Mul-Prc004-E4 - 08012007 Raup
Mul-Prc004-E4 - 08012007 Raup
Features Summary 6
Quantum Climate Changer Dimensional Chart 7
Outdoor Unit Application Considerations 8
Equipment Selection 9
Wiring Diagrams 42
Mechanical Specifications 48
Dimensional Drawing Condensing Unit 49
1
Model Number Description
(Raup - TTV)
DIGIT 1,2,3 Remote Condensing Unit / Air-Cooled / Up- DIGIT 1,2 Indoor Unit / Cooling Only
Flow
DIGIT 3 Air Flow Configuration
DIGIT 4 Development Sequence V = Vertical Discharge
DIGIT 5,6,7 Nominal Cooling Capacity [MBH] DIGIT 4,5,6 Nominal Cooling Capacity [MBH]
250 = 250 400 = 400 600 = 600 250 = 250 400 = 400 600 = 600
300 = 300 500 = 500 300 = 300 500 = 500
2
General Data 200 - 620 MBH
Condensing Units
Notes:
[1] at 7deg C SST and 35 deg C Ambient, 400V, Subcooling 8.3K, Superheat 11.1K
[2] Per Motor @ 400V
[3] Per Circuit
[4] Minimum Circuit Ampacity (MCA) is 125% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the condenser fan FLA.
[5] High Ambient and Low Ambient Options Available.
3
General Data Indoor (Blower
Coil) Units
TTV 250 TTV 300 TTV 400 TTV 500 TTV 600
Evaporator Coil Rows/FPF 3/144 3/144 3/144 4/144 4/144
Evaporator Rated Air Flow Cfm 7760 9240 12120 15130 18080
Cmh 13180 15700 20590 25700 30720
Configuration Vertical with vertical fan discharge configurations
Face Area Sq. ft/m2 16.7/1.55 19.2/1.78 26.2/2.44 34.8/3.24 37.98/3.53
Tube Material Copper
Tube Type Smooth
Tube Size (OD) in/mm 3/8 / 9.5 3/8 / 9.5 3/8 / 9.5 0.5 / 12.7 0.5 / 12.7
No. Of Circuits 1 1 2 2 2
Refrigerant Flow Control TXV
Drain Connection Size in 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4
Evaporator Fan/Motor
Drive Type Belt
FLA/LRA (each) (2) 8/42 12/82 12/82 16/104 23/153
No of Motors Std. HP(kw) 1-5(3.7kw) 1-7.5(5.5kW) 1-7.5(5.5kW) 1-10(7.5kw) 1-15(11kw)
Hi Static 10(7.5) 15(11) 15(11) 20(15) 20(15)
Diameter of Fan in/mm 15.7/400 15.7/400 15.4/390 17.7/450 17.7/450
Width of Fan in/mm 12.6/320 12.6/320 15.4/390 14.2/360 14.2/360
No of Fans 1 1 2 2 2
Indoor Fan Type Centrifugal FC
Fan Pulley Pitch Diameter mm 224 224 224 250 250
Air Qty. - Max cfm 8900 10600 13800 16700 21800
- Min cfm 5900 7000 9100 11000 14400
Fan Motor Type TEFC 400V/ 3P/ 50Hz
Std. Fan Speed (Std. Factory Set) 850 900 900 760 760
@ ESP including filters in /Pa 1.1/275 1/250 0.9/225 1.5/375 1.1/275
Max. Allowable Fan RPM 1100 1100 1200 1000 1000
Motor Pulley Pitch Diameter mm 140.0 140.0 140.0 132 132
Filters
Size (Qty) in (8) 16x20(4) 15x20, (2) 16x20 (6) 16x25(2) 16x20, (1) 20x25 (3) 20x20
Std. 1” Washable (1) 16x25, (2) 15x25 (3) 20x25(6) 16x25, (3) 25x25 (6) 20x25
Suction Line OD in 2 1/8" 2 1/8" 1 5/8" 2 1/8" 2 1/8"
Liquid Line OD in 7/8" 7/8" 7/8" 7/8" 7/8"
Approx. Operating Weight lbs/kg 778/353 928/421 1073/487 1510/685 1651/749
Unit Dimensions HxWxD mm 1219x1808x1040 1372x1808x1040 1520x2088x1040 1653x2596x1275 1777x2596x1275
Trane double walled Quantum Climate Changer Air Handlers are available for semi custom configurations and specialized
indoor conditions.
4
System Performance Matrix
Capacities based on ambient temperature of 95 F [35 C]. Coil on coil temperature of 80 / 67 F [26 / 19 C] EDB/EWB.
Rated at 400V / 3P / 50Hz
Capacities are gross and do not include the evaporator fan motor heat deduction
Custom Matches & configuration are available with the Trane Quantum Climate Changer air handler.
5
Features Summary
Features Summary
Features Benefits
Scroll Compressors o Less vibration and a Quieter Operation o Advanced & reliable refrigerant & oil management
o Durability / Extended Life Built in dirt saperator to technology for large scroll compressors.
prevent dirt reaching the bearings High volume o Low friction and high volumetric efficiency
oil sump prevents excessive oil loss.
efficiency achieved by ensuring orbiting scrolls,
o Comprehensive Compressor Protection for orbit on an oil flim that minimizes friction &
added reliability. wear, and at the same time ensuring absolute
o Tandem Capability Achieves high part load radial tightness. Radial contact is minimized via
efficiencies and additional part load control. opposing floating seals.
o High emergy efficiency ratio and outstanding
endurance
Smart Controls Simple but sophistacated control using ensures maximum compressor protection
microprocessor technology enables: against cycling.
* temperature setpoints and zone temperatures * Fully factory packaged starters enable the
to be fed to the controller for optimized comfort installer to power up, charge, pipe and run the
cooling with minimum installation downtime. system with minimum site electrical installation.
* Diagnose problems accurately and swiftly * Special intergrated system level control using
minimizing downtime. system level Trane ICS.
* Preprogrammed compressor sequencing
Safeties & Protection All condensing units come standard with: o Reverse rotation protection on compressors
o Compressor overheat , overcurrent and phase through safeties that trip the system on high
loss protection . temperature.
o High and low pressure safety switches to o Compressor time delays and on-off sequencing
protect the system against operations outside logic that is built into the microprocessor
recommended pressure limits. algorithm for maximum protection.
o Stainless Steel & Corossion Resistant Coated o Corossion resistant coated coils as an option.
Robust Casing external bolts.
o High efficiency Trane slit fin coils.
o Weather resisant baked matt polyester powder
painted GI panels.
o Heavy gauge welded steel base with mounting
holes.
Modular Installation o Modular designs allow for side by side installation o Small footprint saves valuable footprint and
to save valuable space. costly transportation.
Pre Matched Compact Air Handlers o Small foot print o Closed cell PE
o Multiple fan arrangements. Vertical or horizontal insulation.
discharge configurations. o Double Inlet Double Width Forward curved fans
o Up to 2.5”[625Pa] ESP o Standard 25mm washable air filters.
o Baked Polyester Powder Painted GI panels for o Oversized motor options for higher static
an attractive long lasting finish. operation.
Custom Matched Quantum Climate Changer o Highly flexible double walled 25mm or 50 mm o Suitable for back up cooling with chilled water
indoor or outdoor Quantum Climate Changer Air systems.
Handler (QCC)
o 100% fresh air selections possible with the
QCC.
