Contingency Evaluation of a Peturbed Electric Network
J. N. Onah1
, T.C Madueme2
and V.C Ukwueze3
1,2,3
(Department Of Electrical Engineering,University Of Nigeria, Nsukka. Enugu State-Nigeria )
Abstract: A single line contingency analysis and generator(s) outages were carried out on a 330kV power
network using MATPOWER 4.1 embedded in MATLAB to carry out fast decoupled load flow studies in order to
identify the voltage violation at various buses, determine power losses at the transmission lines and to compute
the performance indices. The performance indices were further ranked in accordance with their severity indices.
Voltages less than 0.95pu were assumed to be low voltages and voltages greater than 1.05pu were also assumed
to be high voltages. It was also assumed that power losses greater than 5% are unacceptable. So a base case
comparative analysis of the load flow studies using three conventional methods showed that Gauss Seidel could
not converge in 0.93seconds and 1000 iterations, Newton Raphson converged in 0.15seconds and 6 iterations.
However, Fast Decoupled Load Flow (FDLF) converged in 0.01second and 28 iterations. Further, a single line
contingency analysis was also carried out on the transmission lines to investigate the performance indices of the
lines which were later ranked in accordance with their severity. The outcome of the simulations showed that at
a time when there was an outage of Kainji-GS, low voltages were found at Kano, Jos, Gombe, Kaduna,
Katampe, Oshogbo, Ajaokuta, New Haven, Aiyede, Ikeja-West, Onitsha, and Akangba buses. And there were
also power losses greater than 5% at Ikeja-West to Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to
Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to Gombe.
Key Words: Contingency Evaluation, FDLF, Performance Index, Power Loss, Line outage.
I. Introduction
A typical issue that confronts the integrated power project is outages on the transmission lines. Outages
diminish the productivity of the transmission system as they cause power disturbance and interference [1].
Moreover, the incessant and unprecedented vandalisation of the power equipment of the Nigerian power
systems resulting in cascaded outages of either the transmission line or the generator(s) in the recent time leaves
much to be desired. Consequently, contingency evaluation is necessary to showcase the areas that may lead to
total system voltage collapse and power losses. We are to carry out Fast Decoupled Load flow to determine the
voltage magnitudes, real and reactive powers that enabled us to calculate the performance indices of each of the
transmission lines and later rank them based on their severity. The study involves (N-1) secure otherwise called
single line contingency evaluation on the Nigerian 330kV transmission grid. Contingency analysis is the study
of the outage of elements such as transmission lines, transformers and generators, and investigation of the
resulting effects on line power flows and bus voltages of the remaining system [2].
II. Overview Of Contingency Evaluation
Nnonyelu et al [2] looked at the overloading at various transmission lines but could not bring to lime
light the voltage instability of the network as well as the effect of power losses in the transmission lines. It has
been established by Chan et al [3] that some transient-stability analysis concerns the transient behaviour of the
power system when moving from the pre-contingency to post-contingency operating point. However, owing to
computational economics, both direct methods [4, 5] and artificial-intelligence methods [6] have often been
proposed for use in online transient-stability assessment. However, it is not easy to apply these methods to larger
power systems involving complex models of plant and contingencies. But an application of a conventional load
flow method, gives a fast and a reliable result. However, Newton-Raphson method may be used to solve the
network equations but the method is computationally expensive because it needs to calculate the Jacobian at
each iteration of the algorithm. To improve the computational performance, a fast decoupled solution technique
is used to solve AC network equations iteratively [7]. It is a very fast and efficient method of obtaining power
flow problem solution. In this method both speed as well as sparsity is exploited. It is an extension of N-R
method formulated in polar coordinate with certain approximations which result into a fast algorithm for power
flow solution. This method exploits the property of the power system where the MW flow-voltage angle and
MVAR flow –Voltage magnitude is loosely coupled. In order words a small change in the magnitude of bus
voltage does not affect the real power flow at the bus and similarly a small change in phase angle of the bus
voltage has hardly any effect on reactive power flow. On the account of loose physical interaction between the
MW and the MVAR flows in a power system, the MW-δ and MVAR-V calculations can be decoupled resulting
Contingency Evaluation of a Peturbed Electric Network
DOI: 10.9790/1676-1052136142 www.iosrjournals.org 137 | Page
to a very simple, fast and reliable algorithm [7]. The fastness is on the account of the sparsity feature of the
admittance matrix that minimizes the computer memory requirement.
Most of the early iterative techniques were based on the Y-matrix of the G-S method [8]. It requires
minimum computer storage and needs only a small number of iterations for small networks. However, as the
size of the network is increased the number of iterations required increases dramatically for large systems. In
some cases the method does not provide solution at all [9]. Hence the slow convergence of G-S method and its
frequent failure to converge in ill- conditioned situations caused the development of Z-Matrix methods [10]. In
spite of the fact that these methods have considerably better converging characteristics, they also have the
demerit of needing a significantly large computer storage memory owing to the fact that Z-matrix is full,
contrary to the Y-Matrix which is sparse. Consequently, the shortcomings led to the development of N-R
algorithm to solve the simultaneous quadratic equations of power network .Contrary to the G-S algorithm, it
needs a large time per iteration but only a few iterations and is significantly independent of the network size.
However, in a realistic power system, there may be a large number of buses, for instance, 100 or more but each
bus is connected to only a small number usually two or more of the remaining buses. That is to say that of
a large power system is very sparse. This implies that it has a large number of zero elements, hence the sparcity
feature of minimizes the computer memory requirement as only non-zero terms are considered for storage
and results in faster computation. This idea leads to the development of Fast Decoupled power flow method. It
is a very fast, reliable and efficient method of obtaining power flow problem solution. It exploits speed and
accuracy in its methodology [5]. It has a compatible accuracy with that of N-R method. For the sake of brevity,
FDPF is an extension of N-R method formulated in polar coordinates with certain approximation which results
in algorithm for power flow solution.
It has been stated by Ekwue et al [11] that power Systems are generally nonlinear in nature and some
primary elements such as generator, branch outage etc contribute to the severity of the nonlinearity. So
considering the merits of FDPF aforementioned, we intend to look at the line flows, losses in the line, voltage
violation constraints and the performance indices which were found missing in the work of the various authors
reviewed above using the fast decoupled power flow algorithm.
III. The Network Under Study And Data
A single line diagram of the 330Kv Nigerian Power grid used in the study is shown in figure 1. It
comprises nine generator buses, eighteen load buses, twenty nine transmission lines of the Nigerian 330kV
transmission system.
Figure 1: One line diagram of Nigerian 330kV transmission grid [2]
Contingency Evaluation of a Peturbed Electric Network
DOI: 10.9790/1676-1052136142 www.iosrjournals.org 138 | Page
Tables 1, 2 and 3 show generator data, load data and line data respectively that are used for the simulations
Table 1: Generator Data
S/No. Bus name PG(MW) Rated
1 Kainji GS 756
2 Shiroro 413
3 Jebba GS 339
4 Sapele 70
5 Egbin 967
6 Afam 316
7 Delta GS 498
8 AES 235
9 Calabar 0
Source: [2 ]
Table 2: Load Data
Source: [2 ]
Contingency Evaluation of a Peturbed Electric Network
DOI: 10.9790/1676-1052136142 www.iosrjournals.org 139 | Page
Table 3: Line Data
Branch No. From To R(pu) X(pu) B(PU)
1 10 1 0.02676 0.06576 1.178
2 8 5 0.00300 0.02100 0.300
3 9 24 0.00216 0.00530 0.2570
4 1 15 0.00699 0.01718 0.308
5 3 15 0.00069 0.0017 0.033
6 15 17 0.01355 0.0333 0.597
7 17 21 0.02167 0.05324 0.521
8 17 20 0.00993 0.02439 0.437
9 20 21 0.01183 0.02906 0.521
10 21 25 0.00147 0.0361 0.065
11 21 5 0.00535 0.01315 0.257
12 5 26 0.00138 0.00339 0.257
13 21 22 0.02417 0.05939 1.162
14 22 4 0.00432 0.01061 0.208
15 4 27 0.00544 0.01336 0.239
16 7 27 0.00276 0.00679 0.239
17 7 22 0.00924 0.0227 0.239
18 18 22 0.0145 0.03564 0.208
19 17 22 0.02167 0.05324 0.954
20 2 15 0.02106 0.05176 0.927
21 2 16 0.01243 0.03055 0.308
22 14 2 0.00829 0.02036 0.364
