0% found this document useful (0 votes)
21 views2 pages

Ups LGR 0239 GB Aa

The document provides detailed specifications for the Keor MP 60 kVA three-phase UPS system, highlighting its characteristics, technical data, user interface, and compliance with standards. It features advanced IGBT inverter technology, supports various battery types, and offers multiple communication interfaces. The UPS is designed for critical applications requiring power continuity in IT, residential, commercial, and tertiary sectors.

Uploaded by

bmks.med
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views2 pages

Ups LGR 0239 GB Aa

The document provides detailed specifications for the Keor MP 60 kVA three-phase UPS system, highlighting its characteristics, technical data, user interface, and compliance with standards. It features advanced IGBT inverter technology, supports various battery types, and offers multiple communication interfaces. The UPS is designed for critical applications requiring power continuity in IT, residential, commercial, and tertiary sectors.

Uploaded by

bmks.med
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

128, av.

du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex


Tél. : 33(0)5 55 06 87 87 - Fax : 33(0)5 55 06 88 88
www.legrand.com

Keor MP 60 kVA Cat.No : 3 112 35


Three-phase UPS system

CONTENT Page

1. Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. Standards and regulations . . . . . . . . . . . . . . . 3
5. Other informations . . . . . . . . . . . . . . . . . . . . . . 3

1. CHARACTERISTICS Range of frequency for


50/ 60 ± 10%
Keor MP is three-phase online double conversion technology UPS system. bypass synchronizing
The Keor MP UPS is based on a Three Level IGBT inverter technology in a Output phases 3Ph + N + PE
compact design, compatible with Li-ion and VRLA battery technology.
Output voltage regulation For static balanced load < 1% ,
unbalanced load < 3%
1.1 Specific application
Dynamic load < 5% & recovery time
Suitable for generic critical application wich needs power continuity.
as per IEC 62040-3
Ideal solution for IT, Residential, Commercial and Tertiary applications.
Voltage harmonics < 2% for linear load & < 4% for non
2. TECHNICAL DATA linear load

2.1 General characteristics Range of frequency for 50/60 ± 10%


bypass synchronizing (Hz)
Nominal power [kVA] 60
Voltage range for static Maximum voltage
Active power [kW] 60 bypass mode 220V: + 25% (optional + 10%, + 15%,
Classification True online double conversion, + 20%)
VFI-SS-111 230V: + 20% (optional + 10%, + 15%)
240V: + 15% (optional + 10%)
Possible configuration 3Ph-3Ph Minimum voltage
Topology DSP based IGBT rectifier with - 45% (optional - 10%, - 15%, - 20%, -
advanced PF correction 30%)
Permitted overload on mains ≤ 110% for 30 mins,
2.2 Input (PF=1)* ≤ 125% for 10 mins,
≤ 150% for 1 min,
Nominal voltage [V] L-L 380, 400, 415 Vac; > 150% for 1.2 secs - the inverter
L-N 220, 230, 240 Vac shuts down
Voltage range[%] At 400 Vac, (-40 %, + 20%) for 40% Overall efficiency in double Up to 95% at 100% load
load; (-22.5%, + 20%) for 100% load conversion mode in linear Up to 95% at 75% load
Frequency [Hz] 50/ 60 with tolerance from 40 to 70 Hz load Up to 95.5% at 50% load
Up to 95% at 25% load
Input phases 3 phase + N + PE
Efficiency on eco mode up to 99%
THDIin [%]
@100% load <3% Crest factor 3:1
Input Power Factor >0.99
2.4 Battery
Power walk-In 1-20 secs (selectable)
Type VRLA and Li-ion
Rectifier hold off 1-200 secs
Nominal battery voltage 432 Vdc ~ 600
[Vdc]
2.3 Output
Nominal Li-ion battery
Topology DSP based PWM 3 level IGBT inverter 512 ~ 614
voltage [Vdc]
Output power factor 1 Battery charging mode 3 stage advanced cycle:
Output load PF handling 0.7 lag to 0.7 lead Boost 14.5V Batt; Maintenance 13.75V
Batt, Equalizing charging
Nominal output voltage with Vac = 380/ 400/ 415V ± 1%
adjustment range ± 0.5 (others selectable) DC ripple < 1%
Output frequency (Hz) 50/60 (± 0.1Hz) in-sync with input Charging current 20 A
frequency

