ELECTRICAL

Document No. DATASHEET FOR POWER Rev 1


PPB-PGS-00-ELE-DS-001-A4 TRANSFORMER Page 1 of 14

COMPANY : PT PERTAMINA PATRA NIAGA

CONTRACTOR : PT PGAS SOLUTION

PROJECT NAME : PIPANISASI PENGAPON BOYOLALI

LOCATION : PENGAPON - BOYOLALI

CONTRACT NO. : SP-009/PNA000000/2023-S0

PO NO. : 3950268999

1 13/10/2023 Re-Issued For Approval ANW/LUT SLM RIZ

0 14/09/2023 Issued For Approval ANW SLM RIZ

PREPARED CHECKED APPROVED CHECKED APPROVED


REV DATE STATUS
PT PERTAMINA
PT PGAS SOLUTION
PATRA NIAGA
PIPANISASI PENGAPON BOYOLALI

Document No. DATASHEET FOR POWER Rev 1


PPB-PGS-00-ELE-DS-001-A4 TRANSFORMER Page 2 of 14

REVISION SHEET

Rev. No. Date Page Description

0 14/09/2023 All Issued For Approval

1 09/10/2023 All Re-Issued For Approval


3&9 Impedance Voltage Minimal has been updated
Tag Number, Noise Level, and Secondary Neutral
3, 6, 9, 12
has been updated
4, 7, 10, 13 Special Test has been updated
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
PPB-PGS-00-ELE-DS-001-A4 3 OF 14

GENERAL DATA

1. Standard : Reffer to doc. PPB-PGS-00-ELE-SP-004-A4


2. Location : Outdoor/Shelter
3. Ambient Air temp : Min. 24ºC 33ºC Max
4. Humidity : Min. 49ºC 98ºC Max.
5. Altitude : 100 meter above Sea Level
6. Hazardous Area Classification : Non Hazardous Area
DATASHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
ENIVIROMENTAL CONDITION Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
A TRANSFORMER FOR MV DESIGN DATA
A.1 Design life Years 20
A.2 Applicable Codes and Standards IEC 60076
A.3 Tag No. TR-SMG-001 1
A.4 Service Power
A.5 No. of Units 1 Unit
A.6 Manufacture VTA
B GENERAL TECHNICAL DATA
B.1 Cooling System Oil Natural Air Natural
B.2 Oil Preservation System Hermetically Sealed With N2
B.3 Type of Protection Weather Proof and Min IP55
B.4 Noise Level 85 db at 1 meter from the edge of the skid 1
B.5 Grounding Shield Separator Yes/No No
C RATING
C.1 Type of Rating Continous
C.2 No. of Phase Phase 3 (Three)
C.3 kVA rating - ONAN (self cooled) kVA 2500
C.4 Primary Voltage (V) V 20000 ± 10 %
C.5 Secondary Voltage (V) V 3300 ± 10 %
C.6 Frequency (Hz) Hz 50 ± 5 %
D TAP CHANGER
D.1 Tap Changer Type/Location Off Circuit Tap Charger/at primary winding of power transformer
D.2 Rated kVA Tap (V) (-) 5%; (-)2.5%; 0; (+)2.5%; (+)5%
D.3 Reduced kVA Tap (V) N/A
D.4 Category of Voltage Variation IEC 60076 Table-2
D.5 Tactile Position Indicator Yes/No Yes
D.6 Positive Visual Yes/No Yes
E WINDINGS
E.1 Polarity (Add-additive / Sub-substractive) YnYn 6 (Vector Group)
E.2 Primary-Secondary Connection Y/Y
E.3 Winding Materials Copper
E.4 Number of Windings VTA
F INSULATION
F.1 Class Rating kV 20
F.2 Basic Impulse Level kV Refer to IEC 60076, 60726
F.3 Power Freq. Test Volt, kV rms kV 50
F.4 Insulation Oil Non-Toxic & Non-Inhibited Mineral Oil
F.5 Insulating material class Refer to IEC 60076, 60726
G IMPEDANCE
G.1 Impedance Voltage Minimal % 7 1
H TEMPERATUR RISE
H.1 Winding (by resis. Method) ˚C 65 ˚C (as per IEC 60076)
H.2 Oil (by thermomether) ˚C 60 ˚C (as per IEC 60076)
H.3 Heat Dissipation kW VTA
I SECONDARY NEUTRAL
I.1 Solid - solid grounding No
I.2 Resist - resistant grounding NER, 100A, 19 ohm, 10 seconds (Supplied by other Vendor)
1
I.3 Un - ungrounded No
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
PPB-PGS-00-ELE-DS-001-A4 4 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


