7 6 5 4 3 2 1

F1-132kV PHUNTSHOTHANG SUBSTATION TO 132 KV LINE - 1


NOTES:-
1. ALL DIMENSIONS AND LEVELS ARE IN METRES UNLESS
OTHERWISE SPECIFIED.
E E
LINE LA
145kV,10kA COMMON CONTROL BOARD(CCB)
2. NO DIMENSION SHOULD BE MEASURED FROM THE DRAWING.
LINE PT
132kV 110kV 110kV 110kV F
3 3 3 3

CORE-1CL0.2 F DMM LINE METERING


CORE-2CL0.5
CORE-2CL3P
A V FM kW kWH PF kVAr HMI

132kV SWITCHYARD LINE BAY-1


89L-ISO-2 CONFIGURATION SAME AS THAT OF F1
132kV,1250A
89L-E/S-2 LINE PROTECTION PANEL (LPP) LEGEND
52L LINE PROTECTION RELAY MAIN
40 LOSS OF FIELD RELAY
SF6,CB MEASUREMENT 46 NEGATIVE PHASE SEQUENCE RELAY
132kV,1250A 87 50BF 67N 27/59 51N 74-1
31.5kA/1sec
DISTURBANCE RECORD

87-OFC 87-RECEIVING END RELAY


50/51 DEFINITE /INVERSE TIME OVER CURRENT RELAY
LINE CT
810/U 21 50/51 25/79 VTS 74-2 FAULT RECORDS
NOTE: RECEIVING END RELAY SHALL BE SAME AS PER SENDING END
51V VOLTAGE CONTROLLED OVER CURRENT RELAY
IEC 61850
300-600-1200
/1/1/1/1/1/1A
52GT GENERATOR TRANSFORMER BREAKER
CL-0.2 86L LINE FAULTS
52L LINE BREAKER
E CL-0.2
CL0.5
CL-PS
CL-PS
LINE PROTECTION RELAY BACKUP
DISTURBANCE RECORD
59 OVER VOLTAGE RELAY
CL-PS
67 50BF 69N 81U 810 50/51 FAULT RECORDS 63 BUCHHOLZ OVER VOLTAGE /NEAUTRAL DISPLACEMENT RELAY
IEC 61850
59N RESIDUAL OVER VOLTAGE /NEAUTRAL DISPLACEMENT RELAY
89L-ISO-1 BUSBAR DIFFERENTIAL PROTECTION
132kV,1250A FROM GT-1 BAY
89LE LINE ISOLATOR WITH EARTH SWITCH
87BB 86BB
89LE-E/S-1 FROM GT-2 BAY 87G GENERATOR DIFFERENTIAL RELAY
87GT OVERALL GENERATOR TRANSFORMER DIFFERENTIAL RELAY
89L LINE ISOLATOR
89GT GENERATOR TRANSFORMER ISOLATOR
ACSR BUS 74 TRIP COIL SUPERVISION RELAY
66kV,1250AMP
24 OVER FLUXING RELAY
50BF LOCAL BREAKER BACK UP RELAY
132kV SWITCHYARD GT BAY-1

89GT1-ISO-2
66kV,1250A VTS VOLTAGE TRANSFORMER SUPERVISION RELAY
89GT1-E/S-1
89GT1-E/S-2 64G1 100% STATOR EARTH FAULT RELAY (BASED ON THIRD HARMONICS)
52GT1
64R RESTRICTED EARTH FAULT RELAY FOR TRANSFORMER
SF6,CB 67/67N DIRECTIONAL OVER CURRENT & EARTH FAULT RELAY
66kV,1250A 81 O/U OVER /UNDER FREQUENCY PROTECTION RELAY
31.5kA/1SEC 132kV BUS COUPLER
86GZ HIGH SPEED TRIP RELAY FOR GENERATOR FOR NON-URGENT FAULT
GT1-CT-2

