Pz1-08 (22) Chikhli Pra Shala Una Gir Somnath

The document is a structural drawing for a project at Chikhli Pra Shala in Una, Gir Somnath, Gujarat, prepared by Akshar Corporation. It includes detailed specifications for materials, dimensions, and construction methods for various structural elements such as columns, beams, and footings. The design adheres to specific standards and guidelines, ensuring compliance with safety and quality requirements.

Uploaded by

dapova9321
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views12 pages

Pz1-08 (22) Chikhli Pra Shala Una Gir Somnath

The document is a structural drawing for a project at Chikhli Pra Shala in Una, Gir Somnath, Gujarat, prepared by Akshar Corporation. It includes detailed specifications for materials, dimensions, and construction methods for various structural elements such as columns, beams, and footings. The design adheres to specific standards and guidelines, ensuring compliance with safety and quality requirements.

Uploaded by

dapova9321
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

STRUCTURAL DRAWING

CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL


AT: - CHIKHLI PRA SHALA
TA : - UNA, DIST:- GIR SOMNATH
FOR S.S.A. GANDHINAGAR, GUJARAT
C:\Users\AKSHAR2\Desktop\samagra shiksha logo.png
PROJECT NO :- S.S.A/25-26/PZ1-08/ASPER SITE LAYOUT-SITE
AKSHAR CORPORATION
STRUCTURAL DESIGNERS
SPECIFIC/REVISE SOIL/CHIKHLI PRA SHALA/22
24, THIRD FLOOR, SHUKAN MALL, SHAHIBAUG, AHMEDABAD-04
PHONE: - 9426002014,9979851794, E-Mail : [email protected], SHEET NO :- 1 TO 11
1 2 3 4 5 6
LONG STEEL TOP BAR
SHORT STEEL
A
TYPICAL SLAB SECTION BOTTOM BAR
A
RING AS PER
COLUMN SCHEDULE COLUMN
TOP BAR
RING AS PER
NOT LESS THAN Ld COLUMN SCHEDULE
150 STIRRUPS SPACING
TYP.
LAP SPLICE IN BEAM BOTTOM BAR TYP.DETAILS.OF A BEAM -COLUMN JUNCTION
LD - DEVELOPMENT LENGTH
NO LAP SHALL BE PROVIDED IN "2 x EFFECTIVE DEPTH
OF BEAM" FROM FACE OF SUPPORT.

10 TIMES OF DIA

WHICHEVER
75mm MIN OR

IS MORE
OF BAR(T)
COLUMN.
B F.F.SLAB B
`A'
NOTE :

10d(> 75mm)
01. THIS DRAWING SHOULD READ IN CONJUCTION WITH ARCH. DRAWING OF SSA AT TIME OF DESIGN OF BUILDING.
02. THE BUILDING IS DESIGN FOR G.F.+ ONE + FUTURE STOREY ONLY. OPEN
CONFINE ZONE : CONFING 8T@75 c/c

CONFINE
03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. & M25 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE. TIE

ZONE
(1) L0/6 REINFORCEMENT
04. ALL R.C.C. SHALL BE MACHINE MIXED & MACHINE VIBRATED. (2) DEPTH OF COLUMN
05. MINIMUM CEMENT CONTENT AS PER MIX DESIGN OR AS PER IS:456. (3) 450 OR WHICH IS MORE
06. CLEAR COVER FOR ALL R.C. WORKS TO BE AS FOLLOWS. # FOOTING & RAFT 50 MM. # COLUMN BELOW GROUND 40 MM. DETAIL AT: 'A' FOR COL
# COLUMN ABOVE GROUND 40 MM. TO RINGS. # BEAMS BOTTOM 25 MM. # BEAMS TOP & SIDES 25 MM. # SLABS & HOOK IN OPEN TIES

L0
8T@150c/c
CHHAJJA 20 MM. # PEDESTAL 40 MM. # R.C. WALLS 20 MM. (Rest)
07. LAP LENGH FOR TMT BAR FOR CONCRETE GRADE M20 IS 57D, M25 IS 49D AND M30 IS 46D, WHERE D = DIA OF BAR..
08. PERIOD FOR REMOVAL OF CENTERING FROM THE DATE OF CONCRETINGS SLAB BOTTOM UP TO 4.5mt SPAN 7 DAYS, 40mm CLEAR COVER

