0% found this document useful (0 votes)
71 views10 pages

Sprinkler TC

The document provides technical information on the TYCO Series TY-B and TY-FRB Poly-Stainless Sprinklers, which are designed for use in corrosive environments. It includes details on their specifications, installation requirements, and compliance with safety standards. Additionally, it highlights the importance of consulting with end users regarding the suitability of the sprinklers for specific corrosive conditions.

Uploaded by

KAIVALYA TIWATNE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views10 pages

Sprinkler TC

The document provides technical information on the TYCO Series TY-B and TY-FRB Poly-Stainless Sprinklers, which are designed for use in corrosive environments. It includes details on their specifications, installation requirements, and compliance with safety standards. Additionally, it highlights the importance of consulting with end users regarding the suitability of the sprinklers for specific corrosive conditions.

Uploaded by

KAIVALYA TIWATNE
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Worldwide

www.tyco-fire.com
Contacts

Series TY-B and TY-FRB


Poly-Stainless Sprinklers
TY-FRB Series
IMPORTANT • 3 mm diameter heat sensitive glass
Refer to Technical Data Sheet bulb
TFP2300 for warnings pertaining to • Quick response (QR) rating
regulatory and health information.
Although corrosion resistant sprinklers
Always refer to Technical Data have passed the standard corrosion
Sheet TFP700 for the “INSTALLER tests of the applicable approval agen-
WARNING” that provides cautions cies, the testing is not representative
with respect to handling and instal- of all possible corrosive atmospheres.
lation of sprinkler systems and com- Consequently, it is recommended that
ponents. Improper handling and the end user be consulted with respect
installation can permanently damage to the suitability of this coating material
a sprinkler system or its compo- for any given corrosive environment.
nents and cause the sprinkler to fail The effects of ambient temperature,
to operate in a fire situation or cause concentration of chemicals, and gas/
it to operate prematurely. chemical velocity, should be consid-
ered, at a minimum, along with the cor-
rosive nature of the chemical to which
Scan the QR code or enter the URL the sprinklers will be exposed.
in a web browser to access the most
up-to-date electronic version of this Upright and Pendent Sprinklers
document. Data rates may apply. The upright and pendent sprinklers are
standard coverage spray sprinklers
available in either 5.6 or 8.0 K-factor.
The recessed version is intended for
use in areas with a finished ceiling.
The two-piece Style 10 (1/2 inch NPT) tection Association, in addition to the
or Style 40 (3/4 inch NPT) recessed standards of any authorities having
escutcheons provide 1/2 inch (12,7 jurisdiction. Failure to do so may impair
mm) of recessed adjustment or 3/4 inch the performance of these devices.
(19,1 mm) of total adjustment from the
flush pendent position. The adjustment The owner is responsible for main-
provided by the recessed escutcheon taining their fire protection system
reduces the accuracy to which the fixed and devices in proper operating con-
pipe drops to the sprinklers must be dition. Contact the installing contrac-
cut. tor or product manufacturer with any
docs.jci.com/tycofire/tfp682 questions.
Horizontal Sidewall Sprinklers

General
The horizontal sidewall sprinklers are
designed for installation along a wall Sprinkler
Description
or side of a beam and just beneath a
smooth ceiling. Sidewall sprinklers are Identification
The TYCO Series TY-B and TY-FRB
commonly used instead of upright and
pendent sprinklers due to aesthetics or Number (SIN)
Poly-Stainless Sprinklers are corrosion building construction considerations,
where piping across the ceiling is not TY-B Standard Response
resistant sprinklers designed for use in TY3151 ����� Upright 5.6K, 1/2 in. NPT
commercial occupancies where corro- desirable.
TY3251 ���� Pendent 5.6K, 1/2 in. NPT
sive atmospheres may exist. A recessed version of the horizon- TY4151 ������� Upright 8.0K, 3/4 in. NPT
The series characteristics are as tal sidewall sprinkler can be achieved
by using the Style 10 recessed TY4251 ����Pendent 8.0K, 3/4 in. NPT
follows: TY3351 �������� HSW* 5.6K, 1/2 in. NPT
escutcheon.
TY-B Series TY-FRB Quick Response
• 5 mm diameter heat sensitive glass NOTICE TY3131 ����� Upright 5.6K, 1/2 in. NPT
bulb
The Series TY-B and TY-FRB Sprinklers TY3231 ���� Pendent 5.6K, 1/2 in. NPT
• Standard response (SR) rating
described herein must be installed TY4131 ������� Upright 8.0K, 3/4 in. NPT
and maintained in compliance with TY4231 ����Pendent 8.0K, 3/4 in. NPT
this document and with the applica- TY3331 �������� HSW* 5.6K, 1/2 in. NPT
ble standards of the National Fire Pro- * = Horizontal Sidewall