23 11 14 0.01985 0.04879 0.874
24 12 14 0.01692 0.04158 0.927
25 12 13 0.002279 0.056 1.01
26 22 23 0.01183 0.02906 0.521
27 19 23 0.00829 0.02036 0.365
28 23 24 0.01191 0.02927 0.524
29 24 6 0.00216 0.0053 0.104
Source: [2 ]
IV. Methodology
The power flow study of the 330kV line was carried out comparatively, using various techniques such
as Gauss-Seidel, Newton Raphson and Fast Decoupled Load Flow. However, Gauss-Seidel could not converge
after 0.93seconds and 1000 iterations. Newton Raphson Converged in 0.15seconds and 6 Iterations but as a
matter of fact, Fast Decoupled load flow converged in 0.01seconds and 28 Iterations. Hence, because of its time
for numerical iteration and its capacity to hold as many data as possible, we utilized the FDLF for the research
work. To compute the performance indices, one of the lines was removed and the load flow analysis was carried
out in order to see the effect on the network. This was done by calculating the performance indices and ranking
them based on highest severity and thus, the operation continued until no severe contingencies are found. The
performance indices are given by
(1)
Moreover, the has got to do with the violation of the line active power flow and it is given by:
AiP = ∑i=1
N
(
Api
Api
max )2x
(2)
Where, = Active power performance index
=Active power flow in line i
Api
max
= Maximum active power flow in line i
N = The total number of transmission lines in the system.
x = the specific exponent where x is assumed to be unity.
And the maximum power flow in each line is given by (3)
Where, Vj = voltage at bus j got from FDLF solution, = Voltage at bus k obtained from FDLF solution. And
= impedance of the line connecting bus j and k.
However, (4)
Contingency Evaluation of a Peturbed Electric Network
DOI: 10.9790/1676-1052136142 www.iosrjournals.org 140 | Page
(5)
Figure 2 shows a bar chart that represents voltage drops at various branches when Kainji- generating
station was not committed. The result shows that the following buses are experiencing low voltages. They are:
Kano, Jos, Gombe, Kaduna, Katampe, Oshogbo, Ajaokuta, New Haven, Aiyede, Ikeja-West, Onitsha and
Akangba.
V. Simulation, Results And Discussion
The input data for the case to be simulated are specified in a set of data matrices packaged as the fields
of a Matlab struct, referred to as a “Matpower case" and denoted by the variable mpc. The struct is typically
defined in a case file called M-file whose return value is mpc struct. The solver was invoked by calling the
simulation function “runpf” and passing in a case file name as the first argument. So the FDLF was ran by
typing runpf(„case27‟) . By default, the results of the simulation are pretty to the screen, displaying a system
summary, bus data, branch data and, for the power flow, binding constraint information. The bus data comprises
the voltage, angle, total generation and load at each bus. The branch data shows the power flows and power
losses in each branch. Then the performance indices were computed using equations 1,2,3,4 and 5. The voltage
drops and the power losses are respectively shown in figure 2 and figure 3.
Figure 2: Voltage drop at the outage of kainji GS
At the outage of Kainji GS, the following branches experienced power losses. They are: Ikeja-West to
Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to
Gombe.
Figure 3: Power loss at the various branches when kainji- generating station was not committed.
Contingency Evaluation of a Peturbed Electric Network
DOI: 10.9790/1676-1052136142 www.iosrjournals.org 141 | Page
Power losses greater than 5% were observed at Ikeja-West to Egbin, Ikeja-West to Benin, Oshogbo to
Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to Gombe transmission lines.
VI. Computing The Performance Indices
The calculation of the performance indices was done using equation 1. The simulation results provided
the requisite parameters such as those given in equations 2, 3, 4 and 5.The results are tabulated in Table 4.
Table 4: Performance indices of the various lines of the network and the ranking based on the severity of the
lines
Branch No.
1 1-10 40.41 0.900 41.31 11
2 8-5 24.85 0.410 25.26 17
3 9-24 6.68 0.40 7.08 24
4 1-15 8.56 0.52 9.08 22
5 3-15 0.16 0.32 0.48 29
6 15-17 4.65 0.88 5.53 25
7 17-21 138.59 0.87 139.46 6
8 17-20 116.43 0.44 116.84 7
9 20-21 85.40 0.01 85.41 8
10 21-25 4.19 16.45 20.64 18
11 21-5 1.08 0.64 1.74 27
12 5-26 1.64 1.08 2.72 26
13 21-22 18.75 20.38 39.13 12
14 22-4 9.37 66.08 75.45 9
15 4-27 13.61 14.30 27.91 13
16 7-27 13.27 12.98 26.25 16
17 7-22 164.42 14.81 179.23 3
18 18-22 9.68 17.80 27.49 14
19 17-22 159.11 18.08 177.19 5
20 2-15 1.34 25.10 26.44 15
21 2-16 60.51 1.02 61.53 10
22 14-2 214 6.52 220.52 1
23 11-14 0.75 0.24 0.99 28
24 12-14 175..62 2.14 177.76 4
25 12-13 9.62 4.34 13.96 20
26 22-23 10.21 2.32 12.53 21
27 19-23 12.41 3.25 15.66 19
28 23-24 6.24 1.22 7.46 23
29 24-6 196.42 4.56 200.98 2
6.2 Relationship Between Performance Indices And Outages
The relationship between the performance indices and outages is plotted in figure 5 below. It has been
shown in Table 4 that contingency has been ranked by considering the line with the highest performance
indices. Kaduna to Shiroro having the highest performance indices is ranked first and Jebba GS to Jebba TS
having the least performance indices is ranked the last. However, the most severe contingency which is clearly
shown in figure 4, should be given priority attention.
Figure 4: Performance indices plotted against line outage numbers.
Contingency Evaluation of a Peturbed Electric Network
DOI: 10.9790/1676-1052136142 www.iosrjournals.org 142 | Page
VII. Conclusion
Considering the number of numerical iteration per time taken, Fast Decoupled load flow method has
proven to be excellent in the load flow analysis of the 27-bus Nigerian 330kV transmission grid. Hence, owing
to its time for numerical iteration, its capacity to hold as many data as possible and its merit of having a matrix
alteration formula that can be incorporated and used to simulate problem of contingencies involving power
system equipment outages without involving the inversion of the Jacobian matrix for all iteration, then FDLF is
considered extensively in the research work. The load flow studies identified buses with low voltages. At the
outage of Kainji generator bus, it was observed that Birnin-Kebbi, Jos, Gombe, Kaduna, Katampe, Oshogbo,
Ajaokuta, New Haven, Aiyede, Ikeja-West, Onitsha and Akangba have voltages less than 0.95pu which was
regarded as low voltages. Power losses greater than 5% were also observed at Jebba TS to Oshogbo, Ikeja-West
to Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to
Gombe. At the outage of Sapele GS and Calabar GS, low voltages were noticed in the same buses given above
and also power losses greater than 5% in the same line above. However, a single line contingency evaluation
shows that a transmission line from Kaduna to Shiroro has the highest severity index and hence ranked number
one (1). The ranking continued until the line with the least performance index. Furthermore, it can be seen that
the outages of one or more generators give low voltages at the same bus and power losses at the same
transmission lines. Hence, it becomes expedient to compensate the lines.
References
[1]. O. A. Ezechukwu. “Expansion planning for Nigerian‟s South East Electric Power Transmission Network”. The International
Journal of Engineering and Science (IJS) Volume 2, Issue 9, pp.1804-1805, 2013.
[2]. C. J. Nnonyelu, T. C. Madueme and B. O. Anyaka “Power System Contingency Analysis”: A study of Nigerian 330kV
Transmission Grid. Proceedings of the 4th
Electrical Engineering National Conference on Energy sources for power generation, 21-
23 July. University of Nigeria,Nsukka. pp. 250, 2013.
[3]. K. W. Chan, R.W. Dunn, A.R. Daniels, J.A. Padget, A.O.Ekwue, E. H. Buxton and M. J. Rawlins. “On-line dynamic-security
contingency screening and ranking”. IEE Proceedings.-Generation, Transmission and Distribution. Vol. 144, No. 2, pp. 132-138,
March 1997.
[4]. A. A Fouad, and V. Vittal, „Dynamic security assessment utilizing the transient energy function method‟, IEEE Trans.Power
Syst.Vol.34, No. 1, pp. 284-291, 1986.
[5]. P. Seaux, M. Pavella, E. Euxibie, B. Heilbronn, and J. F. Lesigne, „Extended equal-area criterion revisited‟. Proceedings of IEEE
Power Engineering Society Summer Meeting, pp. 422-426, 1991.
[6]. El-Kady, M. A. Tang, C. K. Carvalho, V.F. Cauley, G. Kumar, A. Brandwajn and A. Ipakchi, “Artificial intelligence applications in
on-line dynamic security assessment”. Proceedings of PSCC 11, Vol. 2, pp. 881-887, 1993.
[7]. J. B. Gupta. “A Course in Power Systems” S. Chand and Company Ltd. India pp. 625, 2013.
[8]. J. A. Treece. “Boot strap Gauss-Seidel load flow”. Proceedings of the IEEE. Vol. 116, pp. 866-870, 1969.
[9]. J. B. Ward and H. W Hale. “Digital Computer Solution of Power Flow Problems”.Trans.Am.Inst.Electr.Eng.Part375, pp. 398-404,
1956.
[10]. G. W. Stagg and A. G. Phadke. “Real Time Evaluation of Power System Contingencies Detection of Steady State Overloads”. IEEE
Power Eng. Soc. Summer power meet, 1970, Paper. No. 70, pp. 692, 1970.
[11]. A. O. Ekwue, H. B. Wan, D. T. Y. Cheng and Y. H. Song. “Voltage Stability Analysis on the NGC System”. Electric Power
Systems Research Vol. 47,Issue 6, pp. 173–180, 1998.