LENGTH
TO STIRRUPS 900mm CENTER STAGGED LAPS
SLAB SPAN MORE THAN 4.5mt 14 DAYS, BEAM BOTTOM UP TO 6.0mt SPAN 14 DAYS, BEAM SPAN MORE THAN 6.0 mt 21 SHOULD BE ACCOMODATED IN

LAP
DAYS, CANTILEVER BEAM BOTTOM 21 DAYS, BEAM SIDES 1 DAYS, COLUMN SIDES 1 DAYS. THIS AREA ONLY SPACING OF

45°
STIRRUPS IS 8T@150 c/c
09. R.C. CONCRETE SHOULD BE CURED FOR A MINIMUM PERIOD OF 10 DAYS.
10. ALL MATERIAL SUCH AS STEEL, CEMENT, SAND & METAL SHALL CONFIRM TO I.S. SPECIFICATION & ALL WORKS SHALL 8T@150c/c

d
F.G.L. & N.G.L. CHECK &

10
BE DONE IN A WORKMAN LIKE MANNER. VERIFY AS PER CONTOUR (Rest)
11. PROPER CHAIRS & GHODAS TO BE PROVIDED FOR TOP BAR OF CANTILEVERED, CHHAJJAS & BENT UP BARS IN SLABS PLAN 8T@75 c/c
TO KEEP THEM IN POSITION. CONFING 8T@75 c/c

CONFINE
ZONE
12. IF ANY DISCRIPENCY IN DWG. SHALL BE BROUGHT NOTICE TO REINFORCEMENT
DETAIL: X-1
STRUCTURAL ENGINEER WELL BEFORE EXECUTION. N.G.L. TOP STEEL
(TYP.) F.G.L. B PILE CAPE PC1
13. ALL STIRRUPS SHALL BE HOOK BENT AT 135° TO 75 LONG AND START 50mm AWAY FROM THE FACE OF SUPPORT..
14. THE CEMENT SHOULD BE CONFIRMING TO GRADE 53 ONLY. C

DEPTH
15. ALL REINFORCEMENT SHOULD CRS BAR CONFIRMING TO PLINTH
SFR BEAM
I.S. 1786 & STEEL GRADE SHALL BE FE-500.
C 300 150
16. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE. 150
17. VERIFY C/C MEASUREMENT WITH ARCHITECTURAL DRAWING. P.C.C.M15

150
12-20 T

2 X PILE
TOP STEEL

DIA.
18. ALL C:M (1:6) FOR ALL AAC BLOCK WORK & MINIMUM DENSITY OF BLOCK IS 8 TO 10 kN/cmt. BOTTOM B
19. LIVE LOAD ON FLOOR AS PER IS:875 - 1987 PART-2 AND TERRACE WATER PROFFING LOAD IS 2.75 kN/SQ.mt. STEEL

DEPTH
20. THE BUILDING IS DESIGNED FOR SEISMIC FORCES AS PER IS 1893-2016 (PART-1) [ WITH IMPORTANCE FACTOR I=1.5]. S.F.R 4-12 T 8T@100c/c
8T@100c/c
21. NO RAIN WATER PIPE ON SANITARY PIPE SHALL BE TAKEN THROUGH R.C.C. COLUMN. PILE VERTICAL
22. FOUNDATION SHOULD NOT BE LAID OVER EXPANSIVE, BLACK OR FILLED UP SOIL. STIRRUPS STEEL
23. ALL C:M (1:6) FOR ALL MASONARY WORK UP TO PLINTH IS WHITE STONE BELA DENSITY OF BRICK IS 20 kN/cmt & AAC 500Ø
BLOCK WORK ABOVE PLINTH MINIMUM DENSITY OF AAC BLOCK IS 8 kN/cmt. WIDTH
BOTTOM STEEL
500Ø PILE 500Ø PILE
24. STATIC INITIAL LOAD TEST FOR PILE SHALL BE CARRIED OUT FOR THE TEST LOAD OF 2.5 X 31.5T = 78.75T AND ROUTINE
SECTION : B - B SECTION : A-A
LOAD TEST FOR PILE SHALL BE CARRIED OUT FOR THE TEST LOAD OF 1.5 X 31.5T = 47.25T FOR PILE UNDER 8T@150c/c 8T@150c/c