Page 1 of 10 AUGUST 2022 TFP682


TFP682
Page 2 of 10

Model Bulb Sprinkler


Temperature Material
K-Factor Type Liquid
Rating
Response Color Brass
135°F (57°C) Orange
155°F (68°C) Red
Upright
TY3151 175°F (79°C) Yellow
and
Pendent 200°F (93°C) Green
TY3251
TY-B 286°F (141°C) Blue
5.6 360°F (182°C) Mauve
1/2 in. NPT
SR 135°F (57°C) Orange
Recessed* 155°F (68°C) Red
Pendent
TY3251 175°F (79°C) Yellow

See Figure 1 200°F (93°C) Green


286°F (141°C) Blue
1, 2, 3
135°F (57°C) Orange
155°F (68°C) Red
Upright
TY4151 175°F (79°C) Yellow
and
Pendent 200°F (93°C) Green
TY4251
TY-B 286°F (141°C) Blue
8.0 360°F (182°C) Mauve
3/4 in. NPT
SR 135°F (57°C) Orange
Recessed** 155°F (68°C) Red
Pendent
TY4251 175°F (79°C) Yellow

See Figure 1 200°F (93°C) Green


286°F (141°C) Blue
NOTES:
1. UL Listed
2. C-UL Listed
3. EAC Approved
* Installed with Style 10 (1/2 NPT) Recessed Escutcheon
** Installed with Style 40 (3/4 NPT) Recessed Escutcheon

TABLE A
POLY-STAINLESS SERIES TY-B STANDARD RESPONSE
5.6 AND 8.0 K-FACTOR UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS

Technical Physical Characteristics


Frame . . . . . . . . . . . . . . . Polyester coated Brass Operation
Data
Button. . . . . . . . . . . . . . . . . L316 Stainless Steel*
Compression Screw ����������L316 Stainless Steel* The glass bulb contains a fluid which
Bulb ������������������������������������������������������������� Glass expands when exposed to heat. When
Approvals Deflector ������������������������������������� Copper/Bronze the rated temperature is reached, the
UL and C-UL Listed Sealing Assembly. . Gold Plated Beryllium Nickel fluid expands sufficiently to shatter the
w/TEFLON**
EAC Approved glass bulb, allowing the sprinkler to
Note: For complete approvals information,
*Type L316 stainless steel (UNS 31603) per ASTM activate and water to flow.
A479/479M or BS EN 1008 WN1.4404.
see Tables A, B, and C.
Design
**Beryllium Nickel (UNS NO3360) Gold Plated per MIL
G-45204, Type 3, Class 2.
Maximum Working Pressure
175 psi (12,1 bar)
Temperature Rating
Criteria
See Tables A, B, C, and D The TYCO Series TY-B and TY-FRB
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency - for example, the UL
Listing is based on the requirements
of NFPA 13. Only the Style 10 or 40
Recessed Escutcheon, as applicable,
is to be used for recessed installation.
TFP682
Page 3 of 10

Model Bulb Sprinkler


Temperature Material
K-Factor Type Liquid
Rating
Response Color Brass
135°F (57°C) Orange
Upright 155°F (68°C) Red
TY3131
and 175°F (79°C) Yellow
Pendent
TY3231 200°F (93°C) Green
TY-FRB
5.6 286°F (141°C) Blue
1/2 in. NPT 135°F (57°C) Orange
QR
Recessed 155°F (68°C) Red
Pendent*
TY3231 175°F (79°C) Yellow

See Figure 2 200°F (93°C) Green


286°F (141°C) Blue
1, 2, 3
135°F (57°C) Orange
Upright 155°F (68°C) Red
TY4131
and 175°F (79°C) Yellow
Pendent
TY4231 200°F (93°C) Green
TY-FRB
8.0 286°F (141°C) Blue
3/4 in. NPT 135°F (57°C) Orange
QR
Recessed 155°F (68°C) Red
Pendent**
TY4231 175°F (79°C) Yellow

