converter
6 flashes Error blanking The receiver has detected blanked beams as beams without inter-
ruption, i.e. locking. Check the configuration settings by means of the
NSR-0801 BUS converter, repeat the teach process with blanking.

6.3 Extended diagnostic


By means of the optional configuration software and the NSR-0801 8. Appendix
BUS converter, an extended diagnostic can be executed. The software
provides the status information of the component and can represent the 8.1 Contact
individual light lines. This feature enables an optimal adjustment of the Consultancy / Sales:
light grid. The diagnostic mode is signalled by the OSSD ON and OSSD K.A. Schmersal GmbH
OFF LED‘s at the receiver. In diagnostic mode, protective mode is Industrielle Sicherheitsschaltsysteme
disabled, the ODDS outputs being locked. The change from diagnostic Möddinghofe 30
mode to protective mode is automatically realised after Power Reset, D-42279 Wuppertal
when the BUS converter is no longer integrated and the connecting Tel:+49 (0) 202 64 74 -0
cable of the sensor is reconnected. Fax:+49 (0) 202 64 74- 100

You will also find detailed information regarding our product variety on
our website: www. schmersal.com

7. Disassembly and disposal Repair handling / shipping:


Safety Control GmbH
7.1 Disassembly Am Industriepark 11
The safety switchgear must be disassembled in a de-energised condi- D-84453 Mühldorf / Inn
tion only. Tel.: +49 (0) 8631-18796-0
Fax: +49 (0) 8631-18796-1
7.2 Disposal
The safety switchgear must be disposed of in an appropriate manner in
accordance with the national prescriptions and legislations.

EN 17
Operating instructions
Safety light grid SLG 425I
Appendix

8.2 EC Declaration of conformity

EC Declaration of conformity
Translation Safety Control GmbH
of the original declaration of conformity Am Industriepark 33
84453 Mühldorf / Inn
Germany
Internet: www.schmersal.com

We hereby certify that the hereafter described safety components both in its basic design and con-
struction conform to the applicable European Directives.

Name of the safety component / type: SLG 425I

Description of the safety component: Safety light grid

Harmonised EC-Directives: 2006/42/EC - EC-Machinery Directive


2004/108/EC - EMC-Directive

Applied standards: EN 61496-1:2004 + A1 2008


CLC/TS 61496-2:2006
EN ISO 13849-1:2008; PL e
EN 62061:2005; SIL 3

Person authorized for the compilation Ulrich Loss


of the technical documentation: Möddinghofe 30
42279 Wuppertal

Notified body for the prototype test: TÜV Nord Cert GmbH
Langemarckstr.20
45141 Essen
ID n°: 0044

EC- test certificate: n° 44 205 10 555867 005

Place and date of issue: Mühldorf, February 1, 2010


SLG 425I-B-EN

Authorised signature Authorised signature


Christian Spranger Klaus Schuster
Managing Director Managing Director

The currently valid declaration of conformity can be down-


loaded from the internet at www.schmersal.net.

Safety Control GmbH


Am Industriepark 33
D-84453 Mühldorf / Inn

Telefon +49 - (0)86 31 - 187 - 9 60
Telefax +49 - (0)86 31 - 187 - 9 61
E-Mail: [email protected]

18 EN

You might also like