6
Quantum Climate Changer
Capacity Chart
Note:
1 Cooling capacities are based on EDB 26.7 C /EWB 19.4 C and 7 deg C SST, 51.7 dec C Condensing Temp.
2 Cooling capacities reflected above are not based on a system match.
3 For actual custom system capacity with Trane condensing units, please refer to your local Trane
representative.
4 Please refer to the dimensional chart belro for standard Trane Quantum Climate Changer dimensionsAll
dimennsions.
7
Outdoor Unit Application
Considerations
8
Equipment Selection
9
FORM 050.40-ES3 (204)
the air and the liquid refrigerant, and the amount of air
passing over the coil.
Equipment
abilitySelection
Once the refrigerant has completely evaporated, its
to cool the air decreases dramatically. If too
little refrigerant is fed to the coil, it will evaporate
LD09136
FIG. 2 - EVAPORATOR COIL TYPES quickly and the air will not be adequately cooled.
EVAPORATOR
If too much refrigerant is fed to the coil it will not
Horizontal Verticle Intertwined As the liquid refrigerant passes evaporate
FORM 050.40-ES3at
through all and
(204) liquid refrigerant
refrigerant willrow
gas in the last return to the
or two
Split Coils Split Coils Coils
The evaporator coil removes heat from
the coil thetubes,
supply compressor. Direct expansion (DX) evaporator coils
heat is tranferred from of the coil tubes. The refrigerant gas
the air
the and the liquid
supply air Therefrigerant,
stream to and
the the amount of air
air-stream, cooling the supply air in the process.
passing over the coil. are refrigerant.
designed to evaporate is superheated to ensureinit the
all refrigerant does
coilnotand
As heat is added to the liquid condense back to its liquid state in the
evaporator coil generally consists of several rows of then “superheat ”suction the refrigerant gas in the last row or
refrigerant,
Once the refrigerant it has
begins to evaporated,
completely evaporate its line. Superheat is also used to
copper tubing mechanically bonded to much aluminum
ability tolike
coolwater (or
the air boiling
decreaseson two of coilIfThe
a stove.
dramatically. tubes.
too The refrigerant
control the expansion gasdevice.
is superheated to
copper) heat transfer
FIG. 2 - EVAPORATOR COIL TYPES
ns. Depending on
little the size
refrigerant
liquid-vapor
LD09136 and
ismixture
fed to the coil,ensure it does
it will evaporate
remains at a not condense back to its liquid state in
FIG. 2 -EVAPORATOR COIL TYPES quickly and the air will not be adequately cooled.
capacity
EVAPORATOR
of the coil it may consist ofIf one,
constant
too muchor several
temperature
refrigerant is fed toand
the
the pressure
suction
coil it will line.
not EXPANSION
Superheat DEVICE
is also used to control the
refrigerant circuits (see Fig. 2). until it completely
evaporate at all and liquidvaporizes
refrigerant will(for R22),
return to the
EVAPORATOR
The evaporator coil removes heat from the supply
expansion device.
while for R407C the temperature and
compressor. Direct expansion (DX) evaporator coils The expansion device controls the flow
air-stream, cooling the supply air in the process. The are designed to evaporate all refrigerant in the coil and
evaporator coil generally consists of several rows of
pressure will drop slightly due to the of liquid refrigerrant to the evaporator
then “superheat ” the refrigerant gas in the last row or
A
The refrigerant
evaporatordistributor
coil removes on
copper tubing mechanically bonded to aluminum (or
each
heatDXglide evaporator
of the
two of coil
coil The
refrigerant.
tubes. The refrigerant
EXPANSION
gas coil capacity
is superheated to
DEVICE
coil. Trane uses temperature
from
circuit
copper) the
heat supply
transfer air-stream,
feeds low
ns. Depending cooling
pressure,
on low
the size the
and temperature
is determined
ensure it does notliquid
by theback
condense typeto and amount
its liquid state in controlled, (thermostatic) expansion
supplyof the
capacity
refrigerant aircoilinit may
to the
coilprocess.
consist
ItThe
of one, or several the suction
of line. Superheat
refrigerant theThe
used,is also used toexpansion
control the
temperature device(TXVs)
valves controls the flow
as shown in Fig.of
3. liquid
The
(see the tubes. is critical that all the
refrigerant
evaporator circuits coil Fig.generally
2). consists expansion device. refrigerant to the evaporator coil. YORK uses
ofdistributor tubes of
several rows are copper
the same lengthdifference
tubing
between the air and the
so the pressure TXV has two primary components: the
A refrigerant distributor on each DX evaporator coil liquid DEVICE and thetemperature
refrigerant,
EXPANSION amount of air controlled, (thermostatic)
valve body expansion
and the sensing bulb. valves
dropfeeds
across
mechanically
circuit them will
bonded
low pressure, be equalliquid
to temperature
low aluminum and
(or thepassing
refrigerant
over willcoil.
the
The expansion device controls (TXVs)
the flow ofas shown in Fig. 3. The TXV has two primary
liquid
be evenly
copper)
refrigerant thedistributed
toheat transfer
coil isto
tubes. Itfins. the coil
Depending
critical that all tubes.
the
refrigerant to the evaporator coil. YORK uses The valve regulates the flow of refrigerant
distributor tubes are the same length
on the size and capacity of the coil so the pressure
Once thecontrolled,
temperature refrigerant
components:
has expansion
(thermostatic) completely
valves
thetovalve body and the sensing bulb.
the evaporator coil. As refrigerant
drop across them will be equal and the refrigerant will
it
beAs may consist of one, or several (TXVs) as shown in Fig. 3. The TXV has two primary
evaporated, its ability to cool the air passes through the valve it is
thedistributed
evenly liquid torefrigerant
the coil tubes. passes through the coilthetubes,
components: valve body and the sensing bulb.
refrigerant circuits (see Fig. 2). decrease dramatically. The valvelittle
If too regulates the flow
adiabatically of refrigerant
expanded to the
(that is, without
Asheat is transferred
the liquid refrigerant passes from thecoilsupply
through the tubes, air stream to the ofevaporator
heat is transferred from the supply air stream to the
refrigerant
The valve regulates is fed to the
the flow coil, it towill
refrigerant coil.
the As
therefrigerant passes through
addition of energy). the the
This causes valve
Arefrigerant.
refrigerantAsdistributorheat is addedon to
each the liquid
evaporator
evaporate refrigerant,
coil. As refrigerant
quickly and passes
the through
air the valve
will not pressure and temperature of the liquid
refrigerant. As heat is added to the liquid refrigerant,
DX evaporator coil
it is adiabatically
it is adiabatically expanded (that is, without the addition expanded (that is, without the addition
ititbegins
beginsto evaporate much circuit
to evaporate like water feeds
much lowa water
boilinglike
on be boiling
adequately on cooled.
athe pressureIf andtootemperature
much refrigerant to drop, making it suitable
pressure,
stove. low mixture
The liquid-vapor temperature liquid
remains at a constant
of energy).
refrigerant
This causes
is fed totodrop,
of
themaking
energy).
coil itit suitable
will not
Thisfor
causes the pressure and temperature
cooling the air.
