N O T E S:- (DRAINAGE)
01. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE INDICATED.
PIPE SIZE:-
O2. DO NOT SCALE THIS DRAWING. WRITTEN DIMENSIONS TO BE FOLLOWED.
03. CONTRACTOR SHALL COORDINATE HIS SHOP DRAWING WITH OTHER SERVICES TYPE DESCRIPTION PIPE SIZES IN MM
BEFORE SUBMITTING FOR CONSULTANT'S APPROVAL. THE SHOP DRAWING SHOULD SOIL RISER IN SHAFT 100Ø / 150Ø
CONTAIN ALL THE DETAILS LIKE EQUIPMENT LOCATION, DIMENSION, CLEARANCES FOR 50Ø
SP BIDET TO WASTE PIPE
ACCESS AND MAINTENANCE DUCT/PIPE ROUTES HANGER DETAILS,INVERT LEVELS ETC. PROJECT
W.C TO SOIL PIPE 100Ø
04. ALL JOINTS BETWEEN SANITARY WARE AND TILES TO BE SEALED WITH APPROVED WASTE RISER IN SHAFT 100Ø / 150Ø IKNS EXPANSION PROJECT
SILICON SEALANT. WASH BASIN TO FG 50Ø PHASE - 1
05. WCS/ BIDETS & URINALS SHALL BE CONNECTED TO VERTICAL VENT STACK WP
SINK TO FG 50Ø
PIPE (VP) OF 82Ø VENT PIPE SHALL HAVE VENTING COWL AT ROOF PARAPET LEVEL FG TO WASTE PIPE 75Ø
THE SEWER STACK PIPE (SP) & WASTE STACK PIPE (WP) SHALL BE CONNECTED RWP RAIN WATER PIPE IN SHAFT 100Ø / 150Ø
TO VP AFTER THE TOP MOST FLOOR LEVEL. 75Ø
VP VENT PIPE IN SHAFT
06. ALL PIPES SHALL HAVE RUBBER LINED (MUPRO OR EQUAL APPROVED ) CLAMP SUPPORTS. UNLESS OTHERWISE INDICATED.
07. VENT PIPE (VP) WITH COWL 82 Ø AND WEATHERING APRON AS PER MSCEB
STANDARD DETAILS.
SCHEDULE OF SUBMERSIBLE PUMPS
08. TRAPPED FLOOR GULLY (T.F.G.) FOR TOILETS SHALL BE OF IPLEX OR
FLOW
APPROVED EQUIVALENT.
REF LOCATION TYPE DESCRIPTION RATE HEAD ELECTRICAL INPUT MAKE MODEL COUNTRY OF ORIGIN CLIENT / OWNER
09. ALL SOIL PIPES TO BE U.P.V.C. (BS 4514) UNLESS OTHERWISE SPECIFIED.
l/s BAR Kw Volts Phase Hz IBN KHULDOON NATIONAL
10. ALL WASTE PIPES (W.P.) TO BE U.P.V.C. (BS 5255) UNLESS OTHERWISE SPECIFIED.
SCHOOL
11. ALL RAIN WATER PIPE (R.W.P.) TO BE U.P.V.C. (BS 4576) UNLESS OTHERWISE SPECIFIED.
12. TRAPPED FLOOR GULLY (T.F.G.) LOCATIONS TO BE CO-ORDINATED WITH THE
RESPECTIVE FLOOR TILE LAYOUT. BASEMENT‐ SUBMERSIBLE PUMPSET(1DUTY & 1 STANDBY) 2 1 0.75 415 3 50
13. ALL ENTRIES TO MANHOLE(MH) TO BE STREAMLINED TO PREVENT IRREGULAR FLOW. LS‐01 SUMP PIT COMPLETE WITH GUIDE RAIL, ISOLATION GRUNDFOS/ UNILIFT KP/
14. INVERT LEVELS FOR ALL MANHOLES TO BE WORKED OUT BY THE CONTRACTOR SUBMERSIBLE VALVES, PULL CHAIN, AUTOMATIC COUPLING, WILO WILO DRAIN EUROPE
ENSURING SELF CLEANING VELOCITIES.MIN. SLOPE OF 1:100. CONTROL PANEL, & LIQUID LEVEL CONTROL /LOWARA TM/DOMO
UNDER WITH SOUNDER/FLASHER ALARM. 1 1 0.37 240 1 50
VENT PIPE TO BE PROVIDED FOR FIRST AND LAST MANHOLES.
LS‐02 GROUND
15. LOCATION OF MANHOLES TO BE CO-ORDINATED WITH FOUNDATION AND LATEST PUMP ROOM KEY PLAN
LANDSCAPE/ARCHITECTURAL DRAWINGS.AND SHALL BE COORDINATED WITH THE SITE
LAYOUT PLAN.
16. THE INSTALLATION OF ALL PIPING, PIPE BEDDING AND BACKFILLING PROCEDURE
SHALL BE AS PER PIPE MANUFACTURER'S RECOMMENDATIONS & SDD STANDARDS. SUBMERSIBLE PUMPSET 7 1 3.7 415 3 50
GARBAGE GRUNDFOS/
17. TRAPS TO BE PROVIDED NEAR INDIVIDUAL SANITARY WARE/APPLIANCES AS PER LS‐03 SUBMERSIBLE (1DUTY,1ASSIST & 1 STANDBY)
ROOM WILO ‐ EUROPE
BS 5572. CONNECTIONS FROM SANITARY WARE/APPLIANCES TO BE COORDINATED COMPLETE WITH CUTTER / GRINDER, GUIDE
/LOWARA
WITH SANITARY WARE SCHEDULE AND DETAILED TOILET LAYOUTS. RAIL, ISOLATION VALVES, PULL CHAIN,
18. PIPES AT ROAD CROSSINGS TO BE PROTECTED WITH U.P.V.C. SLEEVES AND AUTOMATIC COUPLING, CONTROL PANEL, &
CONCRETE SURROUNDS. LIQUID LEVEL CONTROL WITH
19. ALL WASTE PIPES FROM SANITARY WARES TO BE TRAPPED FLOOR GULLY TO BE SOUNDER/FLASHER ALARM.
50Ø. UNLESS OTHERWISE SPECIFIED.