J TERMINAL BOX (BUSHING CHAMBER)
J.1 Primary
J.2 Enclosure Side Mounted / IP 55 , Hinged Door
J.3 Bushing Connection Porcelain Air Terminal Chamber
J.4 Size Cable As per cable Schedule
J.5 Cable entry Bottom Entry, Removable gland plates
J.6 Cable Gland As per cable Schedule
J.7 Terminal Box Ingress Protection IP 55 to IEC 60529
J.8 Facility for MV cable screen earthing Yes/No Yes
J.9 Secondary
J.10 Enclosure Side Mounted / IP 55 , Hinged Door
J.11 Bushing Connection Busbar type suitable with 2 holes terminal lug
J.12 Cable entry Bottom Entry, Removable gland plates
J.13 Cable Gland As per cable Schedule
J.14 Number & type of cables As per cable Schedule
J.15 Conductor Size mm2 As per cable Schedule
J.16 Facility for cable screen earthing Yes/No Yes
J.17 Neutral CTs required Yes/No Yes
J.18 Rating VTA
J.19 Burden VTA
J.20 Accuracy Class Class 5P
J.21 Ingress Protection for Terminal Box IP55 to IEC 60529
K COLOUR
K.1 Colour Finishing Light Grey - RAL 7035
L ACCESSORIES (In Addition to Manufactur Standard Accessories)
L.1 Dial Thermometer (with alarm contactor) Required
L.2 Pressure Relay (with alarm contactor) Required
L.3 Forced Cooling-Fan N/A
L.4 Lightning Arrestor Manufacture Standard

Withstand Without Damage for two (2)


second during a (3 phase) simmetrical fault
L.5 kA 25
on the secondary - primary being supplied
by a system of S/C level (kA / MVA)

L.6 Anti Condensation Heater Yes/No Yes, Required


M ENCLOSURE
M.1 Enclosure Type Metallic
M.2 Protection IP 55
M.3 Material Sheet Steel, Painted
M.4 Floor Mounted with heavy duty rigid steel base Yes/No Yes
Max Heat Dissipation at Full (100%)
M.5 kW VTA
load / 50 % load
M.6 Type and No. of Lifting Points VTA
M.7 Spreader Beams or Frames Required Yes/No VTA
M.8 Type of Base Jacking Arrangement VTA
M.9 Earthing Lug Yes/No Yes, 2 Numbers, (Diagonal Opposite)
M.10 Transformer Enclosure Dimension (LXWXH) mm VTA
M.11 Transformer Dimension (LXWXH) mm VTA
M.12 Transportion Weight Kg VTA
N CONTROL PROTECTION SYSTEM
N.1 Voltage Control Circuit 230 V AC from UPS, 50 Hz
N.2 Over Temperature Yes, High-High
N.3 Over Pressure Yes, High-High Pressure for Trip
N.4 Oil Level Yes, Low Level Oil
O TESTS
O.1 Routine Test Yes
O.2 Type Test Certificate only is required
O.3 Special Test VTA 1
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
PPB-PGS-00-ELE-DS-001-A4 5 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


P TRANSFORMER ACCESSORIES
1 Oil Level gauge with related temperature markings
2 Top oil dial tipe thermometer
3 Pressure /Vacuum gauge & bleeder
4 Pressure relief device with auxiliary contacts
5 Two tank ground pads/terminals
6 Provision for lifting
7 Name plate
8 Sudden pressure relay with alarm provision, on sealed transformer
9 Neutral CT
10 Winding Temperature Indicator
11 Pad lockable drain valve
12 Skids or wheels
13 Thermometer pocket at point of tank top oil
14 Off load tap charger with range ± 5% in 2.5% steps complete with padlock facilities
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
PPB-PGS-00-ELE-DS-001-A4 6 OF 14