stove. The liquid-vapor mixture remains
of theat a
liquid constant
refrigerant for
temperature
refrigerant and pressure
to theuntilcoil it completely
tubes.vaporizes
It is evaporate
cooling the air. at all and liquid of the liquid refrigerant to drop, making it suitable for
refrigerant
temperature
(for
that all and
R22), while for R407C
critical pressure
the temperatureuntil
the distributor itare
and pressure
tubes completely vaporizes
will drop slightly due to the glide of the refrigerant. The will return to the cooling
compressor. the air. The amount of refrigerant fed to the
Direct
(for
the
coil R22),
same
capacity whilesofor
islength
determined R407C
bythe type andthe
the pressure temperature
drop
amount of expansionand ofpressure
The amount refrigerant fed to the coil is based on the
cooling load of the (DX)
supplyevaporator coilsamount
air and the resultant are coil is based on the cooling load of the
will drop
across
refrigerant used,slightly
them thewill dueequal
be
temperature to the and
glide
difference between of thedesigned
the refrigerant. The
to evaporate all refrigerant supply air and the resultant amount
The amount of refrigerant fed to the coil is based on the
refrigerant will be
coil capacity evenly distributed
is determined to type
by the in and
the amount
coil and ofthen “superheat” the
the coil tubes. cooling load of the supply air and the resultant amount
refrigerant used, the temperature difference between
Diaphragm
105ºF Capillary
210 psig Tube
Distributor
Evap. Coil
Diaphragm 44ºF, 74 psig
Liquid Line
Valve Body
Sensing Bulb
105ºF 63ºF 59ºF, 100 psig Capillary
108 psig
210
Superheat psig Tube
Spring Distributor
46ºF
78 psig 59ºF, 74 psig Evap. Coil
Superheat
Adjustment
Superheated 44ºF, 74 psig
Screw (Set toLiquid
34 psig) Line Equalizer Line LD09137
FIG.3 3-THERMAL
FIG. - THERMAL EXPANSION VALVE
REXPANSION VALVE (TXV)
(TXV) COMPONENTS
COMPONENTS
YORK INTERNATIONAL 13
10
Equipment Selection
of superheat created. As the cooling The valve body contains a superheat RAUP Condensing Unit Performance
load increases, the liquid refrigerant spring that keeps everything in balance. Information
absorbs more heat and evaporates By turning a screw in the bottom of the
more quickly. This means that more valve the spring can be set for a certain When using a pre-engineered
of the evaporator coil is available to amount of superheat. For example, if condensing unit, you can use ratings
superheat the refrigerant vapor and it the superheat spring is set for 15 °F of such as those shown in Fig. (RAUP
leaves the coil at a higher temperature. superheat it will exert a pressure on the R22, R407C Performance Data) to
Conversely as the cooling load valve equal to the pressure the determine which condensing unit size
decreases, the liquid refrigerant does vaporized gas in the sensing bulb will will satisfy the cooling capacity of the
not evaporate as quickly so less exert on the valve diaphragm when the system.
superheating occurs and the refrigerant suction gas is superheated by 15 °F.
leaves the coil at a lower temperature. The equalizer line is used to prevent Evaporator Coil TXV Size
the pressure drop that occurs across Capacity (Tons)
The sensing bulb attached to the valve the distributor and DX coil from affecting 4 to 6 5
is charged with a mix of liquid and the operation of the expansion valve. 6 to 10 8
vapor refrigerant. This refrigerant must 9 to 13 11
be the same type as that in the system. APPLICATION DESIGN CONDITIONS 12 to 18 15
The refrigerant vapor in the sensing 16 to 24 20
bulb exerts pressure on a diaphragm in Before selecting equipment, you must 24 to 36 30
the valve body, which causes the valve first establish these basic working pa-
Choose a TXV that matches the tonnage
to open or close. rameters:
• The design cooling load of the evaporator coil it serves
As the temperature of the superheated • The design outdoor air temperature It is recommended to provide and
suction gas leaving the evaporator • The refrigerant saturated suction install one TXV per distributor.
rises due to an increase in the temperature For larger coil capacities, refer to the
cooling load, refrigerant in the sensing
quantity of circuits in the AHU and total
bulb evaporates increasing the The design-cooling load is typically
AHU tonnage to determine the number
pressure on the valve diaphragm. The found on the job schedule. The design
increased pressure causes the valve to outdoor air temperature may also be and tonnage & quantity of the TXV
open and allows more refrigerant to flow listed on the job schedule. If the
into the coil to meet the higher cooling saturared suction temperature (SST) TXV Size TXV Qty.
demand. When the temperature of the is not known, assume it is in the range RAUP 250 11 (20) 2 (1)
suction gas drops due to a decrease in of 40 °F to 45 °F. This represents the RAUP 300 20 (30) 2 (1)
the cooling load, the gas in the sensing standard industry approach. RAUP 400 20 2
bulb condenses reducing its pressure RAUP 500 30 2
on the valve diaphragm. This allows the RAUP 600 30 2
valve to restrict the flow of refrigerant
TXV Qty. listed here is based on the
into the coil until the lower cooling
assemption that the Evaporator has
demand is adequately met.
similar circuits to the RAUP
TXV Selection when matched with an
AHU, should be based primarily on the
final system capacity
Correction Factor
Altitude Correction Multiplier For Capacity
Altitude (Ft.) 2,000 4,000 6,000 8,000 10,000
Condensing Unit Only 0.982 0.960 0.933 0.902 0.866
Condensing Unit / Air Handling Unit Combination 0.983 0.963 0.939 0.911 0.881
Condensing Unit With Evaporator 0.986 0..968 0.947 0.921 0.891
11
Equipment Selection
12
�������������������������������������������������
���
���
���
���
���
���
���
���
13
���
���
���
������������������
���
���
���
���
���
���
Performance (50Hz), R22
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 250 Condensing Unit
���������������������������
���
���
���
���
���
14
���
���
������������������
���
���
���
���
Performance (50Hz), R22
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 300 Condensing Unit
��������������������
���
���
���
���
���
���
���
15
���
���
������������������
���
���
���
���
���
Performance (50Hz), R22
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
���������������������������
RAUP 400 Condensing Unit
���
���
���
���
���
���
���
16
���
���
���
������������������
���
���
���
���
���
���
Performance (50Hz), R22
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 500 Condensing Unit
���������������������������
���
���
���
���
���
���
���
���
���
���
17
���
���
���
������������������
���
���
���
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