See Figure 4 200°F (93°C) Green


286°F (141°C) Blue
NOTES:
1. UL Listed
2. C-UL Listed
3. EAC Approved
* Installed with Style 10 (1/2 NPT) Recessed Escutcheon
** Installed with Style 40 (3/4 NPT) Recessed Escutcheon

TABLE B
POLY-STAINLESS SERIES TY-FRB QUICK RESPONSE
5.6 AND 8.0 K-FACTOR UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP682
Page 4 of 10

Model Bulb Sprinkler


Temperature Material
K-Factor Type Liquid
Rating
Response Color Brass
135°F (57°C) Orange
155°F (68°C) Red
Horizontal 175°F (79°C) Yellow
Sidewall
TY3351 200°F (93°C) Green
TY-B 286°F (141°C) Blue
5.6 360°F (182°C) Mauve
1/2 in. NPT
SR 135°F (57°C) Orange
Recessed
Horizontal 155°F (68°C) Red
Sidewall* 175°F (79°C) Yellow
TY3351
200°F (93°C) Green
See Figure 5
286°F (141°C) Blue 1, 2, 3
135°F (57°C) Orange
155°F (68°C) Red
Horizontal
Sidewall 175°F (79°C) Yellow
TY3331
200°F (93°C) Green
TY-FRB
5.6 286°F (141°C) Blue
1/2 in. NPT 135°F (57°C) Orange
QR Recessed
Horizontal 155°F (68°C) Red
Sidewall* 175°F (79°C) Yellow
TY3331
200°F (93°C) Green
See Figure 6
286°F (141°C) Blue
NOTES:
1. UL Listed
2. C-UL Listed
3. EAC Approved
* Installed with Style 10 (1/2 NPT) Recessed Escutcheon
TABLE C
POLY-STAINLESS SERIES TY-B STANDARD RESPONSE
AND POLY-STAINLESS SERIES TY-FRB QUICK RESPONSE
5.6 K-FACTOR HORIZONTAL SIDEWALL SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP682
Page 5 of 10

WRENCH 1/2" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression * Temperature


FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector * on Deflector.
1

7/16" 3
(11,1 mm)
NOMINAL 2-3/16" 2
MAKE-IN (55,6 mm)
4
2-3/16" 1-1/2"
(55,6 mm) (38,1 mm) 5

6*
STYLE 10 2-7/8" (73,0 mm) DIA.
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 1
POLY-STAINLESS SERIES TY-B STANDARD RESPONSE
UPRIGHT (TY3151) AND PENDENT (TY3251) 5.6 K-FACTOR 1/2 INCH NPT SPRINKLERS

WRENCH 1/2" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression * Temperature


FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector * on Deflector.
1

7/16" 3
(11,1 mm)
NOMINAL 2-3/16" 2
MAKE-IN (55,6 mm)
4
2-3/16" 1-1/2"
(55,6 mm) (38,1 mm) 5

6*
STYLE 10 2-7/8" (73,0 mm) DIA.
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 2
POLY-STAINLESS SERIES TY-FRB QUICK RESPONSE
UPRIGHT (TY3131) AND PENDENT (TY3231) 5.6 K-FACTOR 1/2 INCH NPT SPRINKLERS

WRENCH 3/4" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression * Temperature


FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector * on Deflector.
1

1/2" 3
(12,7 mm)
NOMINAL 2
MAKE-IN 2-5/16"
(58,7 mm)
4
2-1/4" 1-9/16"
(57,2 mm) (39,7 mm) 5

6*
STYLE 40 2-7/8" (73,0 mm) DIA.
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 3
POLY-STAINLESS SERIES TY-B STANDARD RESPONSE
UPRIGHT (TY4151) AND PENDENT (TY4251) 8.0 K-FACTOR 3/4 INCH NPT SPRINKLERS
TFP682
Page 6 of 10

WRENCH 3/4" ESCUTCHEON 1 - Frame 3 - Sealing 5 - Compression * Temperature


FLATS NPT PLATE SEATING 2 - Button Assembly Screw rating indicated
SURFACE 4 - Bulb 6 - Deflector * on Deflector.
1

1/2" 3
(12,7 mm)
NOMINAL 2
MAKE-IN 2-5/16"
(58,7 mm)
4
2-1/4" 1-9/16"
(57,2 mm) (39,7 mm) 5