GENERAL DATA

1. Standard : Reffer to doc. PPB-PGS-00-ELE-SP-004-A4


2. Location : Outdoor/Shelter
3. Ambient Air temp : Min. 24ºC 33ºC Max
4. Humidity : Min. 49ºC 98ºC Max.
5. Altitude : 100 meter above Sea Level
6. Hazardous Area Classification : Non Hazardous Area
DATASHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
ENIVIROMENTAL CONDITION Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
A TRANSFORMER FOR LV DESIGN DATA
A.1 Design life Years 20
A.2 Applicable Codes and Standards IEC 60076
A.3 Tag No. TR-SMG-002 1
A.4 Service Power
A.5 No. of Units 1 Unit
A.6 Manufacture VTA
B GENERAL TECHNICAL DATA
B.1 Cooling System Oil Natural Air Natural
B.2 Oil Preservation System Hermetically Sealed With N2
B.3 Type of Protection Weather Proof and Min IP55
B.4 Noise Level 85 db at 1 meter from the edge of the skid 1
B.5 Grounding Shield Separator Yes/No No
C RATING
C.1 Type of Rating Continous
C.2 No. of Phase Phase 3 (Three)
C.3 kVA rating - ONAN (self cooled) kVA 400
C.4 Primary Voltage (V) V 3300 ± 10 %
C.5 Secondary Voltage (V) V 400 ± 10 %
C.6 Frequency (Hz) Hz 50 ± 5 %
D TAP CHANGER
D.1 Tap Changer Type/Location Off Circuit Tap Charger/at primary winding of power transformer
D.2 Rated kVA Tap (V) (-) 5%; (-)2.5%; 0; (+)2.5%; (+)5%
D.3 Reduced kVA Tap (V) N/A
D.4 Category of Voltage Variation IEC 60076 Table-2
D.5 Tactile Position Indicator Yes/No Yes
D.6 Positive Visual Yes/No Yes
E WINDINGS
E.1 Polarity (Add-additive / Sub-substractive) Dyn 11 (Vector Group)
E.2 Primary-Secondary Connection Δ/Y
E.3 Winding Materials Copper
E.4 Number of Windings VTA
F INSULATION
F.1 Class Rating kV 3.3
F.2 Basic Impulse Level kV Refer to IEC 60076, 60726
F.3 Power Freq. Test Volt, kV rms kV 50
F.4 Insulation Oil Non-Toxic & Non-Inhibited Mineral Oil
F.5 Insulating material class Refer to IEC 60076, 60726
G IMPEDANCE
G.1 Impedance Voltage Minimal % 4
H TEMPERATUR RISE
H.1 Winding (by resis. Method) ˚C 65 ˚C (as per IEC 60076)
H.2 Oil (by thermomether) ˚C 60 ˚C (as per IEC 60076)
H.3 Heat Dissipation kW VTA
I SECONDARY NEUTRAL
I.1 Solid - solid grounding Solidly
I.2 Resist - resistant grounding No
I.3 Un - ungrounded No 1
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
PPB-PGS-00-ELE-DS-001-A4 7 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


J TERMINAL BOX (BUSHING CHAMBER)
J.1 Primary
J.2 Enclosure Side Mounted / IP 55 , Hinged Door
J.3 Bushing Connection Porcelain Air Terminal Chamber
J.4 Size Cable As per cable Schedule
J.5 Cable entry Bottom Entry, Removable gland plates
J.6 Cable Gland As per cable Schedule
J.7 Terminal Box Ingress Protection IP 55 to IEC 60529
J.8 Facility for MV cable screen earthing Yes/No Yes
J.9 Secondary
J.10 Enclosure Side Mounted / IP 55 , Hinged Door
J.11 Bushing Connection Busbar type suitable with 2 holes terminal lug
J.12 Cable entry Bottom Entry, Removable gland plates
J.13 Cable Gland As per cable Schedule
J.14 Number & type of cables As per cable Schedule
J.15 Conductor Size mm2 As per cable Schedule
J.16 Facility for cable screen earthing Yes/No Yes
J.17 Neutral CTs required Yes/No Yes
J.18 Rating VTA
J.19 Burden VTA
J.20 Accuracy Class Class 5P
J.21 Ingress Protection for Terminal Box IP55 to IEC 60529
K COLOUR
K.1 Colour Finishing Light Grey - RAL 7035
L ACCESSORIES (In Addition to Manufactur Standard Accessories)
L.1 Dial Thermometer (with alarm contactor) Required
L.2 Pressure Relay (with alarm contactor) Required
L.3 Forced Cooling-Fan N/A
L.4 Lightning Arrestor Manufacture Standard