Performance (50Hz), R22
�������������������������
RAUP 600 Condensing Unit
18
���
���
���
���
�������������������
���
���
���
���
���
���
���
���
���
���
Unit Performance (50Hz)
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 400 x 2 Condensing
����������������������������������
����
����
����
����
����
����
19
����
���
���
���
���
���
���
Unit Performance (50Hz)
�� �� �� �� �� �� �� �� �� ��
RAUP 500 x 2 Condensing
����
����
����
����
����
����
20
����
����
����
�������������������
����
����
���
���
���
���
Unit Performance (50Hz)
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 600 x 2 Condensing
����������������������������������
���
���
���
���
���
���
21
���
���
������������������
���
���
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
Performance R407C (50Hz)
RAUP 250 Condensing Unit
���������������������������
���
���
���
���
���
22
���
���
������������������
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
Performance R407C (50Hz)
RAUP 300 Condensing Unit
��������������������
���
���
���
���
���
���
23
���
���
������������������
���
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
���������������������������
Performance R407C (50Hz)
RAUP 400 Condensing Unit
���
���
���
���
���
���
���
24
���
���
���
������������������
���
���
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
Performance R407C (50Hz)
RAUP 500 Condensing Unit
���������������������������
���
���
���
���
���
���
���
���
���
25
���
���
���
���
������������������
���
���
���
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
�������������������������
Performance R407C (50Hz)
RAUP 600 Condensing Unit
26
���
���
���
���
�������������������
���
���
���
���
���
���
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 400 x 2 Condensing
����������������������������������
����
����
����
����
����
����
27
���
���
�������������������
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 500 x 2 Condensing
����������������������������������
����
����
����
����
����
����
28
����
����
����
�������������������
����
����
���
���
���
���
�� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� �� ��
RAUP 600 x 2 Condensing
����������������������������������
29
0 32 104.4 357 29.8 16.5 240 4.0 58 98.8 337 33.0 18.6 270 4.0 58 92.9 317 36.8 20.8 302 4.0 58 86.8 296 40.8 23.3 338 4.0 58 80.4 275 45.2 26.0 376 4.0 58
2 36 112.3 384 30.6 17.1 247 4.3 63 106.3 363 33.8 19.1 277 4.3 63 100.0 342 37.6 21.4 310 4.3 63 93.5 319 41.6 23.8 346 4.3 63 86.6 296 46.2 26.5 385 4.3 63
4 39 118.4 405 31.2 17.5 253 4.6 67 112.1 383 34.4 19.5 284 4.6 67 105.5 360 38.2 21.8 316 4.6 67 98.6 337 42.4 24.3 352 4.6 67 91.4 312 46.8 27.0 391 4.6 67
6 43 126.8 433 32.0 18.0 262 5.0 73 120.0 410 35.4 20.1 292 5.0 73 113.0 386 39.2 22.4 325 5.0 73 105.6 361 43.2 24.9 361 5.0 73 98.0 335 47.8 27.6 401 5.0 73
8 46 133.2 455 32.6 18.5 268 5.4 78 126.1 431 36.0 20.6 299 5.4 78 118.7 405 39.8 22.9 332 5.4 78 111.0 379 44.0 25.4 368 5.4 78 103.0 352 48.4 28.1 408 5.4 78
10 50 141.8 484 33.6 19.1 277 5.8 84 134.3 459 37.0 21.2 308 5.8 84 126.4 432 40.8 23.6 342 5.8 84 118.3 404 44.8 26.1 378 5.8 84 109.8 375 49.4 28.8 418 5.8 84
8 46 175.2 599 42.2 18.4 267 5.4 78 166.4 568 46.4 20.5 297 5.4 78 157.2 537 51.0 22.7 330 5.4 78 147.6 504 56.2 25.2 366 5.4 78 137.6 470 61.8 27.9 405 5.4 78
10 50 186.9 638 43.4 19.0 276 5.8 84 177.5 606 47.8 21.1 306 5.8 84 167.7 573 52.4 23.4 340 5.8 84 157.5 538 57.6 25.9 376 5.8 84 147.0 502 63.2 28.6 415 5.8 84
RAUP Performance
30
2 36 106.7 364 30.6 17.1 247 4.3 63 101.0 345 33.8 19.1 277 4.3 63 95.0 325 37.6 21.4 310 4.3 63 88.8 303 41.6 23.8 346 4.3 63 82.3 281 46.2 26.5 385 4.3 63
4 39 112.5 384 31.2 17.5 253 4.6 67 106.5 364 34.4 19.5 284 4.6 67 100.2 342 38.2 21.8 316 4.6 67 93.7 320 42.4 24.3 352 4.6 67 86.8 297 46.8 27.0 391 4.6 67
6 43 120.4 411 32.0 18.0 262 5.0 73 114.0 389 35.4 20.1 292 5.0 73 107.3 367 39.2 22.4 325 5.0 73 100.3 343 43.2 24.9 361 5.0 73 93.1 318 47.8 27.6 401 5.0 73
8 46 126.5 432 32.6 18.5 268 5.4 78 119.8 409 36.0 20.6 299 5.4 78 112.7 385 39.8 22.9 332 5.4 78 105.4 360 44.0 25.4 368 5.4 78 97.8 334 48.4 28.1 408 5.4 78
10 50 134.7 460 33.6 19.1 277 5.8 84 127.6 436 37.0 21.2 308 5.8 84 120.1 410 40.8 23.6 342 5.8 84 112.4 384 44.8 26.1 378 5.8 84 104.3 356 49.4 28.8 418 5.8 84
75 24 61 16 419 123 335 98 26 399 117 327 96 30 380 111 315 92 34 359 105 309 90 38
RAUP 400 TTV 400 12120 77 25 64 18 444 130 324 95 26 423 124 313 92 30 401 117 305 89 34 379 111 295 87 38
5.7 80 27 67 19 462 135 319 93 26 442 129 314 92 30 421 123 303 89 34 398 117 294 86 38
86 30 71 22 - - - - - - - - - - - -
75 24 61 16 536 157 440 129 33 513 150 426 125 37 490 143 416 122 42 464 136 371 109 47
RAUP 500 TTV 500 15130 77 25 64 18 565 165 418 122 33 540 158 410 120 37 515 151 397 116 42 487 143 385 113 47
7.1 80 27 67 19 592 173 420 123 33 568 166 409 120 37 541 159 395 116 42 514 151 386 113 47
86 30 71 22 - - - - - - - - - - - -
75 24 61 16 645 189 542 159 40 621 182 528 155 45 594 174 517 151 50 564 165 502 147 56
RAUP 600 TTV 600 18080 77 25 64 18 682 200 518 152 40 656 192 512 150 45 627 184 496 145 50 595 174 482 141 56
8.5 80 27 67 19 714 209 514 150 40 686 201 508 149 45 658 193 493 144 50 623 182 480 141 56
86 30 71 22 - - - - - - - - - - - -
31
Unit Unit CFM EDB EWB TC SCH PI TC SCH PI TC SCH PI TC SCH PI
CMS F C F C MBH kW MBH kW kW MBH kW MBH kW kW MBH kW MBH kW kW MBH kW MBH kW kW
75 24 61 16 398 117 319 93 26 379 111 311 91 30 361 106 299 88 34 341 100 294 86 38
RAUP 400 TTV 400 12120 77 25 64 18 421 123 308 90 26 402 118 298 87 30 381 112 290 85 34 360 105 281 82 38
RAUP-TTV System
5.7 80 27 67 19 439 129 303 89 26 420 123 298 87 30 400 117 288 84 34 378 111 280 82 38
86 30 71 22 - - - - - - - - - - - -
75 24 61 16 510 149 418 122 33 488 143 405 119 37 465 136 396 116 42 441 129 352 103 47
RAUP 500 TTV 500 15130 77 25 64 18 536 157 397 116 33 513 150 390 114 37 489 143 377 110 42 463 136 366 107 47
7.1 80 27 67 19 562 165 399 117 33 540 158 389 114 37 514 151 375 110 42 488 143 366 107 47
86 30 71 22 - - - - - - - - - - - -
75 24 61 16 613 179 515 151 40 590 173 502 147 45 564 165 491 144 50 536 157 477 140 56
RAUP 600 TTV 600 18080 77 25 64 18 648 190 493 144 40 624 183 486 142 45 596 175 471 138 50 565 165 458 134 56
8.5 80 27 67 19 678 199 488 143 40 652 191 482 141 45 625 183 468 137 50 592 173 456 133 56
86 30 71 22 - - - - - - - - - - - -
For ease of selection, 5 pre selected systems with indoor units TTV are available as in the following performance table.
Notes
TC Gross Total Capacity All Capacities are gross and do not include a deduction for evaporator fan motor heat..
SC Sensible Capacity Interpolation is allowed. Do not extrapolate.