More Related Content

PDF
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
IDES Editor
 
PDF
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
IDES Editor
 
PDF
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
IDES Editor
 
PPTX
ANN for Load Flow Studies
mjvshin
 
PDF
Line Losses in the 14-Bus Power System Network using UPFC
IDES Editor
 
PDF
Design and Performance of a PV-STATCOM for Enhancement of Power Quality in Mi...
International Journal of Power Electronics and Drive Systems
 
PDF
Optimal Capacitor Placement for IEEE 14 bus system using Genetic Algorithm
AM Publications
 
PDF
Fault location techniques in smart distribution system
Siksha 'O' Anusandhan (Deemed to be University )
 
Artificial Intelligence Technique based Reactive Power Planning Incorporating...
IDES Editor
 
Optimal Placement of DG for Loss Reduction and Voltage Sag Mitigation in Radi...
IDES Editor
 
Design and Performance Analysis of Genetic based PID-PSS with SVC in a Multi-...
IDES Editor
 
ANN for Load Flow Studies
mjvshin
 
Line Losses in the 14-Bus Power System Network using UPFC
IDES Editor
 
Design and Performance of a PV-STATCOM for Enhancement of Power Quality in Mi...
International Journal of Power Electronics and Drive Systems
 
Optimal Capacitor Placement for IEEE 14 bus system using Genetic Algorithm
AM Publications
 
Fault location techniques in smart distribution system
Siksha 'O' Anusandhan (Deemed to be University )
 