Withstand Without Damage for two (2)


second during a (3 phase) simmetrical fault
L.5 kA 25
on the secondary - primary being supplied
by a system of S/C level (kA / MVA)

L.6 Anti Condensation Heater Yes/No Yes, Required


M ENCLOSURE
M.1 Enclosure Type Metallic
M.2 Protection IP 55
M.3 Material Sheet Steel, Painted
M.4 Floor Mounted with heavy duty rigid steel base Yes/No Yes
Max Heat Dissipation at Full (100%)
M.5 kW VTA
load / 50 % load
M.6 Type and No. of Lifting Points VTA
M.7 Spreader Beams or Frames Required Yes/No VTA
M.8 Type of Base Jacking Arrangement VTA
M.9 Earthing Lug Yes/No Yes, 2 Numbers, (Diagonal Opposite)
M.10 Transformer Enclosure Dimension (LXWXH) mm VTA
M.11 Transformer Dimension (LXWXH) mm VTA
M.12 Transportion Weight Kg VTA
N CONTROL PROTECTION SYSTEM
N.1 Voltage Control Circuit 230 V AC from UPS, 50 Hz
N.2 Over Temperature Yes, High-High
N.3 Over Pressure Yes, High-High Pressure for Trip
N.4 Oil Level Yes, Low Level Oil
O TESTS
O.1 Routine Test Yes
O.2 Type Test Certificate only is required
O.3 Special Test VTA 1
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM PENGAPON)
PPB-PGS-00-ELE-DS-001-A4 8 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


P TRANSFORMER ACCESSORIES
1 Oil Level gauge with related temperature markings
2 Top oil dial tipe thermometer
3 Pressure /Vacuum gauge & bleeder
4 Pressure relief device with auxiliary contacts
5 Two tank ground pads/terminals
6 Provision for lifting
7 Name plate
8 Sudden pressure relay with alarm provision, on sealed transformer
9 Neutral CT
10 Winding Temperature Indicator
11 Pad lockable drain valve
12 Skids or wheels
13 Thermometer pocket at point of tank top oil
14 Off load tap charger with range ± 5% in 2.5% steps complete with padlock facilities
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
PPB-PGS-00-ELE-DS-001-A4 9 OF 14

