alle etee1e Government of India
grax Fad Northern Railway,
Away aiataa, aster
war
No. 10/W/O/Poiley/Building New Delhi, Dated 13 July 2016
C Engineer's Circular No. 629
Sub: Standardization of heights/dimensions/elearances for fixtures /littings/clement
buildings and overall planning of building,
1.0 Necessity for high quality architectural and functional design of buildings needs no fresh
emphasis. However. it is noted that this aspect is not being paid due attention as noted
from the buildings constructed during the recent years. in terms of utility, function and
architectural design. Many of the architectural elements, sanitary-ware, bath and kitch
fittings, faucets, kitchen platforms, shelves, ete. are being provided without payin
adequate attention to their functional requirement. This leads to discomfort and
inconvenience to the user.
24) Knowledge of Anthropometry (relationship between the human body and movement of
the body with things and spaces that it comes in contact in day to day life) is extremely
important in deciding layout, space requirement and dimensions of various components
of any building, Some basic structural and functional dimensions of an average human
body are piven in ANNEXURE-1
3.0 Based on common experience and as per figures given in “Fundamentals of
ceture for Railway Civil Engineers Volume-l IRICEN”, some of the
recommended dimensions, clearances, heights, etc. are tabulated below. for guidance:
Yable:1
S.No. | Architectural Fixture/Pitting/Flement. | Height/Dimension/Clearance
| | From floor level in mm
| Lop of Kitchen platform | 800 |
| 2 | Minimum clear opening below slab of kitchen | 680
platform to accommodate a cooking der |
3 | Lop edge of kitchen sink 740
1 | Height of Pap in kitchen ground sink 400
5 | Height of Range Hood! Vent Hood from | 60010 750
| kitchen’s working top |
6 | Height of Ventilator 300 mm below Slab or |
| Just below bottom of Beam,
7 | Front top edge of wash hand basin 850
Vision Statement
Failure Free, Restriction Free, Refreshing, Speedy Travel and Creation of Aesthetically Sound, Quality
Structures in Green, Clean, Enlivening Environment”
Engg, Deptt /NR10
1M
{ie
B
4
1s
16
7
18
| 19
20
21
2
24
25
26
| ie
28
Failure Free, Restriction Free, Refreshing, Speedy Travel and Creation of Aesthetically Sound, Quality
Height of Dado
| Height of Skirting
| Top of partitions for urinals
| Lip of urinal for gentlemen
Bottom edge of reflecting surface of
mittor fixed behind wash basin
| Height of Rod of towel rail from floor level
Bottom of shower rose
| Height of Stop cock for shower rose
| Height of Tap in water closet
Minimum size of Water Closet
Minimum size of Water Closet for disabled
Minimum size of Bathroom
Minimum size of Bathroom for disabled
Minimum size of toilet in staff quarter
Maximum size of toilet in staff quarter and rest
houses
Slope in Bathroom floor
Height of Tap in bathroom
Licight of Tap in bathroom-if used for
taking bath sitting on floor, below the tap
Bottom of ceiling fan
| Height of Window AC from floor level
ht of Split AC from floor level (avoid beam
and lintel for fastener/installation inner unit)
| Maximum size of bed room in staff quarter and
| rest houses in rectangular shape
Top of railing in balcony
Top of stair case railing (measured
from edge of nosing of steps)
Clearance between ceiling fan and
ling
Projection of tap in bathroom
Projection of shower
Distance between centre of W. C. and
adjacent wall
in front of W. © (Commercial use
only)
Depth of wardrobe
vision Statement
Structures in Green, Clean, Enlivening Environment”
900 (in corridors)
1200 (WC)
1500 (in toilet)
100 or 150
1300
700
1300
900
2000
1000
220
1000 « 1200
1500 x 1750
1200 = 1500
1500 * 1650
1650 » 2400
3000 « 2000
1: 150
| 700
| 1100
| 2600
900 to 1200
2100 to 2400
| 4500 = 4000
| 900
850
300 min.
200
| soo
450
600
0038 | Height of Plinth above the likely ground/floor | 600 (for quarters, barrack:
level expected in future (minimum) Godown, Workshop,
Station building (halt,
way-side & crossing),
shelter for porters, electric
| sub-station, for
| Mechanised Laundry)
39 | Plinth of service Buildings at platform To be decided based on High
| Level Platform
| 40. | Floor to floor height (minimum) 3300 (barrack, booking &
| office at halt, way-side &
crossing station)
3600 (lor Quarter, running
room, booking office.
godown, workshop, duty
bunk)
4600 (for waiting hall at halt,
way-side, crossing station)
| 41 | Slope in roof | min, 1:80
1.0. Besides above, the following should also be taken note of, during, constru
buildings:
a) Inkitchen, upper storage shelf is at a height of 450mm from working top except at sink.
Clear height at sink of upper shelf to be kept 600mm from working top.
b) A bag shelf of 300x200 to be
bags et
«d at suitable place in toilet for ladies purse, brief case.
for satety of luggage of toilet users.