BUS CVT
132kV 110kV110kV110kV
150/1/1/1/1/1A 3 3 3 3 86G HIGH SPEED TRIP RELAY FOR GENERATOR FOR URGENT FAULT
CL-0.2
86T HIGH SPEED TRIP RELAY FOR TRANSFORMER FAULT

RATING & SCHEME SHALL BE SAME AS GT-1 BAY


CORE-1:CL 1.0
CL-0.2
CORE-2:CL 0.2
CL-PS SPARE
CL-0.5
CORE-3:CL 3P 86L HIGH SPEED TRIP RELAY FOR LINE FAULTS
CL-PS
F F
GT1LA PART OF UNIT CONTROL BOARD-1 PART OF UNIT CONTROL BOARD-1
96kV,10kA
DMM GENERATOR TRANSFORMER METERING DMM GENERATOR TRANSFORMER METERING A AMMETER
D A V FM PF A V FM PF
AT AUXILIARY TRANSFORMER
kW kWH kVAr kW kWH kVAr

TO LPP FOR 87BB TO LPP FOR 87BB BPT BUS POTENTIAL TRANSFORMER
CT CURRENT TRANSFORMER
TO UPP-1 & UPP-2
ET EXCITATION TRANSFORMER
E FOR GT-1 & PROT E F FUSE
OVERHEAD CONDUCTOR G GENERATOR
GT-1 GT-2
TVM TRI-VECTOR METER
14.7MVA 3Ph 18MVA 3Nos.1Ø kW KILOWATT
GEN.TRANSFORMER

GEN.TRANSFORMER
66/11kV 11/132kV kVAR KILOVOLT AMPERE REACTIVE
,ONAN 50Hz,ONAN
,YNd11 OCTC,YNd11 LAVT LIGHTNING ARRESTOR & VOLTAGE TRANSFORMER
NCT-1 NIS NEUTRAL ISOLATING SWITCH
NCT-1 CL-PS
CL-PS NGT NEUTRAL GROUNDING TRANSFORMER
NCT NEUTRAL CURRENT TRANSFORMER
OLTC OVER LOAD TAP CHANGER
PF POWER FACTOR
11kV XLPE, CU. CABLE(UE) PT POTENTIAL TRANSFORMER
QDC QUADRATURE DROOP COMPENSATION
GT1-CT-1 GT2-CT-1
2800/1/1A DMM GT-LV METERING-1 DMM GT-LV METERING-2 1200/1/1A
CL-PS CL-PS
CL-O.5 A V FM kW A V FM kW CL-1.5
VOLTAGE VOLTAGE
kWH PF kVAr SIGNAL SIGNAL kWH PF kVAr
BUSBAR FROM BUS PT FROM BUS PT
BUSBAR
11kV,3Ø 11kV,3Ø
11kV MV SWITCHGEAR-1

11kV MV SWITCHGEAR-2
50Hz,2800A SAT MECHANICAL SAT MECHANICAL 50Hz,1600A
25kA/1SEC FAULT RELAYS FAULT RELAYS 25kA/1SEC
C BPT-1
SAT-1 LBS ELECTRICAL INTERLOCK SAT-2 LBS
11kV,400A BPT-2
11kV,400A
52G-1 (VCB) 10.5kV110kV110kV 25kA,1SEC 49W 63T
25kA,1SEC
10.5kV110kV110kV
52G-2 (VCB) GENERATOR
49W 63T 11kA,1600A
11kA,2800A 3 3 3 3 3 3
11kV MV SWITCHGEAR