GENERAL DATA

1. Standard : Reffer to doc. PPB-PGS-00-ELE-SP-004-A4


2. Location : Outdoor/Shelter
3. Ambient Air temp : Min. 24ºC 33ºC Max
4. Humidity : Min. 78ºC 89ºC Max.
5. Altitude : 100 meter above Sea Level
6. Hazardous Area Classification : Non Hazardous Area
DATASHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
ENIVIROMENTAL CONDITION Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
A TRANSFORMER FOR MV DESIGN DATA
A.1 Design life Years 20
A.2 Applicable Codes and Standards IEC 60076
A.3 Tag No. TR-BYL-001 1
A.4 Service Power
A.5 No. of Units 1 Unit
A.6 Manufacture VTA
B GENERAL TECHNICAL DATA
B.1 Cooling System Oil Natural Air Natural
B.2 Oil Preservation System Hermetically Sealed With N2
B.3 Type of Protection Weather Proof and Min IP55
B.4 Noise Level 85 db at 1 meter from the edge of the skid 1
B.5 Grounding Shield Separator Yes/No No
C RATING
C.1 Type of Rating Continous
C.2 No. of Phase Phase 3 (Three)
C.3 kVA rating - ONAN (self cooled) kVA 1250
C.4 Primary Voltage (V) V 20000 ± 10 %
C.5 Secondary Voltage (V) V 3300 ± 10 %
C.6 Frequency (Hz) Hz 50 ± 5 %
D TAP CHANGER
D.1 Tap Changer Type/Location Off Circuit Tap Charger/at primary winding of power transformer
D.2 Rated kVA Tap (V) (-) 5%; (-)2.5%; 0; (+)2.5%; (+)5%
D.3 Reduced kVA Tap (V) N/A
D.4 Category of Voltage Variation IEC 60076 Table-2
D.5 Tactile Position Indicator Yes/No Yes
D.6 Positive Visual Yes/No Yes
E WINDINGS
E.1 Polarity (Add-additive / Sub-substractive) YnYn 6 (Vector Group)
E.2 Primary-Secondary Connection Y/Y
E.3 Winding Materials Copper
E.4 Number of Windings VTA
F INSULATION
F.1 Class Rating kV 20
F.2 Basic Impulse Level kV Refer to IEC 60076, 60726
F.3 Power Freq. Test Volt, kV rms kV 50
F.4 Insulation Oil Non-Toxic & Non-Inhibited Mineral Oil
F.5 Insulating material class Refer to IEC 60076, 60726
G IMPEDANCE
G.1 Impedance Voltage Minimal % 5.5 1
H TEMPERATUR RISE
H.1 Winding (by resis. Method) ˚C 65 ˚C (as per IEC 60076)
H.2 Oil (by thermomether) ˚C 60 ˚C (as per IEC 60076)
H.3 Heat Dissipation kW VTA
I SECONDARY NEUTRAL
I.1 Solid - solid grounding No
I.2 Resist - resistant grounding NER, 100A, 19 ohm, 10 seconds (Supplied by other Vendor)
1
I.3 Un - ungrounded No
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
PPB-PGS-00-ELE-DS-001-A4 10 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


J TERMINAL BOX (BUSHING CHAMBER)
J.1 Primary
J.2 Enclosure Side Mounted / IP 55 , Hinged Door
J.3 Bushing Connection Porcelain Air Terminal Chamber
J.4 Size Cable As per cable Schedule
J.5 Cable entry Bottom Entry, Removable gland plates
J.6 Cable Gland As per cable Schedule
J.7 Terminal Box Ingress Protection IP 55 to IEC 60529
J.8 Facility for MV cable screen earthing Yes/No Yes
J.9 Secondary
J.10 Enclosure Side Mounted / IP 55 , Hinged Door
J.11 Bushing Connection Busbar type suitable with 2 holes terminal lug
J.12 Cable entry Bottom Entry, Removable gland plates
J.13 Cable Gland As per cable Schedule
J.14 Number & type of cables As per cable Schedule
J.15 Conductor Size mm2 As per cable Schedule
J.16 Facility for cable screen earthing Yes/No Yes
J.17 Neutral CTs required Yes/No Yes
J.18 Rating VTA
J.19 Burden VTA
J.20 Accuracy Class Class 5P
J.21 Ingress Protection for Terminal Box IP55 to IEC 60529
K COLOUR
K.1 Colour Finishing Light Grey - RAL 7035
L ACCESSORIES (In Addition to Manufactur Standard Accessories)
L.1 Dial Thermometer (with alarm contactor) Required
L.2 Pressure Relay (with alarm contactor) Required
L.3 Forced Cooling-Fan N/A
L.4 Lightning Arrestor Manufacture Standard

Withstand Without Damage for two (2)


second during a (3 phase) simmetrical fault
L.5 kA 25
on the secondary - primary being supplied
by a system of S/C level (kA / MVA)