What's hot (20)

PDF
Droop control approach for power sharing in AC microgrid
Siksha 'O' Anusandhan (Deemed to be University )
 
PDF
Short and open circuit faults study in the PV system inverter
International Journal of Power Electronics and Drive Systems
 
PDF
IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
IRJET Journal
 
PDF
Penetration of PluginHybrid Electric Vehicles via Distribution Network
Raja Larik
 
PDF
Frequency regulation service of multiple-areas vehicle to grid application in...
IJECEIAES
 
PDF
Coordinated planning in improving power quality considering the use of nonlin...
IJECEIAES
 
PDF
Decentralised PI controller design based on dynamic interaction decoupling in...
IJECEIAES
 
PDF
Power transformer faults diagnosis using undestructive methods and ann for dg...
Mellah Hacene
 
PDF
Comparison of electronic load using linear regulator and boost converter
International Journal of Power Electronics and Drive Systems
 
PDF
Heuristic remedial actions in the reliability assessment of high voltage dire...
IJECEIAES
 
PDF
IRJET- Feed-Forward Neural Network Based Transient Stability Assessment o...
IRJET Journal
 
PDF
Design methodology of smart photovoltaic plant
IJECEIAES
 
PDF
A0710113
IOSR Journals
 
PDF
The gravitational search algorithm for incorporating TCSC devices into the sy...
IJECEIAES
 
PDF
DETERMINISTIC APPROACH AVAILABLE TRANSFER CAPABILITY (ATC) CALCULATION METHODS
Raja Larik
 
PDF
CONTROL OF BATTERY OPERATED SYSTEM WITH A DC-DC BOOSTCONVERTER FED DSTATCOM U...
ijiert bestjournal
 
PDF
Ga based optimal facts controller for maximizing loadability with stability c...
IAEME Publication
 
PDF
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Tao Yang
 
PDF
Power System State Estimation - A Review
IDES Editor
 
Droop control approach for power sharing in AC microgrid
Siksha 'O' Anusandhan (Deemed to be University )
 
Short and open circuit faults study in the PV system inverter
International Journal of Power Electronics and Drive Systems
 
IRJET- Voltage Stability, Loadability and Contingency Analysis with Optimal I...
IRJET Journal
 
Penetration of PluginHybrid Electric Vehicles via Distribution Network
Raja Larik
 
Frequency regulation service of multiple-areas vehicle to grid application in...
IJECEIAES
 
Coordinated planning in improving power quality considering the use of nonlin...
IJECEIAES
 
Decentralised PI controller design based on dynamic interaction decoupling in...
IJECEIAES
 
Power transformer faults diagnosis using undestructive methods and ann for dg...
Mellah Hacene
 
Comparison of electronic load using linear regulator and boost converter
International Journal of Power Electronics and Drive Systems
 
Heuristic remedial actions in the reliability assessment of high voltage dire...
IJECEIAES
 
IRJET- Feed-Forward Neural Network Based Transient Stability Assessment o...
IRJET Journal
 
Design methodology of smart photovoltaic plant
IJECEIAES
 
A0710113
IOSR Journals
 
The gravitational search algorithm for incorporating TCSC devices into the sy...
IJECEIAES
 
DETERMINISTIC APPROACH AVAILABLE TRANSFER CAPABILITY (ATC) CALCULATION METHODS
Raja Larik
 
CONTROL OF BATTERY OPERATED SYSTEM WITH A DC-DC BOOSTCONVERTER FED DSTATCOM U...
ijiert bestjournal
 
Ga based optimal facts controller for maximizing loadability with stability c...
IAEME Publication
 
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Tao Yang
 
Power System State Estimation - A Review
IDES Editor
 
Ad

Viewers also liked (14)

PPT
Taller de construcción
Mamen Guerrero
 
PDF
E012262226
IOSR Journals
 
PDF
Influence of the speed in advance and the laser’s power on the zone affected ...
IOSR Journals
 
PDF
Mex02
lalolanda21
 
PDF
Carpeta mega-a3
JORGE SEBASTIAN CALLE AYALA
 
PPTX
Animación (imagenes)
UNED
 
PDF
Leisure Patterns Among Nigerian University Lecturers: the Potential for Leisu...
IOSR Journals
 
PDF
R01051141149
IOSR Journals
 
PPT
Characteristics of life
vjcummins
 
DOCX
steven cv-1
steven sioh
 
PDF
Papelería y Anuncios
Gabriel Álvarez
 
ODP
Gloria fuertes
Mamen Guerrero
 
PPTX
NJ Future Redevelopment Forum 2017 Maraziti
New Jersey Future
 
Taller de construcción
Mamen Guerrero
 
E012262226
IOSR Journals
 
Influence of the speed in advance and the laser’s power on the zone affected ...
IOSR Journals
 
Animación (imagenes)
UNED
 
Leisure Patterns Among Nigerian University Lecturers: the Potential for Leisu...
IOSR Journals
 
R01051141149
IOSR Journals
 
Characteristics of life
vjcummins
 
steven cv-1
steven sioh
 
Papelería y Anuncios
Gabriel Álvarez
 
Gloria fuertes
Mamen Guerrero
 
NJ Future Redevelopment Forum 2017 Maraziti
New Jersey Future
 
Ad

Similar to Q01052136142 (20)

PDF
IRJET- Improved Electrical Power Supply to Trans-Amadi Industrial Layout, Por...
IRJET Journal
 
PDF
Power Flow Analysis of Island Business District 33KV Distribution Grid System...
IJERA Editor
 
PDF
IRJET- Improvement of Voltage Stability by Placing UPFC using Fuzzy Logic
IRJET Journal
 
PDF
Convergence Problems Of Contingency Analysis In Electrical Power Transmission...
CSCJournals
 
PDF
Predicting Post Outage Transmission Line Flows using Linear Distribution Factors
Dr. Amarjeet Singh
 
PDF
The International Journal of Engineering and Science (The IJES)
theijes
 
PDF
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
IRJET Journal
 
PDF
Influencing Factors on Power Losses in Electric Distribution Network
IJAEMSJORNAL
 
PDF
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
IRJET Journal
 
PDF
IRJET-Identification of Weak Bus using Load Variation
IRJET Journal
 
PDF
Comparative Study of Modified Euler and 4th Order Runge Kutta Numerical Techn...
pollen barua
 
PDF
Voltage stability assessment prediction using a guide strategy-based adaptive...
International Journal of Power Electronics and Drive Systems (IJPEDS)
 
PDF
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
ijiert bestjournal
 
PDF
Two-way Load Flow Analysis using Newton-Raphson and Neural Network Methods
IRJET Journal
 