Technical sheet: UPS_LGR_0239_GB_AA Updated: 26/03/2025 Created: 26/03/2025

1/2
Keor MP 60 kVA Cat.No : 3 112 35
Three-phase UPS system

2.5 Communication Interface 2.8 Block Diagram

Cabinet displays Synoptic LED bar Maintenance


MCCB

Input/Output wirings 3Ph + N + PE from the bottom and


rear STSB
MCCB

Functioning mode On-line/ parallel mode/ frequency EMI EMI

converter/ eco mode/ eco parallel Main


Input
MCCB
PFC
rectifier
Busbar Inverter
Output
MCCB
Output

mode(PECO)
Discharge Charge
Maintenance by-pass EMI

MCCB - Included (Standard)


switch Battery Charger

Static by-pass Yes


3. COMMUNICATION & CONNECTIVITY
Cold start Yes 1. Serial interface RS485 (ModBus protocol RTU) (Inbuilt)
Paralleling Max 6 cabinets 2. SNMP (Optional)
3. Parallel interface kit (5 meters)(Optional)
USB port Yes 4. LBS interface kit
MODBUS/ RS485/RS232 Yes 5. Isolation transformer (Optional)
6. Dry contact (Optional)
RJ45 LAN/WAN Yes 7. Temperature sensor (Optional)
Potential free contact Yes 8. Backfeed protection (Optional)
9. REPO (Optional)
SNMP Yes (optional) 10. RAM panel (Optional)
Load bus sync kit Yes (optional) 11. Isolation transformer (Optional)

Safety and Protection Overload, Short circuit, Back 4. SOFTWARE ENABLED FUNCTIONS
feed port available (external 1. Generator compatible
2. Rectifiers sequential star
connection optional), Over & low
3. Softstart rectifier
voltage, Fast acting fuses 4. Cold start
Available neutral status TN-C, TN-S 5. VFI / VFD (Eco) operating mode management
6. Frequency converter
Event logs Upto 1000 first in/out 7. EPO
8. Common battery bank with 2 UPS
2.6 Enviromental specs
Operating temperature [°C] 0 - 40 3. STANDARDS AND REGULATIONS
Operating humidity [Rh] 20% - 95% non-condensing
The UPS Keor MP has the CE Mark accordingly with the EU Directives
Storage temparature [°C] 20 - 55 2006 95 2004 108 and it comply with following standards
Maximum noise audible at - EN 62040-1: General rules for electric safety
58 - EN 62040-2: Electromagnetic compatibility and immunity (EMC)
1m [dBA]
- EN 62040-3: Performances and testing rules
- EN 62040-4: Environmental
2.7 Mechanical characteristics
- ROHS / REACH
Overall net weight [Kg] 110
Frame dimensions 250 x 850 x 1000 4. OTHER INFORMATIONS
[W x D x H] [mm]
Protection index IP20
Color shade RAL 9005 + 9003

Installation and maintenance manual: mounting informations and


maintenance guide available on e-catalogue

For further technical information, please contact Legrand technical


support.
Unless otherwise indicated, data reported in this document refers
exclusively to test conditions according to product standards.
For different conditions of use of the product, inside electrical
equipment or in any different installation context, refer to the
regulatory requirements of the equipment, local regulations and design
specifications of the system.

Note: Specifications are subject to change with continuous development


* < 30 degrees celsius for overload </= 125% & </= 150%

Technical sheet : UPS_LGR_0239_GB_AA Updated: 26/03/2025 Created: 26/03/2025

2 /2

You might also like