6*
STYLE 40 2-7/8" (73,0 mm) DIA.
RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 4
POLY-STAINLESS SERIES TY-FRB QUICK RESPONSE
UPRIGHT (TY4131) AND PENDENT (TY4231) 8.0 K-FACTOR 3/4 INCH NPT SPRINKLERS

1 - Frame
DEFLECTOR Installation
HAT 5 The TYCO Series TY-B and TY-FRB
-
2 Button
3 - Sealing sprinklers must be installed in accor-
Assembly dance with this section.
4 - Bulb General Instructions
5 - Compression Do not install any bulb type sprinkler
Screw if the bulb is cracked or there is a loss
6 - Deflector * of liquid from the bulb. With the sprin-
6* 4 2 3 1
kler held horizontally, a small air bubble
9/16" WRENCH 1/2" should be present. The diameter of the
(14,3 mm) FLATS NPT air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) and 3/32
inch (2,4 mm) for the 360°F (182°C)
temperature ratings.
A 1/2 inch NPT sprinkler joint should be
obtained with a minimum to maximum
torque of 7 to 14 ft-lbs (9,5 to 19,0 Nm).
A 3/4 inch NPT sprinkler joint should be
1-13/16" 7/16" obtained with a minimum to maximum
(46,0 mm) (11,1 mm) torque of 10 to 20 ft-lbs (13,4 to 26,8
CENTERLINE NOMINAL Nm). Higher levels of torque may distort
OF SPRINKLER MAKE-IN the sprinkler inlet and cause leakage or
WATERWAY impairment of the sprinkler.
1-1/2"
(38,1 mm) Do not attempt to compensate for
ESCUTCHEON
insufficient adjustment in the sprinkler
PLATE SEATING 2-3/16" by under- or over-tightening the sprin-
SURFACE (55,6 mm) kler. Re-adjust the position of the sprin-
kler fitting to suit.

STYLE 10
RECESSED
ESCUTCHEON

* Temperature rating is
indicated on Deflector

2-7/8" DIA.
(73,0 mm)

FIGURE 5
POLY-STAINLESS SERIES TY-B STANDARD RESPONSE HORIZONTAL
SIDEWALL (TY3351) 5.6 K-FACTOR 1/2 INCH NPT SPRINKLERS
TFP682
Page 7 of 10