PDF
A comprehensive fuzzy-based scheme for online detection of operational and t...
IJECEIAES
 
PDF
Paper id 2520147
IJRAT
 
PDF
Machine learning for prediction models to mitigate the voltage deviation in ...
IJECEIAES
 
PDF
Artificial Neural Networks for Control.pdf
satouf1
 
PDF
IRJET- Load Flow Analysis of IEEE 14 Bus Systems in Matlab by using Fast Deco...
IRJET Journal
 
PDF
Investigation Effect of Outage Line on the Transmission Line for Karbalaa-132...
IRJET Journal
 
IRJET- Improved Electrical Power Supply to Trans-Amadi Industrial Layout, Por...
IRJET Journal
 
Power Flow Analysis of Island Business District 33KV Distribution Grid System...
IJERA Editor
 
IRJET- Improvement of Voltage Stability by Placing UPFC using Fuzzy Logic
IRJET Journal
 
Convergence Problems Of Contingency Analysis In Electrical Power Transmission...
CSCJournals
 
Predicting Post Outage Transmission Line Flows using Linear Distribution Factors
Dr. Amarjeet Singh
 
The International Journal of Engineering and Science (The IJES)
theijes
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
IRJET Journal
 
Influencing Factors on Power Losses in Electric Distribution Network
IJAEMSJORNAL
 
IRJET- Assessment of Voltage Stability in a Power System Network and its Impr...
IRJET Journal
 
IRJET-Identification of Weak Bus using Load Variation
IRJET Journal
 
Comparative Study of Modified Euler and 4th Order Runge Kutta Numerical Techn...
pollen barua
 
Voltage stability assessment prediction using a guide strategy-based adaptive...
International Journal of Power Electronics and Drive Systems (IJPEDS)
 
LOAD FLOW ANALYSIS FOR A 220KV LINE – CASE STUDY
ijiert bestjournal
 
Two-way Load Flow Analysis using Newton-Raphson and Neural Network Methods
IRJET Journal
 
A comprehensive fuzzy-based scheme for online detection of operational and t...
IJECEIAES
 
Paper id 2520147
IJRAT
 
Machine learning for prediction models to mitigate the voltage deviation in ...
IJECEIAES
 
Artificial Neural Networks for Control.pdf
satouf1
 
IRJET- Load Flow Analysis of IEEE 14 Bus Systems in Matlab by using Fast Deco...
IRJET Journal
 
Investigation Effect of Outage Line on the Transmission Line for Karbalaa-132...
IRJET Journal
 

More from IOSR Journals (20)

PDF
A011140104
IOSR Journals
 
PDF
M0111397100
IOSR Journals
 
PDF
L011138596
IOSR Journals
 
PDF
K011138084
IOSR Journals
 
PDF
J011137479
IOSR Journals
 
PDF
I011136673
IOSR Journals
 
PDF
G011134454
IOSR Journals
 
PDF
H011135565
IOSR Journals
 
PDF
F011134043
IOSR Journals
 
PDF
E011133639
IOSR Journals
 
PDF
D011132635
IOSR Journals
 
PDF
C011131925
IOSR Journals
 
PDF
B011130918
IOSR Journals
 
PDF
A011130108
IOSR Journals
 
PDF
I011125160
IOSR Journals
 
PDF
H011124050
IOSR Journals
 
PDF
G011123539
IOSR Journals
 
PDF
F011123134
IOSR Journals
 
PDF
E011122530
IOSR Journals
 
PDF
D011121524
IOSR Journals
 
A011140104
IOSR Journals
 
M0111397100
IOSR Journals
 
L011138596
IOSR Journals
 
K011138084
IOSR Journals
 
J011137479
IOSR Journals
 
I011136673
IOSR Journals
 
G011134454
IOSR Journals
 
H011135565
IOSR Journals
 
F011134043
IOSR Journals
 
E011133639
IOSR Journals
 
D011132635
IOSR Journals
 
C011131925
IOSR Journals
 
B011130918
IOSR Journals
 
A011130108
IOSR Journals
 
I011125160
IOSR Journals
 
H011124050
IOSR Journals
 
G011123539
IOSR Journals
 
F011123134
IOSR Journals
 
E011122530
IOSR Journals
 
D011121524
IOSR Journals
 

Recently uploaded (20)

PDF
Brief History of Internet - Early Days of Internet
sutharharshit158
 
PDF
Tea4chat - another LLM Project by Kerem Atam
a0m0rajab1
 
PDF
Oracle AI Vector Search- Getting Started and what's new in 2025- AIOUG Yatra ...
Sandesh Rao
 
PPTX
Simple and concise overview about Quantum computing..pptx
mughal641
 
PDF
GDG Cloud Munich - Intro - Luiz Carneiro - #BuildWithAI - July - Abdel.pdf
Luiz Carneiro
 
PDF
Structs to JSON: How Go Powers REST APIs
Emily Achieng
 
PPTX
Dev Dives: Automate, test, and deploy in one place—with Unified Developer Exp...
AndreeaTom
 
PPTX
Applied-Statistics-Mastering-Data-Driven-Decisions.pptx
parmaryashparmaryash
 
PPTX
OA presentation.pptx OA presentation.pptx
pateldhruv002338
 
PDF
How ETL Control Logic Keeps Your Pipelines Safe and Reliable.pdf
Stryv Solutions Pvt. Ltd.
 
PDF
Doc9.....................................
SofiaCollazos
 
PDF
Software Development Methodologies in 2025
KodekX
 
PDF
Google I/O Extended 2025 Baku - all ppts
HusseinMalikMammadli
 
PDF
A Strategic Analysis of the MVNO Wave in Emerging Markets.pdf
IPLOOK Networks
 
PPTX
What-is-the-World-Wide-Web -- Introduction
tonifi9488
 
PPTX
Agile Chennai 18-19 July 2025 | Emerging patterns in Agentic AI by Bharani Su...
AgileNetwork
 
PDF
CIFDAQ's Market Wrap : Bears Back in Control?
CIFDAQ
 
PDF
OFFOFFBOX™ – A New Era for African Film | Startup Presentation
ambaicciwalkerbrian
 
PPTX
Introduction to Flutter by Ayush Desai.pptx
ayushdesai204
 
PDF
Peak of Data & AI Encore - Real-Time Insights & Scalable Editing with ArcGIS
Safe Software
 
Brief History of Internet - Early Days of Internet
sutharharshit158
 
Tea4chat - another LLM Project by Kerem Atam
a0m0rajab1
 
Oracle AI Vector Search- Getting Started and what's new in 2025- AIOUG Yatra ...
Sandesh Rao
 
Simple and concise overview about Quantum computing..pptx
mughal641
 
GDG Cloud Munich - Intro - Luiz Carneiro - #BuildWithAI - July - Abdel.pdf
Luiz Carneiro
 
Structs to JSON: How Go Powers REST APIs
Emily Achieng
 
Dev Dives: Automate, test, and deploy in one place—with Unified Developer Exp...
AndreeaTom
 
Applied-Statistics-Mastering-Data-Driven-Decisions.pptx
parmaryashparmaryash
 
OA presentation.pptx OA presentation.pptx
pateldhruv002338
 
How ETL Control Logic Keeps Your Pipelines Safe and Reliable.pdf
Stryv Solutions Pvt. Ltd.
 