PI Power Imput, kW Compressors
Indoor Unit Fan Performance
Data
SI Unit
External Static Pressure (Pa)
124.5 149.4 199.2 249 298.8 348.6 398.4 448.2 498
CMS RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.9 634 1.417 661 1.492 713 1.716 764 1.865 812 2.089 860 2.313 907 2.537 953 2.761 999 3.1
3.2 662 1.641 687 1.716 736 2.0 784 2.089 831 2.313 876 2.611 919 2.835 961 3.059 1002 3.3
3.7 725 2.313 748 2.462 791 2.611 834 3.0 876 3.134 917 3.283 958 3.582 999 3.880 1036 4.1
3.7 732 2.388 755 2.537 798 2.686 840 3.1 881 3.208 922 3.432 963 3.656 1003 4.0 1040 4.3
4.3 805 3.358 825 3.507 866 3.805 903 4.0 941 4.402 977 4.701 1013 4.850 1049 5.074 1065 5.3
4.5 835 3.805 855 4.0 894 4.328 931 4.552 967 4.850 1001 5.223 1036 5.447 1071 5.746 1105 6.0
Std. Motor is 5hp (3.7kW). High Static Option is 10hp (7.5kW)
SI Unit
External Static Pressure (Pa)
124.5 149.4 199.2 249 298.8 348.6 398.4 448.2 498
CMS RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
3.5 692 2.0 717 2.2 762 2.4 807 2.6 851 2.8 894 3.0 936 3.3 976 3.5 1016 3.8
3.7 719 2.3 743 2.5 786 2.6 829 3.0 870 3.2 911 3.4 952 3.6 992 3.9 1030 4.2
4.2 790 3.3 810 3.4 852 3.7 890 3.9 927 4.2 964 4.6 1000 4.8 1036 4.9 1072 5.2
4.4 806 3.5 825 3.7 866 4.0 904 4.2 940 4.5 977 4.9 1012 5.1 1047 5.3 1082 5.5
4.8 865 4.5 882 4.6 919 4.9 956 5.2 990 5.4 1023 5.7 1057 6.2 1089 6.6 1121 6.8
5.3 924 6.0 958 6.1 990 6.3 1023 6.7 1057 7.2 1088 7.4 1118 7.6 - - - -
Std. Motor is 7.5hp (5.5kW). High Static Option is 15hp (11kW)
SI Unit
External Static Pressure (Pa)
124.5 149.4 199.2 249 298.8 348.6 398.4 448.2 498
CMS RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
4.6 609 2.2 737 2.4 799 2.7 861 3.0 918 3.3 971 3.6 1021 3.9 1068 4.2 1115 4.6
4.8 631 2.5 754 2.6 812 2.9 873 3.3 930 3.6 983 3.9 1032 4.3 1078 4.6 1124 4.9
5.3 687 3.2 798 3.4 854 3.7 906 4.0 960 4.4 1014 4.8 1062 5.2 1108 5.5 1152 5.9
5.7 730 3.9 835 4.0 887 4.4 937 4.4 986 5.1 1036 5.5 1085 6.0 1131 6.4 1175 6.6
5.8 744 4.1 847 4.3 897 4.6 947 5.0 994 5.4 1043 5.8 1093 6.2 1139 6.6 1182 7.0
6.4 802 5.1 900 5.3 943 5.7 990 6.1 1035 6.5 1078 6.9 1123 7.3 1169 7.8 1213 8.3
6.9 863 6.4 954 6.6 996 7.0 1035 7.4 1079 7.9 1154 8.4 1200 9.0 - - - -
Std. Motor is 7.5hp (5.5kW). High Static Option is 15hp (11kW)
32
Indoor Unit Fan Performance
Data
SI Unit
External Static Pressure (Pa)
124.5 149.4 199.2 249 298.8 348.6 398.4 448.2 498 547.8 597.6 622.5
CMS RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
5.7 479 1.9 509 2.2 570 2.6 638 3.4 698 4.1 745 4.7 787 5.2 826 5.7 865 6.1 904 6.6 943 7.2 963 7.4
6.0 489 2.2 516 2.4 574 2.8 634 3.4 702 4.3 754 5.1 796 5.7 834 6.1 871 6.6 907 7.2 944 7.7 963 7.9
6.6 511 2.6 536 2.8 587 3.3 638 3.7 695 4.5 758 5.5 808 6.3 849 7.0 885 7.6 920 8.1 953 8.7 970 9.0
7.1 532 3.1 556 3.4 602 3.8 651 4.3 697 4.9 751 5.7 810 6.8 859 7.8 899 8.6 934 9.2 967 9.9 983 10.1
7.7 553 3.7 577 4.0 622 4.5 664 4.9 710 5.5 753 6.1 802 6.9 858 8.1 907 9.3 947 10.2 982 11.0 998 11.3
8.2 577 4.4 601 4.6 642 5.2 682 5.7 722 6.3 766 6.9 805 7.5 850 8.3 902 9.6 951 10.9 992 11.9 1010 12.4
8.6 597 4.9 619 5.2 658 5.7 698 6.3 734 6.9 775 7.5 815 8.1 854 8.8 897 9.8 945 11.0 991 12.4 - -
Std. Motor is 10hp (7.5kW). High Static Option is 20hp (15kW)
SI Unit
External Static Pressure (Pa)
124.5 149.4 199.2 249 298.8 348.6 398.4 448.2 498 547.8 597.6 622.5
CMS RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
6.8 569 3.7 592 4.0 635 4.4 682 4.9 728 5.5 777 6.3 832 7.4 882 8.5 923 9.4 959 10.2 992 10.8 1008 11.1
7.0 579 4.0 602 4.3 643 4.7 689 5.2 733 5.8 777 6.4 831 7.5 885 8.8 929 9.8 966 10.6 999 11.3 1015 11.7
7.5 605 4.7 625 4.9 667 5.4 705 6.0 749 6.6 789 7.2 831 7.9 881 9.0 932 10.4 977 11.6 1014 12.5 - -
8.0 631 5.5 651 5.7 691 6.3 727 6.9 765 7.5 806 8.1 843 8.7 882 9.5 928 10.6 977 12.0 - - - -
8.5 658 6.4 677 6.7 714 7.3 751 7.9 785 8.4 821 9.1 860 9.9 895 10.4 931 11.3 973 12.4 - - - -
9.0 686 7.4 705 7.8 739 8.4 775 9.0 808 9.6 840 10.2 876 11.0 912 11.7 945 12.4 - - - - - -
9.5 713 8.5 732 8.9 765 9.6 799 10.2 832 10.9 862 11.5 893 12.2 927 13.0 - - - - - - - -
10.1 740 9.8 759 10.2 792 10.8 823 11.5 856 12.2 886 12.9 - - - - - - - - - - - -
10.3 756 10.5 775 10.9 808 11.6 838 12.3 - - - - - - - - - - - - - - - -
Std. Motor is 15hp (11kW). High Static Option is 20hp (15kW)
Notes
To determine power of the motor to be installed, the following correction factors have to be applied to the fan Shaft Absorbed hp.
Fan Motor hp = Absorbed Fan Shaft hp x Correction Factor
Correction Factor = 1.2 for absorbed Fan Shaft < 10kW (13.4hp)
Correction Factor = 1.15 for absorbed Fan Shaft > 10kW (13.4hp)
Fan Motor Heat (MBH) = 2.55 x BH
Data Includes pressure drop due to filters and wet coil.
33
Line Sizing, Routing,
Line Sizing, Routing, and
Component
and ComponentSelection
Selection
Figure 2.2.Liquid-Line
Figure Liquid-LineRiser Limitations
Riser for RAUC
Limitations for20- through
RAUP 120-Condensing
Condensing UnitsUnits
Riser
Riserheight
heightlimitations defined
limitations in this chart
defined in this
assume that the liquid line contains 10 elbows.
chart assume that the liquid line
The effect of additional elbows varies based on
contains 10 elbows. The effect of
the specific characteristics of each installation.
additional elbows varies based on
the specific characteristics of each
installation.