10000
PIER/COLUMN AS PER I.S. 2911.PART-IV. REST
25. PILE SHALL BE CAST THRULY VERTICAL & CONCRETING SHALL BE DONE UNINTERRAPTED AS PER IS.2911.
D/2+150 D X 3 TIMES D/2+150 A A A A
26. THE EMBANKMENT OF PILE INTO CAP SHOULD BE 75MM.
27. PILE CAP AND PLINTH BEAM SHOULD BE CASTED MONOLITHICAL.
PILE VERTICAL
28. TOP OF THE PILE SHALL BE CHIPPED OFF FOR 300 MM LENGTH AFTER PILE CONCRETING
STEEL

D/2+150 D/2+150
29. INTEGRITY TEST ON PILE SHALL BE CARRIED OUT AS PER GOV. OF GUJARAT CIRCULAR No. ASR/102028 / 108/C DATED COLUMN
06-04-2018.

2 X PILE
1 PILE (D) 1

DIA.
30. COLUMN VERTICAL STEEL SHALL BE ALLOWED ONLY LAPS, STRICKLY PROHIBITED FOR WELDING OR COUPLER. PILE (D)
8T@100c/c
D

75
PILE PILE
500
D PILE CAP PLAN
PILE CAP
SECTION :1 - 1
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL GENERAL DETAILS FOR FOOTING
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-01 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
SCHEDULE OF COLUMN & FOOTING (Z-3)
2300
2300 2300 C1 C5 C2 C3 C4 C9 C6 C10 C11 C12 C13
C14 C15
C7 C8
1 2 3 4 5
3800

B B
2300

2300

C1 C5
3800

3800

C4
C2 C3 B B
2 SET+3 LINK
A 2300 PC1 2300 PC1
700
A
M20
PC2 350 X 700
4-16 T+10-12 T
PC2 PC2 BBB BBB BB B
A
A A
A A
A
BBB BBB BB B
2 SET+2 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+2 LINK
700 700 700 700 700
2300 2300 2300 M20 M20 M20 M20 M20
350 X 700 350 X 700 350 X 700 350 X 700 350 X 650
12-20 T 10-16 T+4-12 T 8-20 T+6-16 T 6-20 T+8-16 T 6-16 T+6-12 T
BBB BB B
A
A A
A A
A
C7 C8 C9 BBB BB B
3800

3800

3800

2 SET+2 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+2 LINK
2300

2300

C6 C10 700 700 700 700 700


M20 M20 M20 M20 M20
350 X 700 350 X 700 350 X 700 350 X 700 350 X 650
12-20 T 14-16 T 8-20 T+6-16 T 6-20 T+8-16 T 6-16 T+6-12 T
BBB B
2300 PC1 2300 PC1
A A
A A A A
A A A A
PC2 PC2 PC2 A A
BBB B
B PC3 PC3 PC3 PC3 PC3 2 SET+2 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+2 LINK B
1266

1266

1266

1266

1266
700 700 700 700 700
M20 M20 M20 M20 M20
C11 C12 C13 C14 C15 350 X 700 350 X 700 350 X 700 350 X 700 350 X 650
12-20 T 8-20 T+6-16 T 8-20 T+6-16 T 6-20 T+8-16 T 2-20 T+10-16 T
833

