22 Dimension of switchgear cubicle :
width (max) mm 750
depth (max) mm To be mentioned
height (max) mm To be mentioned
23 Test certificate report : To be submitted
Issued by
Reference No.
Date of test report
24 Weight (exclude C.B. Switchgear) kg To be mentioned
C. 20 KV CURRENT TRANSFORMER
i) 20 KV CURRENT TRANSFORMER FOR
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
4
INCOMING
FEEDER
1 Manufacturer
2 Type Indoor
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio, class, rated output :
(a) for differential protection and for
REF protection :
Ratio A 200/1
Class X
Output VA .......
(b) for O/C and E/F protection :
Ratio A 200/1
Class - 5P20
Output VA 10 s/d 15
(c) for instrument and metering :
Ratio A ---------
Class - 0.2
Output VA 10 s/d 15
6 Rated short time current kA, 1 sec. 20
7 Knee point voltage V
8 Rated continuous thermal current A 630
9 Weight kg To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
5
(c) for instrument and metering :
Ratio A ---------
Class - 0.2
Output VA 15
6 Rated short time current kA, 1 sec. 20
7 Knee point voltage V
8 Rated continuous thermal current A 630
9 Weight kg To be mentioned
D. 20 KV POTENTIAL TRANSFORMER
1 Manufacturer
2 Type To be mentioned
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio, class, output :
for busbar and tap changer control,
under-voltage
relay :
Ratio V/V 20000:√3/100:√3/
100:√3
class of accuracy of secondary - 0.2
class of accuracy of tertiary - 3P
output of secondary VA 100
output of tertiary VA 15
6 Weight kg To be mentioned
7 Catalog, drawing or other references - To be submitted
E. PROTECTION
i) DIFFERENTIAL RELAY
1 Manufacturer To be mentioned
2 Type of Differentialrelay To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
6
Earth fault element % of CT To be mentioned
rating
4 Range of timing settings at 10 x CT sec. To be mentioned
rating
5 Burden of relay at 10 x CT rating sec. To be mentioned
6 Percentage of current setting at % To be mentioned
which relay will reset
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
7
viii) UNDERVOLTAGE RELAY
1 Manufacturer To be mentioned
2 Type of relay To be mentioned
3 Number of stage To be mentioned
4 Voltage range V To be mentioned
5 Voltage adjustment step V To be mentioned
6 Time delay range Sec. To be mentioned
x) 20 KV FUSES
1 Manufacturer To be mentioned
2 Type To be mentioned
3 Nominal voltage kV 20
4 Highest system voltage kV 24
5 Rated current A ----
6 Current characteristic - To be mentioned
7 Weight kg To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
8
horn off - Yes
Accept - Yes
Reset - Yes
lamp test - Yes
13 To be installed into control cubicle - Yes
as specified
G. AC AMMETER
1 Manufacturer To be mentioned
2 Type To be mentioned
3 Quantity to be measured :
AC (3 x 1 phase with selector switch) 1 phase
4 Class of accuracy - 1
5 Range of indication A 0-1200; 0-2400
0-300 ; 0-600
6 Effective range To be mentioned
7 Rated operating conditions :
rated current A 5
rated voltage V 100
rated internal resistance To be mentioned
rated resistivity of separate To be mentioned
resistance
rated transformation ratio of CT A/A To be mentioned
rated power consumption VA To be mentioned
8 Minimum creepage distance To be mentioned
between live
conductor and earthed case
9 Protection degree IP3x
10 Size mm To be mentioned
11 Type of instrument mechanism To be mentioned
12 Scale characteristics :
scale length To be mentioned
scale pattern : - linear To be mentioned
- non-linear To be mentioned
scale with overload range To be mentioned
max. scale value A 0-1200; 0-2400
0-300 ; 0-600
13 Vibration strength N To be mentioned
14 Mounting position - Flush
15 Circuit of rectifier :
full wave bridge current To be mentioned
full wave shunt current To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
9
center-tapped circuit with current To be mentioned
transformer
16 Design of case - Square
(round/square/rectangular)
17 Color of case To be mentioned
18 Error of indication (absolute error) To be mentioned
19 Relative error in % To be mentioned
20 Limit of temperature rise ref. - 40 °C at 100 %
ambient temperature humidity
21 Weight per instrument kg To be mentioned
22 Catalog, drawing or other references - To be submitted
23 Type test Certificate - To be submitted
24 Sample test Report - To be submitted
H. AC VOLTMETER
1 Manufacturer To be mentioned
2 Type To be mentioned
3 Quantity to be measured : V
AC (3 x 1 phase with selector switch) - phase to phase
and phase
to neutral
4 Class of accuracy - 1
5 Range of indication kV 0 - 25
6 Effective range To be mentioned
7 Rated operating conditions :
rated current To be mentioned
rated voltage : V 100
rated internal resistance
rated resistivity of separate
resistance
rated transformation ratio of VT kV/kV 20:√3/0.10:√3
rated power consumption VA To be mentioned
8 Minimum creepage distance To be mentioned
between live
conductor and earthed case
9 Protection degree IP4x