Doc9.....................................
SofiaCollazos
 
Software Development Methodologies in 2025
KodekX
 
Google I/O Extended 2025 Baku - all ppts
HusseinMalikMammadli
 
A Strategic Analysis of the MVNO Wave in Emerging Markets.pdf
IPLOOK Networks
 
What-is-the-World-Wide-Web -- Introduction
tonifi9488
 
Agile Chennai 18-19 July 2025 | Emerging patterns in Agentic AI by Bharani Su...
AgileNetwork
 
CIFDAQ's Market Wrap : Bears Back in Control?
CIFDAQ
 
OFFOFFBOX™ – A New Era for African Film | Startup Presentation
ambaicciwalkerbrian
 
Introduction to Flutter by Ayush Desai.pptx
ayushdesai204
 
Peak of Data & AI Encore - Real-Time Insights & Scalable Editing with ArcGIS
Safe Software
 

Q01052136142

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 5 Ver. II (Sep – Oct. 2015), PP 136-142 www.iosrjournals.org DOI: 10.9790/1676-1052136142 www.iosrjournals.org 136 | Page Contingency Evaluation of a Peturbed Electric Network J. N. Onah1 , T.C Madueme2 and V.C Ukwueze3 1,2,3 (Department Of Electrical Engineering,University Of Nigeria, Nsukka. Enugu State-Nigeria ) Abstract: A single line contingency analysis and generator(s) outages were carried out on a 330kV power network using MATPOWER 4.1 embedded in MATLAB to carry out fast decoupled load flow studies in order to identify the voltage violation at various buses, determine power losses at the transmission lines and to compute the performance indices. The performance indices were further ranked in accordance with their severity indices. Voltages less than 0.95pu were assumed to be low voltages and voltages greater than 1.05pu were also assumed to be high voltages. It was also assumed that power losses greater than 5% are unacceptable. So a base case comparative analysis of the load flow studies using three conventional methods showed that Gauss Seidel could not converge in 0.93seconds and 1000 iterations, Newton Raphson converged in 0.15seconds and 6 iterations. However, Fast Decoupled Load Flow (FDLF) converged in 0.01second and 28 iterations. Further, a single line contingency analysis was also carried out on the transmission lines to investigate the performance indices of the lines which were later ranked in accordance with their severity. The outcome of the simulations showed that at a time when there was an outage of Kainji-GS, low voltages were found at Kano, Jos, Gombe, Kaduna, Katampe, Oshogbo, Ajaokuta, New Haven, Aiyede, Ikeja-West, Onitsha, and Akangba buses. And there were also power losses greater than 5% at Ikeja-West to Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to Gombe. Key Words: Contingency Evaluation, FDLF, Performance Index, Power Loss, Line outage. I. Introduction A typical issue that confronts the integrated power project is outages on the transmission lines. Outages diminish the productivity of the transmission system as they cause power disturbance and interference [1]. Moreover, the incessant and unprecedented vandalisation of the power equipment of the Nigerian power systems resulting in cascaded outages of either the transmission line or the generator(s) in the recent time leaves much to be desired. Consequently, contingency evaluation is necessary to showcase the areas that may lead to total system voltage collapse and power losses. We are to carry out Fast Decoupled Load flow to determine the voltage magnitudes, real and reactive powers that enabled us to calculate the performance indices of each of the transmission lines and later rank them based on their severity. The study involves (N-1) secure otherwise called single line contingency evaluation on the Nigerian 330kV transmission grid. Contingency analysis is the study of the outage of elements such as transmission lines, transformers and generators, and investigation of the resulting effects on line power flows and bus voltages of the remaining system [2]. II. Overview Of Contingency Evaluation Nnonyelu et al [2] looked at the overloading at various transmission lines but could not bring to lime light the voltage instability of the network as well as the effect of power losses in the transmission lines. It has been established by Chan et al [3] that some transient-stability analysis concerns the transient behaviour of the power system when moving from the pre-contingency to post-contingency operating point. However, owing to computational economics, both direct methods [4, 5] and artificial-intelligence methods [6] have often been proposed for use in online transient-stability assessment. However, it is not easy to apply these methods to larger power systems involving complex models of plant and contingencies. But an application of a conventional load flow method, gives a fast and a reliable result. However, Newton-Raphson method may be used to solve the network equations but the method is computationally expensive because it needs to calculate the Jacobian at each iteration of the algorithm. To improve the computational performance, a fast decoupled solution technique is used to solve AC network equations iteratively [7]. It is a very fast and efficient method of obtaining power flow problem solution. In this method both speed as well as sparsity is exploited. It is an extension of N-R method formulated in polar coordinate with certain approximations which result into a fast algorithm for power flow solution. This method exploits the property of the power system where the MW flow-voltage angle and MVAR flow –Voltage magnitude is loosely coupled. In order words a small change in the magnitude of bus voltage does not affect the real power flow at the bus and similarly a small change in phase angle of the bus voltage has hardly any effect on reactive power flow. On the account of loose physical interaction between the MW and the MVAR flows in a power system, the MW-δ and MVAR-V calculations can be decoupled resulting