833

833

833

833
BBB B
`X-1'
A A
1962 1962 1962 1962 1962 A A A A
A A A A
A A
BBB B
2 SET+2 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+3 LINK 2 SET+2 LINK
FOUNDATION LAY-OUT 700
M25
700
M25
700
M25
700
M25
700
M25
350 X 700 350 X 700 350 X 700 350 X 700 350 X 650
12-20 T 8-20 T+6-16 T 8-20 T+6-16 T 6-20 T+8-16 T 2-20 T+10-16 T
8T@75c/c 8T@75c/c 8T@75c/c 8T@75c/c 8T@75c/c
8T@150c/c 8T@150c/c 8T@150c/c 8T@150c/c 8T@150c/c
SCHEDULE OF PILE
PC1 PC2 PC3
2300 x 2300 2300 x 3800 AS PER PLAN
2600 x 2600 2600 x 4100 AS PER PLAN
C C
750 750 750
M25 M25 M25
PC1 PC2 PC3
4 6 3
NOTE : 10000 10000 10000
01. FOUNDATION ARE DESIGNED FOR THE S.B.C. OF 500 DIA. PILE IS 500 500 500
31.5 TON @ DEPTH 10.00 mt. BASED ON SOIL INVESTIGATION
M25 M25 M25
REPORT OF SUBMITTED BY
AGENCY NAME:- GEO TEST HOUSE 12-20 T 12-20 T 12-20 T
PROJECT NO :- BRD/GIR/4786/158002/1 8T@75c/c 8T@75c/c 8T@75c/c
RECEIVED BY THIS OFFICE Dt. 05-04-2025.
02. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE. 8T@150c/c 8T@150c/c 8T@150c/c
03. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE 12T@125c/c 12T@100c/c 12T@100c/c
REFER THIS PROJECT DWG No. - S-01.
16T@125c/c 16T@100c/c 16T@100c/c
04. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
05. CLEAR COVER FOR ALL R.C. WORKS TO BE AS FOLLOWS. #
FOOTING & RAFT 50 MM. # COLUMN BELOW GROUND 40 MM. #
COLUMN ABOVE GROUND 40 MM. TO RINGS. # BEAMS BOTTOM
25 MM. # BEAMS TOP & SIDES 25 MM. # SLABS & CHHAJJA 20 MM.
D # PEDESTAL 40 MM. # R.C. WALLS 20 MM. GOOD FOR CONSTRUCTION SEISMIC ZONE : III D
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL FOUNDATION LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-02 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6

GOOD FOR CONSTRUCTION


SEISMIC ZONE : III
4-8 T 3-12 T
6-8 T TOP STEEL TOP STEEL
4,6 3,5
2 1
8T@150c/c 8T@150c/c
A 10
2-16 T + 1-12 T A
9 11 8T@150c/c
12
13 SECTION -AA SECTION -BB ALL
DN 14
15
PB5 (230X570)
16 3-12 T 3-12 T 2-16 T
17
18
19
UP 20 BEAM 3-20 T 3-20 T
4,6 3,5
2 1
3-12 T 2-20 T+1-16 T
8T@100c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
ALL ALL 12 No. REST 12 No.
PB1 (230X570) PBR1(230X570) PB4 (230X570)
NOTE :
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
A A A A 02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
B
REFER THIS PROJECT DWG No. - S-01.
03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
B M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE. B
B
2-8 T PLINTH LVL.
PLINTH BEAM LAY-OUT
8T@200c/c
2-16 T 2-16 T CP
3-8 T
3-20 T 3-20 T 3-20 T 3-20 T 3-20 T
PB
2-16 T+1-20 T 2-16 T+1-20 T
10T@100c/c 10T@140c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c P.C.C(1:4:8)
15 No. REST 15 No. 15 No. REST 15 No. 15 No. REST 15 No.
PB2 (230X570) PB3a (230X570) PB3b TYPICAL PLINTH
2-16 T
2-16 T+1-20 T 2-16 T+1-20 T 2-16 T+1-20 T 2-16 T+1-20 T 2-16 T+1-20 T
C C
2-12 T
3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
PB6a (230X570) PB6b PB6c PB6d (230X570)
2-16 T
3-16 T 3-16 T 3-16 T 2-16 T+1-20 T 3-16 T
3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
D D
PB7a (230X570) PB7b PB7c PB7d (230X570)
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL PLINTH BEAM LAYOUT& DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-03 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
2-16 T 2-16 T
3-16 T 2-16 T+1-20 T 2-16 T+1-20 T 3-16 T 3-20 T 3-20 T
2-12 T 2-12 T
3-16 T 2-16 T+1-20 T
A 10T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c A
ALL 18 No. REST 18 No. ALL 18 No. REST 18 No. ALL
PB8a (230X570) PB8b PB9a (230X570) PB9b PB9c (350X570)
2-16 T
2-16 T+1-20 T 3-20 T 3-20 T
2-12 T
2-16 T+1-20 T
8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
ALL 18 No. REST 18 No.
PB10a (230X570) PB10b
MASONARY WALL
B 12T@90 c/c B
SLAB TOP STEEL LANDING LEVEL
2-20 T LEVEL
LB1
8T@115c/c
3-20 T 3-20 T 6-8T RING
BOTTOM STEEL
2-25 T+1-20 T 12T@90 c/c
8T@100c/c
ALL
LB1 (300X570) 12T@90 c/c
MASONARY WALL
SLAB 8T@200 c/c
MASONARY WALL LEVEL 12T@90 c/c 12T@90 c/c SLAB
LANDING LEVEL 12T@90 c/c LEVEL
TOP STEEL LANDING LEVEL 8T@200 c/c
C 8T@115c/c C
8T@115c/c 6-8T LB1 FLIGHT - 3,5
LB1
6-8T RING 12T@90 c/c
BOTTOM STEEL FLIGHT - 4,6 12T@90 c/c
12T@90 c/c
MASONARY WALL
8T@200 c/c
LANDING LEVEL 8T@200 c/c NOTE : 12T@90 c/c PLINTH
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE. 12T@90 c/c LEVEL
8T@115c/c
02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE FLIGHT - 1
REFER THIS PROJECT DWG No. - S-01.
LB1 8T@200 c/c
6-8T 12T@90 c/c 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. & F.GR. LVL.
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
FLIGHT - 2
D GOOD FOR CONSTRUCTION SEISMIC ZONE : III PLINTH BEAM
D
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL PLINTH BEAM LAYOUT& DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-03.A R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
C B C C B C B C 3-12 T TOP STEEL TOP STEEL