10 Size mm To be mentioned
11 Type of instrument mechanism - To be mentioned
12 Scale characteristics :
scale length To be mentioned
scale pattern : - linear To be mentioned
- non-linear To be mentioned
scale with overload range To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
10
max. scale value kV 30
13 Vibration strength N To be mentioned
14 Mounting position - Flush
15 Design of case To be mentioned
(round/square/rectangular)
16 Color of case To be mentioned
17 Error of indication (absolute error) To be mentioned
18 Relative error in % To be mentioned
19 Limit of temperature rise ref. - 40 °C at 100 %
ambient temperature humidity
20 Weight per instrument kg To be mentioned
21 Catalog, drawing or other references - To be submitted
22 Type test Certificate - To be submitted
23 Sample test Report - To be submitted
I. WATTMETER
1 Manufacturer To be mentioned
2 Type To be mentioned
3 Quantity to be measured : MW
AC (3 phase, 1 phase) - 3 phase
Balanced Yes
Unbalanced Yes
DC -
4 Class of accuracy 1
5 Range of indication MW As required
6 Effective range
7 Rated operating conditions :
rated current A 5
rated voltage V 100
rated power consumption VAmax
rated transformation ratio of :
voltage transformer kV/kV 20:√3/0.10:√3
current transformer A/A To be mentioned
Ohmic resistance of :
current path To be mentioned
voltage path To be mentioned
- inductance of current path To be mentioned
8 Minimum creepage distance To be mentioned
9 Protection degree IP4x
10 Size mm To be mentioned
11 Type of instrument mechanism To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
11
(number of wattmeter elements)
12 Scale characteristics : Multi scale
scale length To be mentioned
scale pattern linear, 0-point at Yes
central position
scale with overload range To be mentioned
max. scale value MW To be mentioned
13 Vibration strength N To be mentioned
14 Mounting position - Flush
15 Design of case - Square
(round/square/rectangular)
16 Color of case To be mentioned
17 Error of indication (absolute error) To be mentioned
18 Relative error in % To be mentioned
19 Limit of temperature rise ref. - 40 °C at 100 %
ambient temperature humidity
20 Weight per instrument kg To be mentioned
21 Catalog, drawing or other references - To be submitted
22 Type test Certificate - To be submitted
23 Sample test Report - To be submitted
J. VARMETER
1 Manufacturer To be mentioned
2 Type To be mentioned
3 Quantity to be measured : MVAR
AC (3 phase, 1 phase) - 3 phase
Balanced Yes
Unbalanced Yes
DC -
4 Class of accuracy 1
5 Range of indication MVAR To be mentioned
6 Effective range To be mentioned
7 Rated operating conditions :
rated current A 5
rated voltage V 100
rated power consumption VAmax Yes
rated transformation ratio of :
voltage transformer kV/kV 20:√3/0.10:√3
current transformer A/A To be mentioned
- Ohmic resistance of :
- current path To be mentioned
- voltage path To be mentioned
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
12
- inductance of current path To be mentioned
8 Minimum creepage distance To be mentioned
9 Protection degree IP4x
10 Size mm To be mentioned
11 Type of instrument mechanism To be mentioned
(number of wattmeter elements)
12 Scale characteristics : Multi scale
scale length To be mentioned
scale pattern linear, 0-point at Yes
central position
scale with overload range To be mentioned
max. scale value MVAR To be mentioned
13 Vibration strength N To be mentioned
14 Mounting position - Flush
15 Design of case - Square
(round/square/rectangular)
16 Color of case To be mentioned
17 Error of indication (absolute error) To be mentioned
18 Relative error in % To be mentioned
19 Limit of temperature rise ref. - 40 °C at 100 %
ambient temperature humidity
20 Weight per instrument kg To be mentioned
21 Catalog, drawing or other references - To be submitted
22 Type test Certificate - To be submitted
23 Sample test Report - To be submitted
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
13
12 Peak asym. short circuit current kA To be mentioned
13 Rated transformation ratio kV/kV 20:√3/0.10:√3
14 Protection degree IP4x
15 Kind of installation To be mentioned
16 Basic meter design (register) kWh
17 Type of register construction Digits 6 +1
18 Mounting position - Flush
19 Vibration strength N To be mentioned
20 Calibration error in % at 100 % % To be mentioned
balance load,
cos phi = 1
21 Max. permissible ambient To be mentioned
temperature rise
22 Design of case - Rectangular
(round/square/rectangular)
23 Color of case To be mentioned
24 Weight per instrument kg To be mentioned
25 Catalog, drawing or other references - To be submitted
26 Type test Certificate - To be submitted
27 Sample test Report - To be submitted
28 Official meter calibration Certificate - To be submitted
This document is the property of Angkasa Pura II. It must not be stored, reproduced or disclosed to others without written
authorization from Angkasa Pura II.
Doc. No.: LAPI-APII-SST7-GEN-DC-004
14