  • 2. Contingency Evaluation of a Peturbed Electric Network DOI: 10.9790/1676-1052136142 www.iosrjournals.org 137 | Page to a very simple, fast and reliable algorithm [7]. The fastness is on the account of the sparsity feature of the admittance matrix that minimizes the computer memory requirement. Most of the early iterative techniques were based on the Y-matrix of the G-S method [8]. It requires minimum computer storage and needs only a small number of iterations for small networks. However, as the size of the network is increased the number of iterations required increases dramatically for large systems. In some cases the method does not provide solution at all [9]. Hence the slow convergence of G-S method and its frequent failure to converge in ill- conditioned situations caused the development of Z-Matrix methods [10]. In spite of the fact that these methods have considerably better converging characteristics, they also have the demerit of needing a significantly large computer storage memory owing to the fact that Z-matrix is full, contrary to the Y-Matrix which is sparse. Consequently, the shortcomings led to the development of N-R algorithm to solve the simultaneous quadratic equations of power network .Contrary to the G-S algorithm, it needs a large time per iteration but only a few iterations and is significantly independent of the network size. However, in a realistic power system, there may be a large number of buses, for instance, 100 or more but each bus is connected to only a small number usually two or more of the remaining buses. That is to say that of a large power system is very sparse. This implies that it has a large number of zero elements, hence the sparcity feature of minimizes the computer memory requirement as only non-zero terms are considered for storage and results in faster computation. This idea leads to the development of Fast Decoupled power flow method. It is a very fast, reliable and efficient method of obtaining power flow problem solution. It exploits speed and accuracy in its methodology [5]. It has a compatible accuracy with that of N-R method. For the sake of brevity, FDPF is an extension of N-R method formulated in polar coordinates with certain approximation which results in algorithm for power flow solution. It has been stated by Ekwue et al [11] that power Systems are generally nonlinear in nature and some primary elements such as generator, branch outage etc contribute to the severity of the nonlinearity. So considering the merits of FDPF aforementioned, we intend to look at the line flows, losses in the line, voltage violation constraints and the performance indices which were found missing in the work of the various authors reviewed above using the fast decoupled power flow algorithm. III. The Network Under Study And Data A single line diagram of the 330Kv Nigerian Power grid used in the study is shown in figure 1. It comprises nine generator buses, eighteen load buses, twenty nine transmission lines of the Nigerian 330kV transmission system. Figure 1: One line diagram of Nigerian 330kV transmission grid [2]
  • 3. Contingency Evaluation of a Peturbed Electric Network DOI: 10.9790/1676-1052136142 www.iosrjournals.org 138 | Page Tables 1, 2 and 3 show generator data, load data and line data respectively that are used for the simulations Table 1: Generator Data S/No. Bus name PG(MW) Rated 1 Kainji GS 756 2 Shiroro 413 3 Jebba GS 339 4 Sapele 70 5 Egbin 967 6 Afam 316 7 Delta GS 498 8 AES 235 9 Calabar 0 Source: [2 ] Table 2: Load Data Source: [2 ]
  • 4. Contingency Evaluation of a Peturbed Electric Network DOI: 10.9790/1676-1052136142 www.iosrjournals.org 139 | Page Table 3: Line Data Branch No. From To R(pu) X(pu) B(PU) 1 10 1 0.02676 0.06576 1.178 2 8 5 0.00300 0.02100 0.300 3 9 24 0.00216 0.00530 0.2570 4 1 15 0.00699 0.01718 0.308 5 3 15 0.00069 0.0017 0.033 6 15 17 0.01355 0.0333 0.597 7 17 21 0.02167 0.05324 0.521 8 17 20 0.00993 0.02439 0.437 9 20 21 0.01183 0.02906 0.521 10 21 25 0.00147 0.0361 0.065 11 21 5 0.00535 0.01315 0.257 12 5 26 0.00138 0.00339 0.257 13 21 22 0.02417 0.05939 1.162 14 22 4 0.00432 0.01061 0.208 15 4 27 0.00544 0.01336 0.239 16 7 27 0.00276 0.00679 0.239 17 7 22 0.00924 0.0227 0.239 18 18 22 0.0145 0.03564 0.208 19 17 22 0.02167 0.05324 0.954 20 2 15 0.02106 0.05176 0.927 21 2 16 0.01243 0.03055 0.308 22 14 2 0.00829 0.02036 0.364 23 11 14 0.01985 0.04879 0.874 24 12 14 0.01692 0.04158 0.927 25 12 13 0.002279 0.056 1.01 26 22 23 0.01183 0.02906 0.521 27 19 23 0.00829 0.02036 0.365 28 23 24 0.01191 0.02927 0.524 29 24 6 0.00216 0.0053 0.104 Source: [2 ] IV. Methodology The power flow study of the 330kV line was carried out comparatively, using various techniques such as Gauss-Seidel, Newton Raphson and Fast Decoupled Load Flow. However, Gauss-Seidel could not converge after 0.93seconds and 1000 iterations. Newton Raphson Converged in 0.15seconds and 6 Iterations but as a matter of fact, Fast Decoupled load flow converged in 0.01seconds and 28 Iterations. Hence, because of its time for numerical iteration and its capacity to hold as many data as possible, we utilized the FDLF for the research work. To compute the performance indices, one of the lines was removed and the load flow analysis was carried out in order to see the effect on the network. This was done by calculating the performance indices and ranking them based on highest severity and thus, the operation continued until no severe contingencies are found. The performance indices are given by (1) Moreover, the has got to do with the violation of the line active power flow and it is given by: AiP = ∑i=1 N ( Api Api max )2x (2) Where, = Active power performance index =Active power flow in line i Api max = Maximum active power flow in line i N = The total number of transmission lines in the system. x = the specific exponent where x is assumed to be unity. And the maximum power flow in each line is given by (3) Where, Vj = voltage at bus j got from FDLF solution, = Voltage at bus k obtained from FDLF solution. And = impedance of the line connecting bus j and k. However, (4)
  • 5. Contingency Evaluation of a Peturbed Electric Network DOI: 10.9790/1676-1052136142 www.iosrjournals.org 140 | Page (5) Figure 2 shows a bar chart that represents voltage drops at various branches when Kainji- generating station was not committed. The result shows that the following buses are experiencing low voltages. They are: Kano, Jos, Gombe, Kaduna, Katampe, Oshogbo, Ajaokuta, New Haven, Aiyede, Ikeja-West, Onitsha and Akangba. V. Simulation, Results And Discussion The input data for the case to be simulated are specified in a set of data matrices packaged as the fields of a Matlab struct, referred to as a “Matpower case" and denoted by the variable mpc. The struct is typically defined in a case file called M-file whose return value is mpc struct. The solver was invoked by calling the simulation function “runpf” and passing in a case file name as the first argument. So the FDLF was ran by typing runpf(„case27‟) . By default, the results of the simulation are pretty to the screen, displaying a system summary, bus data, branch data and, for the power flow, binding constraint information. The bus data comprises the voltage, angle, total generation and load at each bus. The branch data shows the power flows and power losses in each branch. Then the performance indices were computed using equations 1,2,3,4 and 5. The voltage drops and the power losses are respectively shown in figure 2 and figure 3. Figure 2: Voltage drop at the outage of kainji GS At the outage of Kainji GS, the following branches experienced power losses. They are: Ikeja-West to Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to Gombe. Figure 3: Power loss at the various branches when kainji- generating station was not committed.