L.6 Anti Condensation Heater Yes/No Yes, Required


M ENCLOSURE
M.1 Enclosure Type Metallic
M.2 Protection IP 55
M.3 Material Sheet Steel, Painted
M.4 Floor Mounted with heavy duty rigid steel base Yes/No Yes
Max Heat Dissipation at Full (100%)
M.5 kW VTA
load / 50 % load
M.6 Type and No. of Lifting Points VTA
M.7 Spreader Beams or Frames Required Yes/No VTA
M.8 Type of Base Jacking Arrangement VTA
M.9 Earthing Lug Yes/No Yes, 2 Numbers, (Diagonal Opposite)
M.10 Transformer Enclosure Dimension (LXWXH) mm VTA
M.11 Transformer Dimension (LXWXH) mm VTA
M.12 Transportion Weight Kg VTA
N CONTROL PROTECTION SYSTEM
N.1 Voltage Control Circuit 230 V AC from UPS, 50 Hz
N.2 Over Temperature Yes, High-High
N.3 Over Pressure Yes, High-High Pressure for Trip
N.4 Oil Level Yes, Low Level Oil
O TESTS
O.1 Routine Test Yes
O.2 Type Test Certificate only is required
O.3 Special Test VTA 1
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
PPB-PGS-00-ELE-DS-001-A4 11 OF 14
` Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
P TRANSFORMER ACCESSORIES
1 Oil Level gauge with related temperature markings
2 Top oil dial tipe thermometer
3 Pressure /Vacuum gauge & bleeder
4 Pressure relief device with auxiliary contacts
5 Two tank ground pads/terminals
6 Provision for lifting
7 Name plate
8 Sudden pressure relay with alarm provision, on sealed transformer
9 Neutral CT
10 Winding Temperature Indicator
11 Pad lockable drain valve
12 Skids or wheels
13 Thermometer pocket at point of tank top oil
14 Off load tap charger with range ± 5% in 2.5% steps complete with padlock facilities
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
PPB-PGS-00-ELE-DS-001-A4 12 OF 14

GENERAL DATA

1. Standard : Reffer to doc. PPB-PGS-00-ELE-SP-004-A4


2. Location : Outdoor/Shelter
3. Ambient Air temp : Min. 24ºC 33ºC Max
4. Humidity : Min. 78ºC 89ºC Max.
5. Altitude : 100 meter above Sea Level
6. Hazardous Area Classification : Non Hazardous Area
DATASHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
ENIVIROMENTAL CONDITION Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
A TRANSFORMER FOR LV DESIGN DATA
A.1 Design life Years 20
A.2 Applicable Codes and Standards IEC 60076
A.3 Tag No. TR-BYL-002 1
A.4 Service Power
A.5 No. of Units 1 Unit
A.6 Manufacture VTA
B GENERAL TECHNICAL DATA
B.1 Cooling System Oil Natural Air Natural
B.2 Oil Preservation System Hermetically Sealed With N2
B.3 Type of Protection Weather Proof and Min IP55
B.4 Noise Level 85 db at 1 meter from the edge of the skid 1
B.5 Grounding Shield Separator Yes/No No
C RATING
C.1 Type of Rating Continous
C.2 No. of Phase Phase 3 (Three)
C.3 kVA rating - ONAN (self cooled) kVA 400
C.4 Primary Voltage (V) V 3300 ± 10 %
C.5 Secondary Voltage (V) V 400 ± 10 %
C.6 Frequency (Hz) Hz 50 ± 5 %
D TAP CHANGER
D.1 Tap Changer Type/Location Off Circuit Tap Charger/at primary winding of power transformer
D.2 Rated kVA Tap (V) (-) 5%; (-)2.5%; 0; (+)2.5%; (+)5%
D.3 Reduced kVA Tap (V) N/A
D.4 Category of Voltage Variation IEC 60076 Table-2
D.5 Tactile Position Indicator Yes/No Yes
D.6 Positive Visual Yes/No Yes
E WINDINGS
E.1 Polarity (Add-additive / Sub-substractive) Dyn 11 (Vector Group)
E.2 Primary-Secondary Connection Δ/Y
E.3 Winding Materials Copper
E.4 Number of Windings VTA
F INSULATION
F.1 Class Rating kV 3.3
F.2 Basic Impulse Level kV Refer to IEC 60076, 60726
F.3 Power Freq. Test Volt, kV rms kV 50
F.4 Insulation Oil Non-Toxic & Non-Inhibited Mineral Oil
F.5 Insulating material class Refer to IEC 60076, 60726
G IMPEDANCE
G.1 Impedance Voltage Minimal % 4
H TEMPERATUR RISE
H.1 Winding (by resis. Method) ˚C 65 ˚C (as per IEC 60076)
H.2 Oil (by thermomether) ˚C 60 ˚C (as per IEC 60076)
H.3 Heat Dissipation kW VTA
I SECONDARY NEUTRAL
I.1 Solid - solid grounding Solidly
I.2 Resist - resistant grounding No
I.3 Un - ungrounded No 1
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
PPB-PGS-00-ELE-DS-001-A4 13 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