Upright and Pendent Sprinklers


The Poly-Stainless Series TY-B and DEFLECTOR
1 - Frame 5
TY-FRB Upright and Pendent Sprin- HAT
2 - Button
klers must be installed in accordance
3 - Sealing
with the following instructions: Assembly
Step 1A. Upright sprinklers must be 4 - Bulb
installed in the upright position, and 5 - Compression
pendent sprinklers are to be installed Screw
in the pendent position. 6 - Deflector *
6* 4 2 3 1
Step 2A. With pipe thread sealant
applied to the pipe threads, hand
9/16" WRENCH 1/2"
tighten the sprinkler into the sprinkler (14,3 mm) FLATS NPT
fitting.
Step 3A. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench, refer to Figure 10.
With reference to Figures 1, 2, 3, and 4,
apply the W-Type 6 Sprinkler Wrench to
the sprinkler wrench flats.
Recessed Pendent Sprinklers 1-13/16" 7/16"
The Poly-Stainless Series TY-B and (46,0 mm) (11,1 mm)
TY-FRB Recessed Pendent Sprinklers CENTERLINE NOMINAL
must be installed in accordance with OF SPRINKLER MAKE-IN
the following instructions: WATERWAY
1-1/2"
Step 1B. After installing the Style 10 (38,1 mm)
or 40 Mounting Plate, as applicable, ESCUTCHEON
over the sprinkler threads and with PLATE SEATING 2-3/16"
pipe sealant applied to the sprinkler SURFACE (55,6 mm)
threads, hand tighten the sprinkler into
the sprinkler fitting.
STYLE 10
Step 2B. Tighten the sprinkler into the RECESSED
sprinkler fitting using only the W-Type ESCUTCHEON
7 Recessed Sprinkler Wrench, refer to
Figure 11. With reference to Figures
1, 2, 3, and 4 apply the W-Type 7 * Temperature rating is
indicated on Deflector
Recessed Sprinkler Wrench to the
sprinkler wrench flats.
Step 3B. After the ceiling has been
installed or the finish coat has been
2-7/8" DIA.
applied, slide the Style 10 or 40 Closure (73,0 mm)
over the sprinkler and push the Closure
over the Mounting Plate until it comes
in contact with the ceiling mounting
surface. FIGURE 6
Horizontal Sidewall Sprinklers POLY-STAINLESS SERIES TY-FRB QUICK RESPONSE HORIZONTAL
The Poly-Stainless Series TY-B and SIDEWALL (TY3331) 5.6 K-FACTOR 1/2 INCH NPT SPRINKLERS
TY-FRB Horizontal Sprinklers must be
installed in accordance with the follow-
Recessed Horizontal Sidewall Step 3E. Tighten the sprinkler into the
ing instructions:
Sprinklers sprinkler fitting using only the W-Type
Step 1C. Horizontal sprinklers must The Poly-Stainless Series TY-B and 7 Recessed Sprinkler Wrench, refer to
be positioned in the horizontal position TY-FRB Recessed Horizontal Sidewall Figure 11. Apply the W-Type 7 Sprinkler
with their centerline of waterway per- Sprinklers must be installed in accor- Wrench to the wrench flats shown in
pendicular to the back wall and parallel dance with the following instructions: Figure 5 and Figure 6.
to the ceiling. The word “TOP” on the
Step 1E. Recessed horizontal sidewall Step 4E. After the wall has been
deflector is to face towards the ceiling.
sprinklers are to be positioned in the installed or the finish coat has been
Step 2C. With pipe thread sealant horizontal position with their centerline applied, slide the Style 10 Closure over
applied to the sprinkler threads, hand of waterway perpendicular to the back the sprinkler and push the Closure over
tighten the sprinkler into the sprinkler wall and parallel to the ceiling. The the Mounting Plate until it comes in
fitting. word “TOP” on the deflector is to face contact with the wall mounting surface.
Step 3C. Tighten the sprinkler into the towards the ceiling.
sprinkler fitting using only the W-Type Step 2E. After installing the Style 10
6 Sprinkler Wrench, as shown in Figure Mounting Plate over the sprinkler
10. Apply the W-Type 6 Sprinkler threads and with pipe thread sealant
Wrench to the wrench flats shown in applied to the sprinkler threads, hand
Figure 5 and Figure 6. tighten the sprinkler into the sprinkler
fitting.
TFP682
Page 8 of 10

2-7/8" DIA. 2-7/8" DIA.


(73,0 mm) 3/4" (19,1 mm) (73,0 mm) 3/4" (19,1 mm)
5/8±1/4" 5/8±1/4"
(15,9±6,4 mm) 1/4" (6,4 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
2-1/4" DIA.
(57,2 mm) (57,2 mm)
FACE OF MOUNTING FACE OF MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8" 1/8"
(3,2 mm) (3,2 mm)

MOUNTING MOUNTING
SURFACE SURFACE

TY3231 or 1-1/4" (31,8 mm) CLOSURE TY4231 or 1-5/16" (33,3 mm)


CLOSURE
TY3251 3/4" (19,1 mm) TY4251 13/16" (20,6 mm)
FIGURE 7 FIGURE 8
POLY-STAINLESS SERIES TY-B OR TY-FRB POLY-STAINLESS SERIES TY-B OR TY-FRB
RECESSED PENDENT 5.6 K-FACTOR 1/2 INCH NPT RECESSED PENDENT 8.0 K-FACTOR 3/4 INCH NPT
SPRINKLER ASSEMBLY SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 40 RECESSED ESCUTCHEON

5/8±1/4"
(15,9±6,4 mm)

FACE OF WRENCH RECESS


MOUNTING
SPRINKLER (END "A" USED FOR
SURFACE
FITTING 1/2" NPT MODELS)

CLOSURE
WRENCH RECESS
(END "B" USED FOR
2-7/8" DIA. 3/4" NPT MODELS)
(73,0 mm)
TY3331 or FIGURE 10
TY3351 2-1/4" DIA. W-TYPE 6 SPRINKLER WRENCH
(57,2 mm)

WRENCH
MOUNTING RECESS
PLATE

1/8"
(3,2 mm)

1-1/4" (31,8 mm) 3/4" (19,1 mm)