11kV MV SWITCHGEAR

11kV MV SWITCHGEAR

11kV MV SWITCHGEAR
25kA,1SEC 31.5kA,1SEC
HRC FUSE DMM SAT METERING DMM SAT METERING HRC FUSE 3PHASE VACUUM CIRCUIT BREAKER
11kV,40A 11kV,40A
SAT-1 DMM A V FM kW A V FM kW SAT-2 DMM
G-1 CT CL-0.5 F F SAT-1E/S kWH PF kVAr kWH PF kVAr SAT-2 CT CL-0.5 NEUTRAL GROUNDING TRANSFORMER AND RESISTOR
2800/1/1/1A CL-3P 40/1A 40/1A CL-3P
CL-PS CL-0.5 CL-0.5 G-2 CT
SPARE 1200/1/1/1A
DMM DMM
CL-0.5 SAT-1E/S SAT-2E/S
CL-PS TRANSFORMER
CL-PS BUS GROUND DMM DMM BUS GROUND
FAULT SAT-1 LA SAT-2 LA FAULT CL-0.5
64BG 25 UCB 64BG 25 UCB CL-PS
12kV,10kA 12kV,10kA
3O ISOLATOR WITH EARTH SWITCH

UNIT CONTROL BOARD-1(UCB-1) 11kV XLPE, CU.CABLE(UE) 11kV XLPE, CU.CABLE(UE)


LIGHTNING ARRESTER
PT-1-1 F UCB GOVERNOR @ UNIT CONTROL + T-G TEMPERATURE CONTROL
F PT-2-1
11kV MV SWITCHGEAR

11kV MV SWITCHGEAR
10.5kV110kV110kV 110kV 25 DMM GENERATOR METERING 10.5kV110kV110kV 110kV
SAT-1 SAT-2
3 3 3 3
F 160kVA, 160kVA,
DG F
3 3 3 3
CURRENT TRANSFORMER
160kVA,3Ø

EMERGENCY SYSTEM
CORE-1:CL 0.5 11kV/415V,3Ph 11kV/415V,3Ph F CORE-1:CL 0.5
STATION AUX.TR

STATION AUX.TR

F A V FM kW kWH PF kVAr
CORE-2:CL 3P F WITH 0.4kV F CORE-2:CL 3P
CORE-2:CL 0.5
DYN11,AN DYN11,AN
AMF 50Hz CORE-2:CL 0.5 SURGE CAPACITOR
F SS F
25A - AUTO
AYNCHRONIZATION DG POTENTIAL TRANSFORMER

RATING & SCHEME SHALL BE SAME AS UNIT-1 BAY


ET-1 F F F F ET-2
11kV/(240V),3Ø
UNIT PROTECTION PANEL-1(UPP-1) E
EXTERNAL SOURCE
E 11kV/(240V),3Ø OUTDOOR TYPE SF6 CB
LA-1 LA-2
TRANSFORMER PROTECTION RELAY 11kV,10kA
11kV,10kA E 1.1kV XLPE, CU.CABLE 1.1kV XLPE, CU.CABLE 1.1kV XLPE, CU.CABLE 1.1kV XLPE, CU.CABLE E SC 0.25 µ F
SC 0.25 µF MEASUREMENT
87GT 50BF 59 27 32
DISTURBANCE RECORD
11kV XLPE, CU.CABLE(UE) 87-OFC
11kV XLPE, CU.CABLE(UE)
81U 810 50/51 24 VTS R LOADING RESISTOR
B FAULT RECORDS

12.5MW STATOR ROTOR DIGITAL IEC 61850


DIGITAL ROTOR STATOR 12.5MW RTD RESISTANCE TEMP. DETECTOR
SYN.GEN

SYN.GEN
AVR B1 BO 74-1 74-2 64 AVR
11kV F F F F LTPT-2 11kV
0.85PF AF VF
LTPT-1 27
30LT
27 27 27
400V 110V VF AF 0.85PF
260 OIL TEMPERATURE RELAY
400V 110V
RS485