120

120
4 115 THK. BRICK

DEPTH

DEPTH
115 THK. BRICK
C B C C B 4 C B C 4-8T MASONARY 6-8T MASONARY
1 BEAM RING
1-10 T

120

120
1-10 T BEAM RING
S1 S1
230 420 230 470

GOOD FOR CONSTRUCTION SEISMIC ZONE : III


3 3-16 T
10
9 11
S1 8T@150c/c BOTTOM STEEL BOTTOM STEEL
A 12
13
ALL SECTION - AA SECTION - BB A
DN 14
15 2 B5 (230X570)
BEAM RING
LIGHT WEIGHT MATERIAL
16 NO. RENIFORCEMENT
17
18 1 10T@150c/c WITH ALT BENT UP
19

DEPTH
UP 20 3-12 T 2 10T@300c/c EXTRA TOP STEEL
S1 S1 S1 BEAM RING
8T@200 c/c 3 8T@175c/c WITH ALT BENT UP
S4

120
BEAM 4 8T@350c/c EXTRA TOP STEEL
1-8 T 5 8T@200c/c DISTRIBUTION STEEL
2 2 230 240/140 230
SECTION - CC 6 8T@150c/c WITH ALT BENT UP
S2
S3 7 10T@300c/c EXTRA TOP STEEL
1 3 S2 S2 8T@100c/c 3-12 T
5 B B ALL
8T@150c/c
3 BR1 (230X570)
A A 3-12 T
NOTE :
SB1(230X120) 01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
A A 02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
B GROUND FLOOR SLAB & BEAM LAY-OUT REFER THIS PROJECT DWG No. - S-01.
B
ALL SLAB ARE 120 THK. UNLESS OTHERWISE SPECIFIED
DIST. STEEL 8T@200 c/c 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
3-12 T 2-16 T 2-16 T
2-20 T+1-25 T 2-20 T+1-25 T 3-20 T 2-20 T+1-25 T 3-20 T
3-12 T 2-20 T+1-16 T 2-20 T+1-16 T
8T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c
ALL 15 No. REST 15 No. 15 No. REST 15 No. 15 No. REST 15 No.
B1 (230X570) B2 (230X570) B3a (230X570) B3b
3-12 T 3-12 T
3-16 T
C C
2-20 T 2-12 T 2-12 T
3-20 T 3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
B4 (230X570) B4a (230X570) B4b
2-16 T
3-20 T 3-20 T 3-20 T 3-20 T 3-20 T
2-16 T+1-20 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
15 No. REST 15 No. 12 No. REST 12 No. 15 No. REST 15 No. 15 No. REST 15 No.
B6a (230X570) B6b B6c B6d (230X570)
D D
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL GROUND FLOOR SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR
FOREXECUTION
EXECUTIONSSA-GIR
SSA - RAJKOT
SOMNATH HAP
HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-04 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
2-16 T