Note:
Note: Preselected
Preselectedliquid-line
liquid-linediameters
diameters are Insulation
independent of line length or rise,
are independent of line length or rise, The liquid line is generally warmer
within the permissible guidelines, for properly charged 20- through 120-ton
within the permissible guidelines, for than the surrounding air, so it does not
RAUC units in normal air-conditioning applications.
properly charged RAUP units in normal require insulation. In fact, heat loss
air-conditioning applications. from the liquid line improves system
Routing. Install the liquid line with a slight slopebecause
capacity in the direction of flow
it provides so
additional
that it can be routed with the
Routing. Install the liquid line with a suction line.
subcooling.
slight slope in the direction of flow so
A height
that it canlimitation
be routed exists
with for
theliquid lines that
suction include a liquid riser because of
Components
the
line. loss of subcooling that accompanies the pressure loss in the height
Liquid-line refrigerant of the
components
liquid column. Figure 2 depicts the permissible rise for
necessary in the liquid linejob
a successful (that is,
include
A height excessive
without limitation exists forsubcooling).
loss of liquid lines Again,
a filter drier,designs
system accessoutside
port, moisture-
the
that includeenvelope
application a liquidofriser
the RAUC because indicating
unit require Trane sight
review.glass, expansion
of the loss of subcooling that valve(s), and ball shutoff valves.
accompanies
Note: Beginning the in
pressure
May 2000,loss 20-in the
through 120-ton RAUC units include a
height of thevalve
check/relief liquid
to column, Figurerefrigerant
prevent liquid 2 from being drawn back to the
depicts
compressor the during the offrise
permissible cycle. in The
therelief valve discharges to the condenser to
liquid
prevent lineexcessive
(that is,without excessive
pressures fromloss
developing in the liquid line during off cycles.
of subcooling). Again, system designs
outside
Insulation. the application
The liquid lineenvelope of warmer than the surrounding air, so
is generally
the RAUP unit require Trane review.
it does not require insulation. In fact, heat loss from the liquid line improves
system capacity because it provides additional subcooling.
10 SS-APG001-EN-0901
34
Line Sizing, Routing, and
Component Selection
35
Line Sizing, Routing, and
Component Selection
Total length of the suction line, Suction Lines Note: If a suction riser is properly
including a maximum rise of 50 feet, sized, oil will return to the compressor
must not exceed 150 feet. Line sizing. Proper suction-line sizing regardless of whether a trap is present.
is required to guarantee that the oil If a suction riser is oversized, adding
returns to the compressor throughout a trap will not restore proper oil
the system’s operating envelope. At the movement.
same time, the line must be sized so
that the pressure drop does not Avoid putting refrigerant lines
excessively affect capacity or efficiency. underground. Refrigerant condensation
To accomplish both objectives, it may or installation debris inside the line,
be necessary to use two different line service access, and abrasion/corrosion
diameters: one for the horizontal run can quickly impair reliability.
and for vertical drops, and another for
the vertical lifts. Insulation. Any heat that transfers
from the surrounding air to the cooler
Routing. To prevent residual or suction lines increases the load on the
condensed refrigerant from “free- condenser (reducing the system’s air-
flowing” toward the compressor, install conditioning capacity) and promotes
the suction line so that it slopes slightly condensate formation (adversely
— that is, by ¼ inch to 1 inch per 10 affecting indoor air quality). After
feet of run [1 cm per 3 m] — toward the operating the system and testing all
evaporator. fittings and joints to verify that the
system is leak-free, insulate the suction
When the application includes a lines to prevent heat gain and unwanted
suction riser, oil must be forced to travel condensation.
the height of the riser. Riser traps and
double risers are unnecessary in the
suction line. All RAUP units unload ■ Access port. The access port is
such that a single line size, standard used to determine suction pressure.
preselected, provides sufficient lift to This port is usually a Schraeder
push entrained oil up the permissible valve with a core.
riser height. To assure proper oil
movement, the permissible unit
separationis 150 ft [45.7 m], including
a maximum vertical rise of 50 ft
[15 m]. System designs outside this
application envelope require Trane
review.
36
Single-Circuit Examples of Field-Installed
RAUCs Examples of
Evaporator Field-Installed
Piping
Evaporator Piping
Single-Circuit
1 Pitch RAUPs
the liquid line slightly—1 in./10 ft Evaporator Coil with
[1 cm/3 m]—so that the refrigerant drains Standard Circuiting
toward the evaporator.
Figure 3. Type UF Evaporator Coil suction line
2 Provide
Withone
One Distributor
expansion valve per distributor.
3 Slightly pitch the outlet line from the suction liquid
1 Pitch
header towardthe theliquid line
suction slightly is,
riser—that — 1 in./ sight line
1 in./1010ft [1ftcm/3
[1 m]
cm/3in the
m]direction
— so ofthatflow.the glass
Use the tube diameter that matches the
refrigerant drains toward the
suction-header connection.
evaporator.
4 Use the tube diameter recommended for a thermal solenoid filter drier
vertical rise in Table 2 (page 6). Assure that expansion valve
2 Provide one expansion valve per valve (TXV)
the top of the riser is higher than the
distributor.
evaporator coil.
5 Arrange the suction line so that the distributor
3 Slightly pitch the outlet line from
refrigerant gas leaving the coil flows
the past
downward, suction header
the lowest toward
suction-header the
outlet, suction riser —
before turning that is, 1 in./10
upward. ft [1
cm/3
6 Pitch the m]line
suction in slightly—1
the direction
in./10 of
ft flow.
[1 cm/3Use the that
m]—so tubethe
diameter that
refrigerant matches
drains
towardthethe suction-header
evaporator. connection.
7 Insulate the suction line.
4 Use the tube diameter recom-
mended for a vertical rise in
Table 2 (page6). Assure that the
top of the riser is higher than the
evaporator coil.
14 SS-APG001-EN-0901
37
Single-Circuit Examples of Field-Installed
RAUCs Examples of
Evaporator Field-Installed
Piping
Evaporator Piping
Figure 4. Type UF Evaporator Coil with Two Distributors
1 Single or Dual-Circuit
Pitch the liquid RAUPs
line slightly—1 in./10 ft suction line Evaporator Coil
[1 cm/3 m]—so that the refrigerant drains with Horizontal-Split
toward the evaporator. “trim” (Standard) Circuiting
Figure 4. Type UF Evaporator Coil solenoid valve
2 Provide one expansion valve per distributor. liquid
With Two Distributors line
3 Slightly pitch the outlet line from the suction
header toward the suction riser—that is, sight
11 in./10
Pitchft [1the liquid
cm/3 m] inline slightly of
the direction —flow.
1 in./ thermal
glass
Use10 ft [1diameter
the tube cm/3 thatm] matches
— so the that the expansion
valve (TXV)
refrigerantconnection.
suction-header drains toward the
evaporator.
4 Arrange the suction line so that the filter drier
refrigerant gas leaving the coil flows
2downward,
Providepast the lowest
one suction-header
expansion valve per “pump-down”
outlet, before turning upward. Use a double-
distributor.
elbow configuration to isolate the TXV bulb
solenoid valve
from other suction headers.
distributor
5 3UseSlightly pitch the outlet line from
the “horizontal” tube diameter identified
the 2 (page
in Table suction
6). header toward the
6 Usesuction riser — recommended
that is, 1 in./10
for aft [1
suction line Evaporator Coil with
the tube diameter
Intertwined Circuiting
cm/3
vertical risem] in the
in Table direction
2 (page 6). Assureofthat
flow.