©) To hang coat, over coa ete.; a hanger should be provided for convenience of toilet
users
di) Allefforts should be made to leave no space between new planned building and existing
building, IF'itis felt necessary to provide space/passage between buildings. minimum 6.1
m may be left in between,
ht & mi
e) Atleast one fit hei
imum 1500mm wide cupboard/almirah should be provided
in rooms of staff quarter.
In drawing room of staff quarters and in visitors room of the rest house show casebook
shelerockery display unit/chest drawers
to be provided.
2) Adequate attention to be paid for deciding the layout of furniture and furnishing while
deciding the layout of building, In this regard, sample drawing given at fig-4 para 203i)
of IRWM correction slip no. 10 to be referred to.
h) Adequate attention to be paid for deciding the electric layout for the building. In this,
regard, sample drawing given at fig-8 para 203(i) of IRWM correction slip no. 10 and
Vision statement
Failure Free, Restriction Free, Refreshing, Speedy Travel and Creation of Aesthetically Sound, Quality
Structures in Green, Clean, Enlivening Environment”
Engg. Ovptt./NRn of swich boards/points for lights
JPO on "Concealed electrical/telecom wiring, loc:
and fan ete, its plan and execution in buildings including composite Tender” CF circular
620, to be referred to.
) Roof ofa building shall invariably be projected at least 230 mm beyond outermost wall.
i) An Apron of width 900 mm (min) to be laid all around the building at natural ground
level in order to protect plinth and keep area, surrounding the building. clean.
ke) Pipe lines for inlet and outlet to over head water storage tanks be kept 75mm to 150mm
above terrace floor and should be placed along the parapet wall for facilitating smooth
flow of rain water and free movement for terrace users.
1) Down comer (soil & waste pipes) should be enclosed & should not be visible in
clevations.
in) Over Head Water Storage Tank should he kept at mumty roof or 3°0" (1000mm) above
terrace floor at suitable place for adequate water pressure in toilets and kitcher
nh) To overcome to inadequacy of surface water. to enhance avalibity of ground water, to
inhance infilteration of rain water in the sub-soil_ & in decline of ground water levels,
Rain Water Harvesting is required to be provided in buildings (Advance correction slip
nno.10 of IRWM),
rable, the green covers is to be provided at the rate of 15% to 20% of total land.
0) Itis des
rs and tre:
p) A staircase shall have all its ri of uniform height and width in all the
a
(i) Height of riser shall not be more than 150 mm in residential building and 125 mm in
commercial building.
(ii) Width of tread shall not be less than 300 mm in resident
ing dimension in mind.
shts. It should be planned accordingly keeping following lim
al building and 360 mm in
commercial building.
5.0. A few sketches showing sample layouts and detailing of some of the structural
ings are enclosed as ANNEXURE-2, for
sidance
components and
6.0 Any change warranted may be allowed by Sr. DEN/Co, /Dy. CE/Const. depending on the
the reasons and advising the same
demand of occasion/site requirements after recordin
to the undersigned.
This has the approval of Principal Chief Et
Ra
(PANKAJ SAXENA)
CHIEF ENGINEER/P&D
vision Statement
“yailure: Free, Restriction Free, Refreshing, Speedy Travel and Creation of Aesthetically Sound, Quality
Structures in Greon, Clean, Enlivening Environment”
Enge. Deptt /NFunctional Body DimensionsANNEXURE - 2 (SHEET NO. 1
2100 ———+
=a
ras
HIMNEY,
es /OODEN
CABINETS:
/OODEN
CABINETS:
4 []_—oish store
CABINETS
—TAP
INK
tal
SECTION AT C-C
PLAN
KITCHEN
GAS STOVE
i
RAINE —#"
Sao,
SECTION AT D-D
|RANITE FINISHING.
OVER SLAB
RECOMMENDED DIMENSIONS / CLEARANCES OF VARIOUS COMPONENTS OF KITCHENANNEXURE - 2 (SHEET NO. 2)
wre vores
cam | rama
GUNZED THES: A sn [SHOWER ROSE
eros crm
: ey
sinc costa —| pot 1. s0 coosr
Gwe
i Z eo es
‘eto
I
: as
‘Mw. FLOORING TLES 29m
‘CONER THAN HOUSE FLOOR
SECTION ATB
aS ee
Lorrsue ¢
raat 7) ial
cumones ||]
To aouait,
usin astern
wa
sts ooene Tues
{oer in nose Looe
SECTION AT A (Western WC) SECTION ATC
LLM
PLAN (URINAL FITTING)
RECOMMENDED DIMENSIONS/CLEARANCES OF VARIOUS COMPONENTS OF BATH & WC ©850 ‘
HEIGHT OF RAILING
ANNEXURE - 2 (SHEET NO. 3)
RAILING
300
150,
RECOMMENDED DIMENSIONS OF STAIRCASE (TREAD,
RISER & RAILING)