GOOD FOR CONSTRUCTION SEISMIC ZONE : III


2-20 T+1-16 T 2-20 T+1-16 T 2-20 T+1-16 T 2-20 T+1-16 T 2-20 T+1-16 T
3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
A 12 No.
A
REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
B7a (230X570) B7b B7c B7d (230X570)
2-16 T 2-20 T
3-20 T 2-25 T+1-20 T 2-25 T+1-20 T 3-16 T 2-25 T+1-20 T 2-25 T+1-20 T
2-12 T 2-12 T
3-20 T 2-20 T+1-25 T
10T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 8T@100c/c
ALL 18 No. REST 18 No. ALL 18 No. REST 18 No. ALL
B8a (230X570) B8b B9a (230X570) B9b B9c (350X570)
2-20 T
B 2-20 T+1-12 T 3-25 T+1-20 T 3-25 T+1-20 T B
2-20 T
2-25 T+1-20 T
8T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c
ALL 18 No. REST 18 No.
B10a (300X570) B10b
C C
NOTE :
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
REFER THIS PROJECT DWG No. - S-01.
D 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
D
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL GROUND FLOOR SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-04.A R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
C B C C B C B C 3-12 T TOP STEEL TOP STEEL

120

120
4 115 THK. BRICK

DEPTH

DEPTH
115 THK. BRICK
C B C C B 4 C B C 4-8T MASONARY 6-8T MASONARY
1 BEAM RING
1-10 T

120

120
1-10 T BEAM RING
S1 S1
230 420 230 470

GOOD FOR CONSTRUCTION SEISMIC ZONE : III


3 3-16 T
10
9 11
S1 8T@150c/c BOTTOM STEEL BOTTOM STEEL
A 12
13
ALL SECTION - AA SECTION - BB A
DN 14
15 2 B5 (230X570)
BEAM RING
LIGHT WEIGHT MATERIAL
16 NO. RENIFORCEMENT
17
18 1 10T@150c/c WITH ALT BENT UP
19

DEPTH
UP 20 3-12 T 2 10T@300c/c EXTRA TOP STEEL
S1 S1 S1 BEAM RING
8T@200 c/c 3 8T@175c/c WITH ALT BENT UP
S4

120
BEAM 4 8T@350c/c EXTRA TOP STEEL
1-8 T 5 8T@200c/c DISTRIBUTION STEEL
2 2 230 240/140 230
SECTION - CC 6 8T@150c/c WITH ALT BENT UP
S2
S3 7 10T@300c/c EXTRA TOP STEEL
1 3 S2 S2 8T@100c/c 3-12 T
5 B B ALL
8T@150c/c
3 BR1 (230X570)
A A 3-12 T
NOTE :
SB1(230X120) 01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
B A FIRST FLOOR SLAB & BEAM LAY-OUT A REFER THIS PROJECT DWG No. - S-01. B
ALL SLAB ARE 120 THK. UNLESS OTHERWISE SPECIFIED 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
DIST. STEEL 8T@200 c/c M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
3-12 T 2-16 T 2-16 T
2-20 T+1-25 T 2-20 T+1-25 T 3-20 T 2-20 T+1-25 T 3-20 T
3-12 T 2-20 T+1-16 T 2-20 T+1-16 T
8T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c
ALL 15 No. REST 15 No. 15 No. REST 15 No. 15 No. REST 15 No.
B1 (230X570) B2 (230X570) B3a (230X570) B3b
3-12 T 3-12 T
3-16 T
C C
2-20 T 2-12 T 2-12 T
3-20 T 3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
B4 (230X570) B4a (230X570) B4b
2-16 T
3-20 T 3-20 T 3-20 T 3-20 T 3-20 T
2-16 T+1-20 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
15 No. REST 15 No. 12 No. REST 12 No. 15 No. REST 15 No. 15 No. REST 15 No.
B6a (230X570) B6b B6c B6d (230X570)
D D
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL FIRST FLOOR SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-05 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
2-16 T