20. ALL UNDERGROUND SEWER PIPES AND FITTINGS FROM MANHOLE TO MANHOLE NOTE:
INCLUDING PIPES WITHIN THE BUILDING BLOCK PERIPHERY TO BE U.P.V.C TO
BS 4660 UNLESS OTHERWISE SPECIFIED. 1. CONTRACTOR SHALL SUBMIT HEAD CALCULATIONS AS PER SITE CONDITION, APPROVED SHOP DRAWINGS AND SUBMIT FOR CONSULTANT'S APPROVAL.
21. PIPE WORK ROUTES ARE DIAGRAMATIC. EXACT ROUTES TO BE INDICATED BY 2. CONTROL PANEL SHALL HAVE SOUNDER AND FLASHER EXTENDED OUTSIDE PUMP ROOM WALL.
CONTRACTOR ON WORKING DRAWINGS AND TO BE APPROVED BY ENGINEER.
22. INSIDE OF ALL MANHOLES TO BE PAINTED IN BLACK BITUMEN PAINT.
23. ALL SEWERAGE & SOAKPIT MANHOLE COVERS SHALL BE GRP HEAVY DUTY DOUBLE
SEAL TYPE, DUCTILE IRON TYPE AND SHALL BE RATED TO EN 124-D400
FOR VEHICULAR TRAFFIC AREA & C250 FOR OTHER AREA. MAKE THERMO DRAIN
OR APPROVED EQUIVALENT. PROVIDE RECESS TYPE DOUBLE SEALED
MANHOLE COVER FOR PAVED AREA AND ARTIFICIAL GRASS AREA. FOR SOFT
LANDSCAPE AREA THE COVER SHALL BE SOLID TYPE WITH GREEN COLOR TO
MATCH SOFT LANDSCAPE.
25. SEWERAGE COLLECTION SYSTEM TO BE IN ACCORDANCE WITH 'SEPPD'
GUIDELINE AND TO BS 8301.
26. ALL PIPES AND FITTINGS TO BE OF ' GULF PLASTICS'. OR APP. EQUAL.
27. PROVIDE FLOOR/CEILING CLEAN OUTS FOR ALL SOIL, STORM & WASTE PIPES WHEREVER
REQUIRED AND ACCESS COVER SHALL BE PROVIDED FOR RODDING EYE, CLEANOUTS.
28. ALL DRAINAGE WORKS SHALL BE COORDINATED WITH THE OTHER SERVICES,
STRUCTURAL AND ARCHITECTURAL REQUIREMENTS.
29. ALL FLOOR DRAINS GRATING PVC MATERIAL TO MATCH ADJACENT FLOOR FINISH/
COLOUR AND AS/ARCHITECTS APP.
30. CONDENSATE DRAIN PIPE SHALL BE UPVC PRESSURE PIPES AND SHALL BE
MINIMUM OF 32Ø AND TERMINATED TO NEAREST IRRIGATION TANK IN BASEMENT .ALL CONDENSATE
PIPE SHALL BE INSULATED AS MENTIONED IN HVAC DRG.
31. ALL WASTE CONNECTION SHALL HAVE BACK INLET GULLY(BIG) BEFORE
CONNECTING TO THE MANHOLE. PROVIDE SOLID BIG COVER AS PER SAMPLE APPROVAL
32. THE VENT PIPES SHALL BE TERMINATED WITH PROTECTIVE VENT COWL.
33. THE COMPLETE DRAINAGE WORK SHALL BE WITH UPVC PIPES & FITTING'S UNLESS
INDICATED OTHERWISE.
34. FINAL LOCATIONS OF ALL FLOOR DRAINS & FLOOR TRAPS SHALL BE
R-00 19-11-18 ISSUED FOR CONSTRUCTION
AS PER ID/ARCHITECT'S APPROVAL.
35. ALL WASTE , SOIL & STORM WATER PIPES RUNNING ABOVE GROUND LEVEL IN OCCUPIED AREA IN PROJECT STAGE
CEILING / AND INSIDE SHAFT SHALL BE LOW NOISE / ACOUSTIC TYPE . CONSTRUCTION DRAWINGS
36. ALL PIPES RUNNING ABOVE TO BE LABELED WITH FLOW DIRECTION.
37. ALL UNDER GROUND DRAINAGE PIPE WORK BELOW DRIVE WAY SHALL BE
PROTECTED WITH PROPER CONCRETE ENCASING AROUND PIPE SLEEVES , IF
THE PIPES ARE LAID WITH IN 1.5 m FROM FINISHED FLOOR LEVEL.
PROJECT NO 2017019 DRAWN AJC
REVIT FILE CHECKED SDK
DATE 19-11-18 VERIFIED SDK
SCALE NTS @ A1 APPROVED DTP
SHEET TITLE
DRAINAGE
NOTES & EQUIPMENT
SCHEDULE
SHEET NUMBER REVISION
MD-001 R-00