0% found this document useful (0 votes)
33 views2 pages

Datos Tecnicos Ttr-8200 - en

Uploaded by

Ana Arellano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views2 pages

Datos Tecnicos Ttr-8200 - en

Uploaded by

Ana Arellano
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Desiccant dehumidifier TTR 8200

Standard equipment Additional equipment option


n Housing made of powder-coated, galvanized sheet steel n Steam heater for regeneration air (saturated steam P > 3 barg)
n Integrated G4 air filters as Z-line filters, separately for process and regeneration n Additional electrical heating for dry air
air n Integrated heat exchanger (cold/warm water) for dry air temperature control
n Filter monitoring with warning light n Boosted or additional fan for higher compression of dry air
n Rotor rotation control n Protection and transport frame, stackable
n 24 V DC control voltage n Castors for transport frame
n Potential-free signal contacts for maintenance / filter change, fault, operation n Wheels
ON / OFF
n Housing components as stainless steel version
n Terminals for hygrostat, 24 V DC
n Hygienic equipment (fans and rotor with hygienic design)
n Terminals for external switch-on/off, 24 V DC
n Weather protection equipment
n Directly driven high-performance EC fans with manual speed adjustment
integrated in the housing (no additional throttle valves required), separately for n Humidity / temperature control (signal transducer kit 4–20 mA / 0–10 V,
process and regeneration air parameterization)
n Flowmatic S, separate electronic fan speed control for process and regeneration n Electronic hygrostat HG125 with two-line LC display
air, controlled to a constant volumetric flow or pressure depending on the n Dew point sensor (-100 - +20 °Cdp / signal 4–20 mA)
process-related target value, control signal 0…10 V or 4–20 mA n Mirror-inverted module assembly – for reversed air flow direction
n Silica gel sorption rotor with internal purging sector for heat recovery and n PWIS-free model
automatically adjusting rotor seal kit
n PT 100 temperature probe
n Rotor drive system with brushless, variable-speed gear motor, toothed belt,
toothed belt pulley and belt tensioner
n Electric regeneration air heater comprising tubular heating elements, equipped
with safety temperature limiters and differential pressure switch, controlled via
semi-conductor relay(s)
n Millenium microprocessor control with four-line plain text display
n Error messages in plain text
n Energy management (temperature-dependent regeneration air heater control)
n Humidity regulation dry air (only in combination with optional moisture
measuring device and signal transducer kit 4–20 mA / 0–10 V)
n Temperature regulation dry air (only with optional temperature probe and
downstream air conditioning)
n Temperature-controlled rundown period
n Integrated control cabinet with all the equipment and supplies required for
operation complying with the TROTEC standard: emergency stop main switch,
selection switch for remote / on-site operation, indicator lights, buttons,
switching devices, fuses, wiring and terminals
n Housing prepared for mirror-inverted assembly; air direction reversal; standard
process air flow direction from left to right

Trotec GmbH Phone: +49 2452 962-400 [email protected] Local court AC Managing Directors:
Grebbener Straße 7 Fax: +49 2452 962-200 www.trotec.om HRB 1 3453 Detlef von der Lieck
52525 Heinsberg Joachim Ludwig, Alexandra Goertz
Desiccant dehumidifier TTR 8200

General technical data (at 20 ° C / 60% rh, 1013 mbar)

Dehumidification 46.2 kg/h

Air volume free-blowing 9000 m³/h

Dry air Air volume nominal 8200 m³/h

Compression 400 Pa

Air volume 1660 m³/h


Regeneration air
Compression 300 Pa

Heating 57 kW

Power input 64.5 kW

Voltage 3/PE/380 - 480 V/50 - 60 Hz

Max. current consumption (@ 3 x 400 V) 93.5 A

Recommended fusing 125 A

Weight 750 kg
1919 mm x 1110 mm x 1680
Dimensions (L x W x H)
mm

298(DN300)
295 485

C B
499(DN500)

D
A
1680
1115
100
507

507

499(DN500)

537 200 644 200 537


1100 88 1744
1110 1919

500 500 A) Prozessluft-Eintritt


processair inlet
B) Regenerationsluft-Eintritt
regen.-air inlet
C) Feuchtluft-Austritt
wetair outlet
D) Trockenluft-Austritt
dryair outlet

Platzbedarf
1000

space requirement

Subject to change without notice. All performance data refer to 1013 mbar, a density of 1.2 kg/m³ and a power supply with 3x400 V/50Hz +PE or 230V/50 Hz. For your project design we recommend to consider a safety discount of 10-20 %
for the dehumidification performance depending on the application.

Trotec GmbH Phone: +49 2452 962-400 [email protected] Local court AC Managing Directors:
Grebbener Straße 7 Fax: +49 2452 962-200 www.trotec.om HRB 1 3453 Detlef von der Lieck
52525 Heinsberg Joachim Ludwig, Alexandra Goertz

You might also like