GOOD FOR CONSTRUCTION SEISMIC ZONE : III


2-20 T+1-16 T 2-20 T+1-16 T 2-20 T+1-16 T 2-20 T+1-16 T 2-20 T+1-16 T
3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
A 12 No.
A
REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
B7a (230X570) B7b B7c B7d (230X570)
2-16 T 2-20 T
3-20 T 2-25 T+1-20 T 2-25 T+1-20 T 3-16 T 2-25 T+1-20 T 2-25 T+1-20 T
2-12 T 2-12 T
3-20 T 2-20 T+1-25 T
10T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 10T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 8T@100c/c
ALL 18 No. REST 18 No. ALL 18 No. REST 18 No. ALL
B8a (230X570) B8b B9a (230X570) B9b B9c (350X570)
2-20 T
B 2-20 T+1-12 T 3-25 T+1-20 T 3-25 T+1-20 T B
2-20 T
2-25 T+1-20 T
8T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c
ALL 18 No. REST 18 No.
B10a (300X570) B10b
C C
NOTE :
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
REFER THIS PROJECT DWG No. - S-01.
D 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
D
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL FIRST FLOOR SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-05.A R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
TOP STEEL TOP STEEL
B B B 3-12 T
120

120
115 THK. BRICK 8T@150c/c
DEPTH

DEPTH
4 115 THK. BRICK
4-8T MASONARY 6-8T MASONARY 3-12 T
B B 4 B
BEAM RING
1 1-10 T SB1(230X120)
120

120
1-10 T BEAM RING
S1 S1 230 420 230 470

GOOD FOR CONSTRUCTION SEISMIC ZONE : III


10
3 BOTTOM STEEL BOTTOM STEEL
S1
A 9 11
12
SECTION - AA SECTION - BB A
13
DN 14
RENIFORCEMENT
15 2 NO. 3-12 T
16
17 1 10T@150c/c WITH ALT BENT UP
18
19 2 10T@300c/c EXTRA TOP STEEL
UP 20
S1 S1 S1
3 8T@175c/c WITH ALT BENT UP 2-20 T
S4 4 8T@350c/c EXTRA TOP STEEL
5 8T@200c/c DISTRIBUTION STEEL 3-20 T
2 2 8T@100c/c 8T@140c/c 8T@100c/c
6 8T@150c/c WITH ALT BENT UP
12 No. REST 12 No.
7 10T@300c/c EXTRA TOP STEEL
S2
S3 B3 (230X570)
1 3 S2 S2
5 A A
3
A A
NOTE :
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
B 02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE B
A A REFER THIS PROJECT DWG No. - S-01.
TERRACE FLOOR SLAB & BEAM LAY-OUT 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
ALL SLAB ARE 120 THK. UNLESS OTHERWISE SPECIFIED
DIST. STEEL 8T@200 c/c M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
COLUMN STOP THIS LVL
2-16 T 2-16 T 3-12 T
3-16 T 3-16 T 2-16 T+1-20 T 2-16 T+1-20 T 2-16 T+1-20 T
3-16 T 3-16 T 3-16 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@150c/c
15 No. REST 15 No. 15 No. REST 15 No. 15 No. REST 15 No. ALL
B1 (230X570) B2a (230X570) B2b B5 (230X570)
3-12 T
3-16 T 3-16 T 3-16 T 2-16 T+1-20 T 3-16 T
C C
2-16 T+1-12 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
15 No. REST 15 No. 12 No. REST 12 No. 15 No. REST 15 No. 15 No. REST 15 No.
B6a (230X570) B6b B6c B6d (230X570)
3-12 T
3-16 T 3-16 T 3-16 T 2-16 T+1-20 T 3-16 T
2-16 T+1-12 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c
12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No. 12 No. REST 12 No.
B7a B7b B7c B7d (230X570)
D (230X570) D
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL TERRACE FLOOR SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-06 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
3-12 T 2-16 T
3-16 T 1-16 T 3-20 T 3-20 T+1-16 T
2-12 T 2-12 T 2-12 T
3-16 T 2-16 T 2-16 T+1-20 T
A 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c 8T@100c/c 8T@100c/c 8T@140c/c 8T@100c/c A
12 No. REST 12 No. 12 No. REST 12 No. ALL 18 No. REST 18 No.
B4a (230X570) B4b B8a (230X570) B8b