RS485
G1 G2
50Hz PF kV
86T GT FAULTS 3 3 DMM SAT METERING DMM SAT METERING DMM SAT METERING DMM SAT METERING 3 3
kV
50Hz V VOLTMETER
CL-0.5 CL-0.5 Pf
STATIC EXCITATION GT-MECHANICAL FAULT RELAY
A V FM kW A V FM kW A V FM kW A V FM kW
STATIC EXCITATION VCB VACUUM CIRCUIT BREAKER
63 49W 260 30G
11kV XLPE, CU.CABLE(UE) LTPT-1,2 &3 LTPT-2 11kV XLPE, CU.CABLE(UE) VS VOLTAGE SELECTOR SWITCH
650/5/5A kWH PF kVAr kWH PF kVAr kWH PF kVAr kWH PF kVAr 400/5/5A
GENERATOR PROTECTION RELAY CL-1.0 CL-1.0 49W WINDING TEMPERATURE RELAY
CT-1-1
CL-5P20 51 51N 86 51 51N 86 51 51N 86 51 51N 86
CL-5P20
CT-2-1
27 UNDER VOLTAGE RELAY
87G 50BF 59 27 32 52SAT-1,2 &3 52DG(ACB) 32R REVERSE POWER RELAY
MEASUREMENT
1200/1/1/1A 1200/1/1/1A
DISTURBANCE RECORD 800A, 4P 630A, 4P
CL-PS(SPARE) 81U 810 50/51 40 46 FAULT RECORDS
ACB, FIXED TYPE
ELECTRICAL INTERLOCK ELECTRICAL INTERLOCK ELECTRICAL INTERLOCK
25kA,1SEC
CL-PS(SPARE) ACB AIR CIRCUIT BREAKER
CL-PS IEC 61850 CL-PS
SPARE 25kA,1SEC SPARE
400VLTAC PANEL

CL-0.5 64G 59N VTS 74-1 74-2 CL-0.5


BUS BAR
NGT PANEL - 1

NGT PANEL - 2
400V, 3Ø 4W CU
50Hz,800A
MCCB

MCCB
MPCB

MPCB

MPCB

MPCB

MPCB

NIS 86G URGENT FAULTS NIS


MCB

MCB

MCB

MCB

MCB

MCB

400A
86GZ NON-URGENT FAULTS
25kA,1SEC 400A
FOR FS REPORT
OUTGOING
NGT R FEEDERS R NGT
11kV/240V M M M M M
11kV/240V Consultant: Owner:
UNIT - 1&2 AUX.FDR. STATION AUX.FDR.
UNIT-1 UNIT-2
DRUK GREEN DEPARTMENT OF ENERGY
CONSULTANCY
D:\LOGO BHUTAN.png
MINISTRY OF ENERGY AND NATURAL RESOURCES

NOTE :- Date Revised Project: 25 MW BEGANA INTEGRATED MULTIPURPOSE


August 2023 date
1. SYNCHRONISING SHALL BE CARRIED OUT 11kV LEVEL SMALL HYDROPOWER PROJECT
A 2. DETAILED PARAMETERS OF NGR, CTS, PTS ETC SHALL BE FURNISHED AT LATER STAGE THIMPHU, BHUTAN
3. TWO NOS. OF EARTHING TRUCK SHALL BE PROVIDED ALONG WITH 11kV M V SWITCHGEAR PANEL ONE FOR Designed K.Phuntsho T.Dorjee
Verified Title:
CABLE EARTHING AND ONE FOR BUS EARTH
4. FOR LINE MAN PROTECTION(DIFFERENTIAL & DISTANCE PROTECTION) RELAY ALONG WITH
INTERFACE SHALL BE PROVIDED SIMILAR TO RELAY PROVIDED AT RECEIVING SUBSTATION . COMMUNICATION Reviewed D.Singer Approved C.Tenzin MAIN SINGLE LINE DIAGRAM
BETWEEN THESE TWO RELAYS SHALL BE THROUGH FIBRE OPTIC CABLE .

Drawn K.Pem Scale AS SHOWN Drawing No.


THIS DRAWING IS MEANT FOR FSR 0
NOT TO BE USED FOR CONSTRUCTION. BIMSHP-EMD-2023-01 Rev.
Aug 29, 2023 - 9:32am