J TERMINAL BOX (BUSHING CHAMBER)
J.1 Primary
J.2 Enclosure Side Mounted / IP 55 , Hinged Door
J.3 Bushing Connection Porcelain Air Terminal Chamber
J.4 Size Cable As per cable Schedule
J.5 Cable entry Bottom Entry, Removable gland plates
J.6 Cable Gland As per cable Schedule
J.7 Terminal Box Ingress Protection IP 55 to IEC 60529
J.8 Facility for MV cable screen earthing Yes/No Yes
J.9 Secondary
J.10 Enclosure Side Mounted / IP 55 , Hinged Door
J.11 Bushing Connection Busbar type suitable with 2 holes terminal lug
J.12 Cable entry Bottom Entry, Removable gland plates
J.13 Cable Gland As per cable Schedule
J.14 Number & type of cables As per cable Schedule
J.15 Conductor Size mm2 As per cable Schedule
J.16 Facility for cable screen earthing Yes/No Yes
J.17 Neutral CTs required Yes/No Yes
J.18 Rating VTA
J.19 Burden VTA
J.20 Accuracy Class Class 5P
J.21 Ingress Protection for Terminal Box IP55 to IEC 60529
K COLOUR
K.1 Colour Finishing Light Grey - RAL 7035
L ACCESSORIES (In Addition to Manufactur Standard Accessories)
L.1 Dial Thermometer (with alarm contactor) Required
L.2 Pressure Relay (with alarm contactor) Required
L.3 Forced Cooling-Fan N/A
L.4 Lightning Arrestor Manufacture Standard

Withstand Without Damage for two (2)


second during a (3 phase) simmetrical fault
L.5 kA 25
on the secondary - primary being supplied
by a system of S/C level (kA / MVA)

L.6 Anti Condensation Heater Yes/No Yes, Required


M ENCLOSURE
M.1 Enclosure Type Metallic
M.2 Protection IP 55
M.3 Material Sheet Steel, Painted
M.4 Floor Mounted with heavy duty rigid steel base Yes/No Yes
Max Heat Dissipation at Full (100%)
M.5 kW VTA
load / 50 % load
M.6 Type and No. of Lifting Points VTA
M.7 Spreader Beams or Frames Required Yes/No VTA
M.8 Type of Base Jacking Arrangement VTA
M.9 Earthing Lug Yes/No Yes, 2 Numbers, (Diagonal Opposite)
M.10 Transformer Enclosure Dimension (LXWXH) mm VTA
M.11 Transformer Dimension (LXWXH) mm VTA
M.12 Transportion Weight Kg VTA
N CONTROL PROTECTION SYSTEM
N.1 Voltage Control Circuit 230 V AC from UPS, 50 Hz
N.2 Over Temperature Yes, High-High
N.3 Over Pressure Yes, High-High Pressure for Trip
N.4 Oil Level Yes, Low Level Oil
O TESTS
O.1 Routine Test Yes
O.2 Type Test Certificate only is required
1
O.3 Special Test VTA
PIPANISASI BOYOLALI - PENGAPON

Document No. 09-Oct-23


REV 1 DATA SHEET FOR POWER TRANSFORMER (AT TBBM BOYOLALI)
PPB-PGS-00-ELE-DS-001-A4 14 OF 14

Units PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


P TRANSFORMER ACCESSORIES
1 Oil Level gauge with related temperature markings
2 Top oil dial tipe thermometer
3 Pressure /Vacuum gauge & bleeder
4 Pressure relief device with auxiliary contacts
5 Two tank ground pads/terminals
6 Provision for lifting
7 Name plate
8 Sudden pressure relay with alarm provision, on sealed transformer
9 Neutral CT
10 Winding Temperature Indicator
11 Pad lockable drain valve
12 Skids or wheels
13 Thermometer pocket at point of tank top oil
14 Off load tap charger with range ± 5% in 2.5% steps complete with padlock facilities