Useofthe
the top the tube
riser isdiameter
higher thanthat
thematches liquid
the suction-header
evaporator coil. connection. line
7 Pitch the suction line slightly—1 in./10 ft sight
4[1 cm/3 m]—so
Arrange that
the the refrigerant
suction line sodrains
that the glass
toward the evaporator.
refrigerant gas leaving the coil flows
8 Insulate the suction line.
downward, past the lowest suction- solenoid
filter drier
9 Onlyheader
use a “trim” solenoid before
valve for turning valve
outlet, thermal
constant-volume, humidity-sensitive
upward. Use a double-elbow expansion
applications. For all other applications, valve (TXV)
configuration
install to isolate
a single solenoid the“pump-
valve (the TXV bulb
distributor
from
down” other valve)
solenoid suction headers.
between the liquid-
line filter drier and the sight glass.
5 Use the “horizontal” tube diameter
identified in Table 2 (page 6).
SS-APG001-EN-0901 15
38
Single-Circuit Examples of Field-Installed
RAUCs Examples of
Evaporator Field-Installed
Piping
Evaporator Piping
Single
1 Pitch or Multiple-Circuit
the liquid line slightly—1 in./10RAUPs
ft Evaporator Coil
[1 cm/3 m]—so that the refrigerant drains with Horizontal-Split
suction line thermal expansion
toward the 5.
Figure evaporator.
Type UF Evaporator Coil (Standard) Circuiting
valves (TXV)
2 Provide
With one
Four Distributors
expansion valve per distributor.
3 Slightly pitch the outlet line from the suction liquid
1 Pitch
header toward thetheliquid line
suction slightly —
riser—that is, 1 in./ line
10ft [1ft cm/3
1 in./10 [1 cm/3 m] direction
m] in the — so of that
flow.the
“trim”
Use the tube diameterdrains that matches the sight
refrigerant toward the solenoid valve glass
suction-header connection.
evaporator.
4 Arrange the suction line so that the
refrigerant gas leaving the coil flows filter drier
2 Provide one expansion valve per
downward, past the lowest suction-header
distributor.
outlet, before turning upward. Use a double-
“pumpdown”
elbow configuration to isolate the TXV bulb
3 other
Slightly pitch the outlet line from solenoid valve
from suction headers.
the
5 Use the suction tube
“horizontal” header toward
diameter the
identified
distributor
suction
in Table 2 (pageriser
6). — that is, 1 in./10 ft [1
6 Use thecm/3
tube m] in the
diameter direction of
recommended for aflow.
Use
vertical risethe tube2diameter
in Table that matches
(page 6). Assure that
the topthe suction-header
of the riser is higher connection.
than the suction line Evaporator Coil with
evaporator coil. thermal expansion Intertwined Circuiting
4 the
7 Pitch Arrange
suctionthe
linesuction linein./10
slightly—1 so that
ft the valves (TXV)
“trim”
refrigerant
[1 cm/3 m]—so thatgas leaving drains
the refrigerant the coil solenoid valve
towardflows downward, past the lowest
the evaporator.
liquid
suction-header
8 Insulate the suction line. outlet, before line
turning
9 Only use upward.
a “trim” Use
solenoid a double-elbow
valve for
sight
configuration
constant-volume, to isolate the TXV bulb
humidity-sensitive glass
from other
applications. For allsuction headers.
other applications,
install a single solenoid valve (the “pump-
down”
5 Use solenoid valve) between
the “horizontal” the liquid-
tube diameter filter drier
line filter drier and the sight glass.
identified in Table 2 (page 6).
“pumpdown”
6 Use the tube diameter recom- solenoid valve
mended for a vertical rise in
Table 2 (page6). Assure that the
top of the riser is higher than
the evaporator coil.
distributor
7 Pitch the suction line slightly — 1
in./10ft [1 cm/3 m] — so that the
refrigerant drains toward the
evaporator.
16 SS-APG001-EN-0901
39
Dual-Circuit Examples of Field-Installed
RAUCs Examples of
Evaporator Field-Installed
Piping
Evaporator Piping
1 Single or Multiple-Circuit
Pitch the liquid RAUPs
lines slightly—1 in./10 ft suction line Evaporator Coil
[1 cm/3 m]—so that the refrigerant drains (circuit 2) with Horizontal-Split
toward the evaporator. (Standard) Circuiting
Figure 6. Type UF Evaporator Coil liquid line
2 Provide one expansion valve per distributor. (circuit 2)
With Two Distributors
3 Slightly pitch the outlet line from the suction sight
header toward the suction riser—that is, glass
1 Pitch the liquid line slightly — 1 in./
1 in./10 ft [1 cm/3 m] in the direction of flow.
Use 10 ft [1diameter
the tube cm/3 that
m] matches
— so the that the
solenoid
refrigerantconnection.
suction-header drains toward the distributor valve
suction line
4 The evaporator.
top of the Circuit 1 suction riser must be (circuit 1)
higher than the bottom evaporator coil. Use
liquid line
2 Provide
the tube diameteronerecommended
expansionforvalve
a per (circuit 1)
vertical rise in Table 2 (page 6).
distributor.
5 Arrange the suction line so that the
refrigerant gas leaving the coil flows
3 Slightly pitch the outlet line from
downward, past the lowest suction-header
thebefore
outlet, suction header toward the
turning upward. thermal filter drier
6 The suction riser — that is, 1 in./10 ft [1
top of the Circuit 2 suction riser must be expansion
cm/3
higher than m] in evaporator
the top the direction of the
coil. Use flow. valve (TXV)
tubeUse the tube
diameter diameterforthat
recommended matches
a vertical
rise the suction-header
in Table 2 (page 6). connection.
7 Pitch the suction lines slightly—1 in./10 ft
4 Them]—so
[1 cm/3 top ofthat
thethe
Circuit 1 suction
refrigerant drainsriser
toward the evaporator.
must be higher than the bottom
8 Insulate the suction coil.
evaporator lines. Use the tube
diameter recommended for a
vertical rise in Table 2 (page 6).
SS-APG001-EN-0901 17
40
Dual-Circuit Examples of Field-Installed
RAUCs Examples of
Evaporator Field-Installed
Piping
Evaporator Piping
Figure 7. Type UF Evaporator Coil with Four Distributors
Single
1 Pitch or Multiple-Circuit
the liquid line slightly—1 in./10RAUPs
ft Evaporator Coil
[1 cm/3 m]—so that the refrigerant drains with Horizontal-Split
toward the evaporator. (Standard) Circuiting
Figure 7. Type UF Evaporator Coil suction line
2 Provide one expansion valve per distributor.
With Four Distributors (circuit 2)
thermal expansion liquid line
3 Slightly pitch the outlet line from the suction valves (TXV) (circuit 2)
header toward the suction riser—that is, solenoid
1 Pitch the liquid line slightly — 1 in./ valve
1 in./10 ft [1 cm/3 m] in the direction of flow.
10 ft [1 cm/3 m] — so that the
Use the tube diameter that matches the
refrigerant
suction-header drains toward the
connection.
evaporator. suction line
4 Arrange the suction line so that the (circuit 1) sight
refrigerant gas leaving the coil flows glass
2 Provide liquid line
downward, pastone expansion
the lowest valve per
suction-header
(circuit 1)
distributor.
outlet, before turning upward. Use a double-
elbow configuration to isolate the TXV bulb
from other suction headers.