GOOD FOR CONSTRUCTION SEISMIC ZONE : III


2-16 T 2-20 T
1-16 T 3-25 T 3-25 T 1-12 T 3-25 T 3-25 T
2-12 T 2-16 T
2-20 T 2-20 T+1-25 T 2-25 T 3-25 T
8T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c 8T@100c/c 8T@100c/c 10T@100c/c 10T@140c/c 10T@100c/c
ALL 18 No. REST 18 No. ALL ALL 18 No. REST 18 No.
B9a (230X570) B9b B9c (350X570) B10a (300X570) B10b
B B
C C
NOTE :
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
REFER THIS PROJECT DWG No. - S-01.
D 03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
D
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL TERRACE FLOOR SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-06.A R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6
1 2 3 4 5 6
A 3-12 T 2-12 T
2 A
A A
S1
1 3-12 T 3-12 T
8T@100c/c 8T@140c/c 8T@100c/c 8T@140c/c
12 No. REST 12 No. ALL
B1 (230X570) B2 (230X570)
2 TOP STEEL 3-12 T
S1
1 120
B 115 THK. BRICK B
6-8T
DEPTH

MASONARY
1
BEAM RING
1-10 T

120
3-12 T
230 8T@100c/c 8T@150c/c 8T@100c/c
AS PER ARCH.
470 12 No. REST 12 No.
BOTTOM STEEL
STAIR TOP SLAB & BEAM LAYOUT B1x (230X570)
ALL SLAB ARE 120 THK. UNLESS OTHERWISE SPECIFIED
SECTION - AA
DIST. STEEL 8T@200 c/c 3-12 T
COLUMN STOP THIS LVL
C C
3-16 T 3-16 T
NO. RENIFORCEMENT
1 8T@175c/c WITH ALT BENT UP
2 8T@350c/c EXTRA TOP STEEL
2-16 T+1-12 T
8T@100c/c 8T@140c/c 8T@100c/c
12 No. REST 12 No. NOTE :
01. ALL DIMENSION ARE IN MM UNLESS SPECIFIED OTHERWISE.
B3 (230X570) 02. FOR GENERAL NOTES, TYPICAL STRUCTURAL DETAILS, PLEASE
REFER THIS PROJECT DWG No. - S-01.
03. MIXES FOR ALL R.C.C. WORK SHALL BE M25 BELOW GR. LVL. &
M20 ABOVE GR. LVL. UNLESS SPECIFIED OTHERWISE.
D D
GOOD FOR CONSTRUCTION SEISMIC ZONE : III
The drawings and the design calculation of the building shall PROJECT: TITLE : SIGN & STAMP
AKSHAR CORPORATION CLIENT be the property of AKSHAR CORPORATION, AHMEDABAD. CAT :-ASPER SITE LAYOUT-SITE SPECIFIC/REVISE SOIL STAIR TOP SLAB & BEAM LAYOUT & DETAILS
STRUCTURAL DESIGNERS The drawings and designs so approved shall not be used in AT: - CHIKHLI PRA SHALA
any way without the prior permission of the akshar corporation,
TA : - UNA, DIST:- GIR SOMNATH
ahmedabad. In case there is any discrepancy found in the
drawing, it shall be brought to the notice of the consultant well SCALE:- 1 : 100 DRG.NO REVISION
24, THIRD FLOOR, SHUKAN MALL, before execution of the work. All dimensions are to be read
R-0 04-03-25 EMAIL FOR EXECUTION SSA - G'NAGAR HAP
SHAHIBAUG, AHMEDABAD-04 DATE:- 03-03-2025 R-0 04-03-25 04 FOR EXECUTION SSA-GIR SOMNATH HAP
and not to be measured. All dimensions are in millimeter. The
PHONE: - 9426002014,9979851794
S.S.A. GANDHINAGAR, GUJARAT structural consultant is not responsible for the quality control DEALT:- RUCHI S-07 R-00 REV.No. DATE Nos. PARTICULAR CHECKED
STRUCTURAL CONSULTANT
E-Mail : [email protected], and supervision of the work being executed on site CHECK:- HIMANSHU PATEL R E V I S I O N
1 2 3 4 5 6