SDLC
Caterpillar Digital Voltage Regulator (CDVR)
0. Communications
1. Principles of Voltage control
2. Modes of Operation
3. Wiring
4. Features
5. Protections
6. Reference Numbers
SDLC
0. Communications
Cat PC Software;
RS-232 direct port.
Electronic Technician;
CAN DATA LINK P9-1,P9-2.
SDLC
1. Principles of Voltage control
T0 T1 T2 T3
OUT REF
VR
Excitation Field
L4
L1
Field L2
L3 Armature
Diode
Field
Stator
Alternator Exciter
SDLC
1. Principles of Voltage control
PID
VR
ERROR
INPUT OUTPUT
∆V ALTERNATOR V, f
V setting Excitation Field
RETROFEED
V actual
SDLC
1. Principles of Voltage control
How to set the Voltage Setting:
PC Software
AVR Voltage (V) …
in “Settings” screen, “Setpoint” tab, “Setpoint” box.
Raise/Lower buttons …
in “Metering” screen, “Fine Adjustment” box.
Externally
Raise/Lower momentary switch
± 10 VDC Auxiliary Supply
CAN DATA LINK
SDLC
1. Principles of Voltage control
Power supply to the CDVR
Self excited
T0 T1 T2 T3
Remnant magnetism
L4 L1
Field L2
L3 Armature
Diode
Field
Stator
T0 T1 T2 T3
Permanent magnetism
L4 L1
Permanent
Field
L3
L2
Armature
Diode
magnet
Field
Stator
L5
SDLC
2. Modes of Operation
Automatic Voltage Regulation
PF Control
VAR Control
Reactive
Power (kVAR)
Pf= cos ω
ω
Real power (kW)
SDLC
3. Wiring
(1) 6-pin connector “P6”
(2) LED Indicator
(3) 12-pin connector “P12”
(4) 9-pin connector “P9”
(5) 9-pin D-sub Connector “J4”
Note: Items 1, 3 & 4 are Molex
brand Connector plugs
SDLC
3. Wiring
SDLC
4. Features
4.1 PID Settings
4.2 Soft Start
4.3 Load profile
4.4 Voltage Drop
4.5 Voltage Droop
SDLC
4. Features
4.1 PID Settings
SDLC
4. Features
4.2 Soft Start
V
100% Vn
Soft Start Bias
Hz
100% fn
1 V/Hz Standard Startup Profile
SDLC
4. Features
4.3 Load Profile
100% Vn
Min V
0
0Hz Min f 100%Hz
SDLC
Worst situation, no help to the engine
3508B, 800kW in one block with:
Knee f =45
Slopes 1and 2 = 0
Min V =50 %
Min f =20 Hz
SDLC
Maximum help to the engine
3508B, 800kW in one block with:
Knee f =50
Slopes 1and 2 = 10
Min V =50 %
Min f =20 Hz
SDLC
Somewhere in the middle
3508B, 800kW in one block with:
Knee f =49
Slopes 1 = 2; Slope 2 = 4
Min V =50 %
Min f =20 Hz
SDLC
4. Features
4.4 Voltage Drop
Used when a single genset is working providing voltage to a load at a certain
distance.
In this case, as the power demand from the load increases ( current through the
cables grows), the voltage losses on the line increases.
We can program on the voltage regulator an increase in the voltage setting according
to the load.
400 v 397 v
Line losses
LOAD
SDLC
4. Features
4.4 Voltage Drop
With Voltage Drop
V
Without Voltage Drop
V Genset Output Voltage
Genset Output Voltage Voltage Drop
Voltage Drop Compensation
LOAD Voltage
LOAD Voltage
LOAD
LOAD
0% LOAD 100% LOAD 0% LOAD 100% LOAD
SDLC
4. Features
4.5 Voltage Droop
Used when paralleling gensets to help the Reactive Load Sharing between them.
We can program on the voltage regulator a decrease in the voltage setting according
to the reactive load.
V
4 % Voltage Droop
416 V Notice that the effects of “Line
Voltage Droop
Genset Output Voltage Drop”and “Droop”are just opposite,
400 V
that is why we can not select them
together.
REACTIVE LOAD
0% 100% Reactive Load
SDLC
5. Protections
SDLC
Questions ???