  • 6. Contingency Evaluation of a Peturbed Electric Network DOI: 10.9790/1676-1052136142 www.iosrjournals.org 141 | Page Power losses greater than 5% were observed at Ikeja-West to Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to Gombe transmission lines. VI. Computing The Performance Indices The calculation of the performance indices was done using equation 1. The simulation results provided the requisite parameters such as those given in equations 2, 3, 4 and 5.The results are tabulated in Table 4. Table 4: Performance indices of the various lines of the network and the ranking based on the severity of the lines Branch No. 1 1-10 40.41 0.900 41.31 11 2 8-5 24.85 0.410 25.26 17 3 9-24 6.68 0.40 7.08 24 4 1-15 8.56 0.52 9.08 22 5 3-15 0.16 0.32 0.48 29 6 15-17 4.65 0.88 5.53 25 7 17-21 138.59 0.87 139.46 6 8 17-20 116.43 0.44 116.84 7 9 20-21 85.40 0.01 85.41 8 10 21-25 4.19 16.45 20.64 18 11 21-5 1.08 0.64 1.74 27 12 5-26 1.64 1.08 2.72 26 13 21-22 18.75 20.38 39.13 12 14 22-4 9.37 66.08 75.45 9 15 4-27 13.61 14.30 27.91 13 16 7-27 13.27 12.98 26.25 16 17 7-22 164.42 14.81 179.23 3 18 18-22 9.68 17.80 27.49 14 19 17-22 159.11 18.08 177.19 5 20 2-15 1.34 25.10 26.44 15 21 2-16 60.51 1.02 61.53 10 22 14-2 214 6.52 220.52 1 23 11-14 0.75 0.24 0.99 28 24 12-14 175..62 2.14 177.76 4 25 12-13 9.62 4.34 13.96 20 26 22-23 10.21 2.32 12.53 21 27 19-23 12.41 3.25 15.66 19 28 23-24 6.24 1.22 7.46 23 29 24-6 196.42 4.56 200.98 2 6.2 Relationship Between Performance Indices And Outages The relationship between the performance indices and outages is plotted in figure 5 below. It has been shown in Table 4 that contingency has been ranked by considering the line with the highest performance indices. Kaduna to Shiroro having the highest performance indices is ranked first and Jebba GS to Jebba TS having the least performance indices is ranked the last. However, the most severe contingency which is clearly shown in figure 4, should be given priority attention. Figure 4: Performance indices plotted against line outage numbers.
  • 7. Contingency Evaluation of a Peturbed Electric Network DOI: 10.9790/1676-1052136142 www.iosrjournals.org 142 | Page VII. Conclusion Considering the number of numerical iteration per time taken, Fast Decoupled load flow method has proven to be excellent in the load flow analysis of the 27-bus Nigerian 330kV transmission grid. Hence, owing to its time for numerical iteration, its capacity to hold as many data as possible and its merit of having a matrix alteration formula that can be incorporated and used to simulate problem of contingencies involving power system equipment outages without involving the inversion of the Jacobian matrix for all iteration, then FDLF is considered extensively in the research work. The load flow studies identified buses with low voltages. At the outage of Kainji generator bus, it was observed that Birnin-Kebbi, Jos, Gombe, Kaduna, Katampe, Oshogbo, Ajaokuta, New Haven, Aiyede, Ikeja-West, Onitsha and Akangba have voltages less than 0.95pu which was regarded as low voltages. Power losses greater than 5% were also observed at Jebba TS to Oshogbo, Ikeja-West to Egbin, Ikeja-West to Benin, Oshogbo to Benin, Kaduna to Shiroro, Kano to Kaduna, Jos to Kaduna and Jos to Gombe. At the outage of Sapele GS and Calabar GS, low voltages were noticed in the same buses given above and also power losses greater than 5% in the same line above. However, a single line contingency evaluation shows that a transmission line from Kaduna to Shiroro has the highest severity index and hence ranked number one (1). The ranking continued until the line with the least performance index. Furthermore, it can be seen that the outages of one or more generators give low voltages at the same bus and power losses at the same transmission lines. Hence, it becomes expedient to compensate the lines. References [1]. O. A. Ezechukwu. “Expansion planning for Nigerian‟s South East Electric Power Transmission Network”. The International Journal of Engineering and Science (IJS) Volume 2, Issue 9, pp.1804-1805, 2013. [2]. C. J. Nnonyelu, T. C. Madueme and B. O. Anyaka “Power System Contingency Analysis”: A study of Nigerian 330kV Transmission Grid. Proceedings of the 4th Electrical Engineering National Conference on Energy sources for power generation, 21- 23 July. University of Nigeria,Nsukka. pp. 250, 2013. [3]. K. W. Chan, R.W. Dunn, A.R. Daniels, J.A. Padget, A.O.Ekwue, E. H. Buxton and M. J. Rawlins. “On-line dynamic-security contingency screening and ranking”. IEE Proceedings.-Generation, Transmission and Distribution. Vol. 144, No. 2, pp. 132-138, March 1997. [4]. A. A Fouad, and V. Vittal, „Dynamic security assessment utilizing the transient energy function method‟, IEEE Trans.Power Syst.Vol.34, No. 1, pp. 284-291, 1986. [5]. P. Seaux, M. Pavella, E. Euxibie, B. Heilbronn, and J. F. Lesigne, „Extended equal-area criterion revisited‟. Proceedings of IEEE Power Engineering Society Summer Meeting, pp. 422-426, 1991. [6]. El-Kady, M. A. Tang, C. K. Carvalho, V.F. Cauley, G. Kumar, A. Brandwajn and A. Ipakchi, “Artificial intelligence applications in on-line dynamic security assessment”. Proceedings of PSCC 11, Vol. 2, pp. 881-887, 1993. [7]. J. B. Gupta. “A Course in Power Systems” S. Chand and Company Ltd. India pp. 625, 2013. [8]. J. A. Treece. “Boot strap Gauss-Seidel load flow”. Proceedings of the IEEE. Vol. 116, pp. 866-870, 1969. [9]. J. B. Ward and H. W Hale. “Digital Computer Solution of Power Flow Problems”.Trans.Am.Inst.Electr.Eng.Part375, pp. 398-404, 1956. [10]. G. W. Stagg and A. G. Phadke. “Real Time Evaluation of Power System Contingencies Detection of Steady State Overloads”. IEEE Power Eng. Soc. Summer power meet, 1970, Paper. No. 70, pp. 692, 1970. [11]. A. O. Ekwue, H. B. Wan, D. T. Y. Cheng and Y. H. Song. “Voltage Stability Analysis on the NGC System”. Electric Power Systems Research Vol. 47,Issue 6, pp. 173–180, 1998.