3 Slightly pitch the outlet line from
5 Use the
the“horizontal”
suction tube
header toward the
diameter filter drier
identified in Table 2 (page 6).
suction riser — that is, 1 in./10 ft [1
6 Use the
cm/3tubem] in the
diameter direction of
recommended for aflow.
vertical rise in Table 2 (page 6). Assure that distributor
Use the tube diameter that matches
the top of the riser is higher than the
the suction-header connection.
evaporator coil.
7 Pitch the suction line slightly—1 in./10 ft Evaporator Coil with
4 Arrange the suction line so that the
[1 cm/3 m]—so that the refrigerant drains Intertwined Circuiting
refrigerant gas leaving the coil flows suction lines
toward the evaporator.
downward,
8 Insulate past the lowest suction-
the suction line.
thermal expansion liquid line
header outlet, before turning valves (TXV) (circuit 2)
(circuit 2)
(circuit 1)
18 SS-APG001-EN-0901
41
Mechanical Specifications
Mechanical Specifications
Air Cooled Condensing Unit
● The contractor shall furnish and install a split air cooled Refrigerant Circuit
condensing unit of size and capacity scheduled at the ● All units shall have 1 or 2 refrigeration circuits with a
required working condition. minimum of 2 manifolded compressors on each circuit for
● The unit shall operate with either a R22 or R407C staging control.
refrigerant. ● The manifolding piping shall be designed to ensure relable
● The unit shall be fully wired with starters and controller at oil return management.
the factory. ● Each circuit shall be provided with factory set high and low
● All units shall be furnished with hermetic scroll compressors, pressure switches.
air cooled condenser and microprocessor control panel.
● Unit shall be able to operate down to 15 C as standard and Electrical
lower with a low ambeint control option.. ● Electrical panels shall be fully mounted and wired in the
● Unit shall be able to operate up to 43 C as standard and up factory with full opening access panel.
to 53 ºC with a high ambient option. ● The starting mechanism of the fans and compressors shall
● The airflow through the condenser shall be handled by be provide by the factory.
multiple direct drive fans. Each fan shall be statically and ● A DOL starting mechanism shall be provided and installed
dynamically balanced. Fan motors shall be with permanently by the factory.
lubricated ball bearings, protected by thermal overloads.
● Units shall be designed and manufactured in accordance Control System
with the quality insurance ISO 9001. ● Units shall be completely factory wired with microprocessor
based controls, starters and terminal block for power
Unit Construction wiring.
● The unit shall be designed for outdoor application and rust ● Control wiring shall be 230V.
protected with polyester powder paint. ● Compressor overheat , overcurrent and phase loss
● The unit base, shall be manufactured with GI steel. protection shall be provided.
● Unit panels shall be removable to facilitate easy service ● High and low pressure safety switches to protect the system
with Allen Key locks. against operations outside recommended pressure limits.
● Compressor, air intake sections shall be protected with ● Reverse rotation protection on compressors through
intake grilles as standard. safeties that trip the system on high temperature.
● Each unit shall be modular in design to facilate a modular ● Compressor time delays and on-off sequencing logic that
installation to minimize installed space. is built into the microprocessor algorythm for maximum
protection.
Condenser Coils ● A dry contact shall be available for remote signalling of
● Air cooled condenser coils shall be smooth bore with general faults.
3/8”copper tubes mechanically bonded to configured ● Segment LED Display shall provide draguostios for
alluminium W3BS slit fins as standard. troubleshooting and setpoint temperatures as well as
● Coils shall be factory leak tested up to 450psig. actual size temperatures.
● Higher corrosion resistant fins shall be available as an ● A multi stage with zone sensors temperature control shall
option. be standard factory installed.
48
Dimension Drawing
Condensing Unit
RAUP 250/300
49
DIMENSIONS
MODEL A B C D
RAUP400
1992
FRONT VIE
Condensing Unit
50
RAUP 500 / 600
DIMENSIONS
MODEL A B C D
RAUP500 151 314 121 1352
RAUP600 153 324 121 1361
Dimension Drawing
FRONT VIEW
Condensing Unit
51
Dimension Drawing Indoor
(Evaporating) Unit
TTV 250
52
Dimension Drawing Indoor
(Evaporating) Unit
TTV 300
TTV 400
53
Dimension Drawing Indoor
(Evaporating) Unit
TTV 500
TTV 600
54
form
To Convert From: To Multiply By: To Convert From: To: Multiply By: times
Flow
Useful Formulas
Note: 3-phase amps or KVA can be used in single-phase
Cubic feet/min (cfm) cubic meters/second (m3/s) .000472 formulas by multiplying average phase leg current
Cubic feet/min (cfm) cubic meters/hr (m3/hr) 1.69884
Multiply By: To Convert From: To: Multiply By: times √ 3 or 1.73. Example:
Gallons/minute (GPM) cubic meters/hr (m3/hr) .2271
V x A x 1.73
Gallons/minute
Energy and (GPM) litres/second (l/s) .06308 KVA =
Power and Capacity 1000
.30481 British Thermal Units (Btu/h) Kilowatt (kW) .000293
25.4 British Thermal Units (Btu/h)
Velocity Kcalorie (Kcal) .252
Tons (refrig. effect) Kilowatt (refrig. effect) 3.516 KW = Real Power; KVA = Apparent Power
Tons
Feet per(refrig.
minuteeffect)
(ft/m) Kilocalories-per
meters hour (Kcal/hr).00508
per second (m/s) 3024
KW = KVA x Power Factor = V x A x Power Factor
.093 Horsepower
Feet per second (ft/s) Kilowatt (kW)
meters per second (m/s) .7457
.3048
645.2 1000
Pressure
.0283
Energy and Power and Capacity
Feet of water (ftH2O) Pascals (PA) 2990 Motor KW = HP x .746; Motor KVA = HP x .746
16387 Inches of water (inH2O) Pascals (PA) 249 Efficiency Eff. x Power Factor
3.785 British Thermal
Pounds Units (Btu/h)
per square Kilowatt (kW)
inch (PSI*)Pascals (PA) .000293
6895
British Motor HP = KW x Eff. = KVA x Power Factor x Eff.
.003785 PSI*Thermal Units (Btu/h) Kcalorie Bar or (Kcal)
KG/CM2 .252
0.06895 .746 .746
Tons (refrig. effect)
*PSIG Kilowatt (refrig. effect) 3.516
Tons (refrig. effect) P-H DIAGRAM - BLENDS
Kilocalories-per hour (Kcal/hr) 3024 Pump HP = GPM x Total Heat (Ft. Water)
.000472 Pump Eff. x 3960
Horsepower Kilowatt (kW) .7457
Bubble (Liquid)
1.69884 Refrigeration Torque (lb.-ft.) x RPM
Point Cycle HP =
.2271 Pressure 5250
.06308
Temperature:
O
C = O
F-32
Feet of water (ftH2O) Pascals (PA) 2990 5 9
Inches of water (inH2O) Pascals (PA) 249
.00508 ∇
Pounds per square inch (PSI*) Pascals (PA) 6895 Refrig. Tons = Btu/h = GPM x t
.3048 12000 24
PSI* Bar
Lines of Constant or KG/CM2 0.06895
*PSIG
Temperature Dew (Vapor) Point
55
Standard Conversion Table
56
Literature Order Number MUL-PRC004-E4 (August 2007)
File Number
For more information, contact your local district TRANE has a policy of continuous product data and product improvement and reserves the right to
office change design and specifications without notice.