3/4" (19,1 mm) 1/4" (6,4 mm)
PUSH WRENCH
FIGURE 9 IN TO ENSURE
POLY-STAINLESS SERIES TY-B OR TY-FRB ENGAGEMENT
RECESSED HORIZONTAL SIDEWALL WITH SPRINKLER
5.6 K-FACTOR 1/2 INCH NPT WRENCHING AREA
SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT FIGURE 11
STYLE 10 RECESSED ESCUTCHEON W-TYPE 7 SPRINKLER WRENCH
TFP682
Page 9 of 10

Care and P/N 57 — XXX — X — XXX


Maintenance
The TYCO Series TY-B and TY-FRB
Sprinklers must be maintained and ser-
viced in accordance with this section. Standard Response (SR) SIN Temperature Rating
Before closing a fire protection system 570 TY-B 5.6K Upright SR TY3151 135 135°F (57°C)
main control valve for maintenance
work on the fire protection system that 590 TY-B 8.0K Upright SR TY4151 155 155°F (68°C)
it controls, permission to shut down the 571 TY-B 5.6K Pendent SR TY3251 175 175°F (79°C)
affected fire protection system must be
591 TY-B 8.0K Pendent SR TY4251 200 200°F (93°C)
obtained from the proper authorities
and all personnel who may be affected 578 TY-B 5.6K HSW SR TY3351 286 286°F (141°C)
by this action must be notified. 360 360°F (182°C)*
The owner must assure that the sprin- Quick Response (QR) SIN * TY-B - Only
klers are not used for hanging of any
objects; otherwise, non-operation in 370 TY-FRB 5.6K Upright QR TY3131
the event of a fire or inadvertent oper- Sprinkler Finish
390 TY-FRB 8.0K Upright QR TY4131
ation may result. 2 Grey Aluminium (RAL9007)
371 TY-FRB 5.6K Pendent QR TY3231
Absence of an escutcheon, which is
used to cover a clearance hole, may 391 TY-FRB 8.0K Pendent QR TY4231
delay the time to sprinkler operation in 378 TY-FRB 5.6K HSW QR TY3331
a fire situation.
TABLE D
Sprinklers that are found to be leaking POLY-STAINLESS SERIES TY-B AND TY-FRB
or exhibiting visible signs of corrosion UPRIGHT, PENDENT AND HORIZONTAL SIDEWALL SPRINKLERS
must be replaced. PART NUMBER SELECTION
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Thereafter, annual inspections accord-
ing to NFPA 25 should suffice; however, Limited
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
instead of inspecting from the floor
level, a random sampling of close-up Warranty
corrosive products of combustion, but visual inspections should be made, so For warranty terms and conditions, visit
have not operated, should be replaced as to better determine the exact sprin- www.tyco-fire.com.
if they cannot be completely cleaned kler condition and the long term integ-
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
rity of the corrosion resistant material
of construction, as it may be affected Ordering
Care must be exercised to avoid
damage to the sprinklers before,
by the corrosive conditions present.
The owner is responsible for the
Procedure
during, and after installation. Sprin- inspection, testing, and maintenance of Contact your local distributor for
klers damaged by dropping, striking, their fire protection system and devices availability. When placing an order,
wrench twist/slippage, or the like, must in compliance with this document, as indicate the full product name and Part
be replaced. Also, replace any sprinkler well as with the applicable standards Number (P/N).
that has a cracked bulb or that has lost of the National Fire Protection Associ- Sprinkler Assemblies
liquid from its bulb. For more informa- ation such as NFPA 25, in addition to Specify: (specify SIN), (specify Stan-
tion, see the Installation section. the standards of any other authorities dard Response or Quick Response),
Frequent visual inspections are rec- having jurisdiction. Contact the install- (specify K-factor), (specify) tempera-
ommended to be initially performed ing contractor or product manufacturer ture rating, (specify Upright, Pendent
for corrosion resistant sprinklers, after with any questions. or HSW), P/N (specify from Table D)
the installation has been completed, Automatic sprinkler systems should be Recessed Escutcheon
to verify the integrity of the corrosion inspected, tested, and maintained by a Specify: Style (specify 10 or 40)
resistant material of construction. qualified Inspection Service in accor- Recessed Escutcheon, Grey Aluminum
dance with local requirements and/or (RAL9007) finish, P/N (specify*)
national codes.
*Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler
Wrench, P/N 56-850-4-001
TFP682
Page 10 of 10

1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220


© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC