LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY
Jonnada, Andhra Pradesh- 535005
UNIT -III
GENERATOR AND TRANSFORMER
PROTECTION (PART I)
Presented by,
Dr. Rohit Babu, Associate Professor
Department of Electrical and Electronics Engineering
Syllabus
Department of Electrical and Electronics Engineering
Part 1. Generator Protection
―Protection of generators against stator faults
―Rotor faults and abnormal conditions
―Restricted earth fault and inter turn fault protection
―Numerical examples
Part 2. Transformer Protection
―Percentage differential protection
―Design of CT’s ratio
―Buchholz relay protection
―Numerical examples
Part 1. Generator Protection
Department of Electrical and Electronics Engineering
―Protection of generators against stator faults
―Rotor faults and abnormal conditions
―Restricted earth fault and inter turn fault protection
―Numerical examples
Generator Protection
Department of Electrical and Electronics Engineering
A modern generating set is generally provided with the following protective schemes.
(i) Stator protection
(a) Percentage differential protection
(b) Protection against stator inter-turn faults
(c) Stator-overheating protection
(ii) Rotor protection
(a) Field ground-fault protection
(b) Loss of excitation protection
(c) Protection against rotor overheating because of unbalanced three-phase stator currents
(iii) Miscellaneous
(a) Overvoltage protection
(b) Overspeed protection
(c) Protection against motoring
(d) Protection against vibration
(e) Bearing-overheating protection
(f) Protection against auxiliary failure
(g) Protection against voltage regulator failure
Stator Protection
Department of Electrical and Electronics Engineering
(A) Percentage Differential Protection
Fig. 1 Percentage differential protection for external fault condition
(instantaneous current directions shown for external fault condition)
• It is used for the protection of generators above 1
MW.
• It protects against winding faults, i.e. phase to phase
and phase to ground faults.
• This is also called biased differential protection or
longitudinal differential protection.
• The polarity of the secondary voltage of CTs at a
particular moment for an external fault has been
shown in the figure.
• In the operating coil, the current sent by the upper
CT is cancelled by the current sent by the lower CT
and the relay does not operate.
Stator Protection
Department of Electrical and Electronics Engineering
Fig. 2 Percentage differential protection of generator
(instantaneous current directions shown for internal fault
condition)
• For an internal fault, the polarity of the secondary
voltage of the upper CT is reversed, as shown in Fig. 2.
• The operating coil carries the sum of the currents sent
by the upper CT and the lower CT and it operates and
trips the circuit breaker.
• The percentage differential protection does not
respond to external faults and overloads.
• It provides complete protection against phase to phase
faults.
• It provides protection against ground faults to about 80
to 85 per cent of the generator windings.
Stator Protection
Department of Electrical and Electronics Engineering
• It does not provide protection to 100 per cent of the winding because it is influenced by the
magnitude of the earth fault current which depends upon the method of neutral grounding.
• Due to the difference in the magnetizing currents of the upper and the lower CTs, the current
through the operating coil will not be zero even under normal loading conditions or during
external fault conditions.
• In case of stator faults, the tripping of circuit breaker to isolate the faulty generator is not
sufficient to prevent further damage as the generator will still continue to supply power to the
fault until its field excitation is suppressed.
Stator Protection
Department of Electrical and Electronics Engineering
Restricted earth-fault protection by differential system
Fig. 3 Percentage of unprotected winding against phase to ground fault
• When the neutral is solidly grounded, it is possible to
provide protection to complete winding of the generator
against ground faults.
• However, the neutral is grounded through resistance to
limit ground fault currents.
• With resistance grounding it is not possible to protect the
complete winding against ground faults.
• The percentage of winding protected depends on the
value of the neutral grounding resistor and the relay
setting.
• The usual practice is to protect 80 to 85% of the generator winding against ground fault. The remaining 15-20%
from neutral end is left unprotected.
• In Fig. 3 for phase to ground fault, it can be seen that the relay setting for the differential protection is determined
by the value of the neutral grounding resistor and the percentage of winding to be protected.
Stator Protection
Department of Electrical and Electronics Engineering
In Fig. 3, let p% of the winding from the neutral remains unprotected. Then (100 – p)% of the winding
is protected. The ground fault current If is given by
where, V is the line to neutral voltage and Rn is the neutral grounding resistance.
For the operation of the relay, the fault current must be greater than the relay pick-up current.
Stator Protection
Department of Electrical and Electronics Engineering
Percentage differential protection for a Y-connected generator with only four leads brought out
• When the neutral connection is made within the
generator and only the neutral terminal is brought
out, the percentage differential protection can be
provided, as shown in Fig. 4.
Fig. 4 Percentage differential protection for Y connected
generator with only four leads brought out
• This scheme protects the generator winding only
against ground faults.
• It does not protect it against phase faults.
Generator-transformer unit protection
Stator Protection
Department of Electrical and Electronics Engineering
(B) Protection against Stator Interturn Faults
• Longitudinal percentage differential protection does
not detect stator interturn faults.
• A transverse percentage differential protection, as
shown in Fig. 5 is employed for the protection of the
generator against stator interturn faults.
Fig. 5 Transverse percentage differential protection for multi-
winding generators
Stator Protection
Department of Electrical and Electronics Engineering
• A faster and more sensitive split-phase
protection as shown in Fig. 6 can be employed.
• In this scheme, a single CT having double
primary is used.
• No bias is necessary because a common CT is
employed so that errors due to CT differences
do not occur.
Fig. 6 Split-phase protection of generator using double primary CTs
Stator Protection
Department of Electrical and Electronics Engineering
Interturn protection based on zero-sequence component
• If generators do not have access to parallel
windings, a method based on zero-sequence
voltage measurement can be employed for
the protection against stator interturn faults.
• This type of scheme will also be applicable to
single winding generators having multi-turn
per phase per slot to protect against interturn
faults.
• Figure 7 shows the schematic diagram of
interturn protection by zero-sequence
• voltage measurement across the machine.
Fig. 7 Interturn protection of generator using zero-sequence voltage
Stator Protection
Department of Electrical and Electronics Engineering
(C) Stator-overheating Protection
Modern generators employ two methods to detect overheating both being used in large generators
(above 2 MW).
First Method, the inlet and outlet temperatures of the cooling medium which may be hydrogen/
water are compared for detecting overheating.
Second Method, the temperature sensing elements are embedded in the stator slots to sense the
temperature.
Stator Protection
Department of Electrical and Electronics Engineering
Fig. 8 Stator-overheating protection
• When the temperature exceeds a certain preset maximum
temperature limit, the relay sounds an alarm.
• The scheme employs a temperature detector unit, relay
and Wheatstone-bridge for the purpose.
• The temperature sensing elements may either be
thermistors, thermocouples or resistance temperature
indicators.
• They are embedded in the stator slots at different
locations.
• These elements are connected to a multi-way selector
switch which checks each one in turn for a period long
enough to operate an alarm relay.
Rotor Protection
Department of Electrical and Electronics Engineering
(A) Field Ground-fault Protection
As the field circuit is operated ungrounded, a single ground fault does not
affect the operation of the generator or cause any damage.
• A dc voltage is impressed between the field circuit and earth through a
polarised moving iron relay.
• It is not necessary to trip the machine when a single field earth fault occurs.
• Usually an alarm is sounded. Then immediate steps are taken to transfer
the load from the faulty generator and to shut it down as quickly.
• In case of brushless machines, the main field circuit is not accessible.
Fig. 9 Earth fault protection
• If there is a partial field failure due to short-circuiting of turns in the main field winding, it is detected by the
increase in level of the field current.
• A severe fault or short-circuiting of the diode is detected by a relay monitoring the current in the exciter control
circuit.
Rotor Protection
Department of Electrical and Electronics Engineering
(B) Loss of Excitation
• When the excitation of a generator is lost, it speeds up slightly and
operates as an induction generator.
• Round-rotor generators do not have damper windings and hence they
are not suitable for such an operation.
• The rotor is overheated quickly due to heavy induced currents in the
rotor iron.
• The rotors of salient pole generators are not overheated because they
have damper windings which carry induced currents.
• The stators of both salient and non-salient pole generators are
overheated due to wattless current drawn by the machines as
magnetising current from the system.
• The stator overheating does not occur as quickly as rotor overheating.
Fig. 10 Loss of excitation relay characteristic
Rotor Protection
Department of Electrical and Electronics Engineering
(c) Protection against Rotor Overheating because of Unbalanced Three-phase Stator Currents
Fig. 11 Protection against unbalanced stator currents
• The overcurrent relay used in the negative phase sequence protection
has a long operating time
• A typical time range of the relay is 0.2 to 2000 s.
• It has a typical construction with a special electromagnet.
• It has shaded pole construction with a Mu-metal shunt.
• The negative sequence filter gives an output proportional to I2.
• It actuates an alarm as well as the time-current relay which has a very
inverse characteristic.
• The alarm unit also starts a timer which is adjustable from 8% to 40% of
negative sequence component.
• The timer makes a delay in the alarm to prevent the alarm from
sounding unnecessarily on unbalanced loads of short duration.
Miscellaneous
Department of Electrical and Electronics Engineering
A. Overvoltage Protection-
• Overvoltage may be caused by a defective voltage regulator or it may occur due to sudden loss of
electrical load on generators.
• Overvoltage relays are provided with hydro and gas-turbine sets.
• Overvoltage relays are not commonly used with turbo-alternators.
B. Overspeed Protection-
• A turbo-generator is provided with a mechanical overspeed device.
• The speed governor normally controls its speed.
• It is designed to prevent any speed rise even with a 100 per cent load rejection.
• An emergency centrifugal overspeed device is also incorporated to trip emergency steam valves
when the speed exceeds 110 percent.
Miscellaneous
Department of Electrical and Electronics Engineering
C. Protection against Motoring-
• When the steam supply is cut off, the generator runs as a motor.
• The steam turbine gets overheated because insufficient steam passes through the turbine to carry
away the heat generated by windage loss.
• Therefore, a protective relay is required for the protection of the steam turbine.
• Generally, the relay operates when power output falls below 3%.
• A sensitive reverse power relay is available which has an operating setting of about 0.5% of the
generator’s output.
D. Protection against Vibration and Distortion of Rotor-
• Vibration is caused by overheating of the rotor or some mechanical failure or abnormality.
Miscellaneous
Department of Electrical and Electronics Engineering
E. Bearing Overheating Protection-
• Temperature of the bearing is detected by inserting a temperature sensing device in a hole in the
bearing.
• For large machines where lubricating oil is circulated through the bearing, an oil flow device is
used to detect the failure of oil cooling equipment.
F. Protection against Auxiliary Failure-
• The power plant auxiliaries are very important for the running of the generating sets.
• High grade protective equipment is employed for their reliable operation.
• For large generating sets, protection against loss of vacuum and loss of boiler pressure are
provided. Such failures are due to the failure of the associated auxiliaries.
Miscellaneous
Department of Electrical and Electronics Engineering
G. Protection against Voltage Regulator Failure-
• Modern quick response automatic voltage regulators are very complex.
• They are subject to component failures.
• Suitable protective devices are provided against their failure.
• A definite time dc overcurrent relay is provided which operates when there is overcurrent in the
rotor circuit for a period longer than a prescribed limit.
• In such a situation, the excitation is switched to a predetermined value for manual control.
Miscellaneous
Department of Electrical and Electronics Engineering
H. Protection against Pole Slipping
• In case of system disturbances after the operation of circuit breaker or when heavy load is thrown or
switched on, the generator rotor may oscillate.
• Consequently, variations in current, voltage and power factor may take place.
• Such oscillations may disappear in a few seconds.
• Therefore, in such a situation, tripping is not desired.
• In some cases, angular displacement of the rotor exceeds the stability limit and the rotor slips a pole
pitch.
• If the disturbance is over, the generator may regain synchronism.
• If it does not, it should be tripped.
Miscellaneous
Department of Electrical and Electronics Engineering
I. Field Suppression
• When a fault occurs in the generator winding, the circuit breaker trips and the generator is
isolated from the system.
• However, the generator still continues to feed the fault as long as the excitation is maintained, and
the damage increases.
• Therefore, it is desirable to suppress the field as quickly as possible.
J. Back-up Protection
• Overcurrent relays are used as back-up protection.
• As the synchronous impedance of a turbo-generator is more than 100%, the fault current,
• may fall below the normal load current.
• Therefore, standard time-overcurrent relays cannot be employed for back-up protection.
• A voltage controlled overcurrent can be employed for such a purpose.
• A better alternative is to use reactance or impedance type distance relays.
Thank you

More Related Content

PPTX
Generator and Transformer Protection (PART 2)
PPTX
Rankine cycle
PDF
Electromagnetic Protection (PART I)
PPTX
Protection of transformer
PPTX
STATIC AND DIGITAL RELAYS
PPTX
Switchgear and protection 3
PDF
Motor protection principles
PPTX
Generator Protection
Generator and Transformer Protection (PART 2)
Rankine cycle
Electromagnetic Protection (PART I)
Protection of transformer
STATIC AND DIGITAL RELAYS
Switchgear and protection 3
Motor protection principles
Generator Protection

What's hot (20)

PDF
Alternator protection
PPTX
Protection Of Generator
PPTX
Electrical HT/LT Motor protection
PPTX
Protection & switchgear
PPTX
FEEDER AND BUS BAR PROTECTION
PDF
Generator Protection By - Er Rahul Sharma
PPTX
Generator protection
PPTX
Automatic Generation Control
PDF
Generator protection
PPTX
Switchgear and protection 1
PDF
Motor Protection
PDF
Protection of transmission lines (distance)
PPTX
transformer protection
PPTX
Buchholz relay
PPT
Substation Training presentation
PPT
transmission-line-protection.ppt
PDF
Power system protection topic 1
PPTX
surge arrester
PPTX
Protection & switchgear
PPTX
Power Transformer Protection
Alternator protection
Protection Of Generator
Electrical HT/LT Motor protection
Protection & switchgear
FEEDER AND BUS BAR PROTECTION
Generator Protection By - Er Rahul Sharma
Generator protection
Automatic Generation Control
Generator protection
Switchgear and protection 1
Motor Protection
Protection of transmission lines (distance)
transformer protection
Buchholz relay
Substation Training presentation
transmission-line-protection.ppt
Power system protection topic 1
surge arrester
Protection & switchgear
Power Transformer Protection
Ad

Similar to Generator and Transformer Protection (PART 1) (20)

PPT
UNIT III PROTECTION OF GENERATOR OCTOBER 2 (2).ppt
PPTX
Switch Gear & Protection (2170908) (Generator Protection)
PPT
Generator protection by a. kato
PPTX
R&I - GENERATOR electrical protection.pptx
PDF
Advanced Generator Ground Fault Protections
PPT
Generator protection by bhushan kumbhalkar
PPT
442639191-Generator-Protection-ppt.ppt
PDF
Generator protection LEC 2
PPT
Power System Protection lectures 5_5.ppt
PPTX
Rotor earth fault protection of electric generator
PPTX
Equipment protection
PPTX
Protection & switchgear
DOCX
New Microsoft Word Document
PPTX
class on Protection.pptx
PPTX
presentation_generator_protection.pptx
PPTX
PROTECTION OF GENERATOR ITS GOOD TO SEE..pptx
PPTX
GENERATOR PROTECTION PART 2 FOR TGE BEST KNOWLEDGE.pptx
PPTX
PROTEIN CALCIAM OF THE EQUIPMENT TO THE PROPOSAL PLANT.111.pptx
PPTX
LECTURE 1 - GENERATOR PROTECTION.pptx
PPTX
MTA GENERATOR PROTECTION .PPT.pptx
UNIT III PROTECTION OF GENERATOR OCTOBER 2 (2).ppt
Switch Gear & Protection (2170908) (Generator Protection)
Generator protection by a. kato
R&I - GENERATOR electrical protection.pptx
Advanced Generator Ground Fault Protections
Generator protection by bhushan kumbhalkar
442639191-Generator-Protection-ppt.ppt
Generator protection LEC 2
Power System Protection lectures 5_5.ppt
Rotor earth fault protection of electric generator
Equipment protection
Protection & switchgear
New Microsoft Word Document
class on Protection.pptx
presentation_generator_protection.pptx
PROTECTION OF GENERATOR ITS GOOD TO SEE..pptx
GENERATOR PROTECTION PART 2 FOR TGE BEST KNOWLEDGE.pptx
PROTEIN CALCIAM OF THE EQUIPMENT TO THE PROPOSAL PLANT.111.pptx
LECTURE 1 - GENERATOR PROTECTION.pptx
MTA GENERATOR PROTECTION .PPT.pptx
Ad

More from Dr. Rohit Babu (17)

PPTX
EDS Unit 6.pptx
PPTX
EDS Unit 5.pptx
PPTX
EDS Unit 1 (Part 1).pptx
PPTX
EDS Unit 3 (Part 1).pptx
PPTX
EDS Unit 4 (Protection and Coordination).pptx
PPTX
EDS Unit 3 (Part 2).pptx
PPTX
HVDC Syllabus.pptx
PPTX
Electrical Distribution Systems: Syllabus
PPTX
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PPTX
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PPTX
FEEDER AND BUS BAR PROTECTION
PPTX
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PPTX
Electromagnetic Protection (PART III)
PDF
Electromagnetic Protection (PART 2)
PDF
SGP Syllabus as per JNTU-K
PPTX
Circuit Breaker: Part 2
PPTX
Circuit Breaker
EDS Unit 6.pptx
EDS Unit 5.pptx
EDS Unit 1 (Part 1).pptx
EDS Unit 3 (Part 1).pptx
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 3 (Part 2).pptx
HVDC Syllabus.pptx
Electrical Distribution Systems: Syllabus
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
FEEDER AND BUS BAR PROTECTION
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
Electromagnetic Protection (PART III)
Electromagnetic Protection (PART 2)
SGP Syllabus as per JNTU-K
Circuit Breaker: Part 2
Circuit Breaker

Recently uploaded (20)

PPTX
wireless networks, mobile computing.pptx
PPTX
Measurement Uncertainty and Measurement System analysis
PPTX
Management Information system : MIS-e-Business Systems.pptx
PPTX
Feature types and data preprocessing steps
PDF
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PDF
LOW POWER CLASS AB SI POWER AMPLIFIER FOR WIRELESS MEDICAL SENSOR NETWORK
PDF
MLpara ingenieira CIVIL, meca Y AMBIENTAL
PDF
Prof. Dr. KAYIHURA A. SILAS MUNYANEZA, PhD..pdf
PDF
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PPTX
PRASUNET_20240614003_231416_0000[1].pptx
PPTX
ASME PCC-02 TRAINING -DESKTOP-NLE5HNP.pptx
PPTX
Amdahl’s law is explained in the above power point presentations
PPTX
CN_Unite_1 AI&DS ENGGERING SPPU PUNE UNIVERSITY
PDF
Computer System Architecture 3rd Edition-M Morris Mano.pdf
PPTX
CONTRACTS IN CONSTRUCTION PROJECTS: TYPES
PPTX
Information Storage and Retrieval Techniques Unit III
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
20250617 - IR - Global Guide for HR - 51 pages.pdf
PPTX
Chapter 2 -Technology and Enginerring Materials + Composites.pptx
wireless networks, mobile computing.pptx
Measurement Uncertainty and Measurement System analysis
Management Information system : MIS-e-Business Systems.pptx
Feature types and data preprocessing steps
UEFA_Embodied_Carbon_Emissions_Football_Infrastructure.pdf
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
LOW POWER CLASS AB SI POWER AMPLIFIER FOR WIRELESS MEDICAL SENSOR NETWORK
MLpara ingenieira CIVIL, meca Y AMBIENTAL
Prof. Dr. KAYIHURA A. SILAS MUNYANEZA, PhD..pdf
August 2025 - Top 10 Read Articles in Network Security & Its Applications
PRASUNET_20240614003_231416_0000[1].pptx
ASME PCC-02 TRAINING -DESKTOP-NLE5HNP.pptx
Amdahl’s law is explained in the above power point presentations
CN_Unite_1 AI&DS ENGGERING SPPU PUNE UNIVERSITY
Computer System Architecture 3rd Edition-M Morris Mano.pdf
CONTRACTS IN CONSTRUCTION PROJECTS: TYPES
Information Storage and Retrieval Techniques Unit III
Exploratory_Data_Analysis_Fundamentals.pdf
20250617 - IR - Global Guide for HR - 51 pages.pdf
Chapter 2 -Technology and Enginerring Materials + Composites.pptx

Generator and Transformer Protection (PART 1)

  • 1. LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY Jonnada, Andhra Pradesh- 535005 UNIT -III GENERATOR AND TRANSFORMER PROTECTION (PART I) Presented by, Dr. Rohit Babu, Associate Professor Department of Electrical and Electronics Engineering
  • 2. Syllabus Department of Electrical and Electronics Engineering Part 1. Generator Protection ―Protection of generators against stator faults ―Rotor faults and abnormal conditions ―Restricted earth fault and inter turn fault protection ―Numerical examples Part 2. Transformer Protection ―Percentage differential protection ―Design of CT’s ratio ―Buchholz relay protection ―Numerical examples
  • 3. Part 1. Generator Protection Department of Electrical and Electronics Engineering ―Protection of generators against stator faults ―Rotor faults and abnormal conditions ―Restricted earth fault and inter turn fault protection ―Numerical examples
  • 4. Generator Protection Department of Electrical and Electronics Engineering A modern generating set is generally provided with the following protective schemes. (i) Stator protection (a) Percentage differential protection (b) Protection against stator inter-turn faults (c) Stator-overheating protection (ii) Rotor protection (a) Field ground-fault protection (b) Loss of excitation protection (c) Protection against rotor overheating because of unbalanced three-phase stator currents (iii) Miscellaneous (a) Overvoltage protection (b) Overspeed protection (c) Protection against motoring (d) Protection against vibration (e) Bearing-overheating protection (f) Protection against auxiliary failure (g) Protection against voltage regulator failure
  • 5. Stator Protection Department of Electrical and Electronics Engineering (A) Percentage Differential Protection Fig. 1 Percentage differential protection for external fault condition (instantaneous current directions shown for external fault condition) • It is used for the protection of generators above 1 MW. • It protects against winding faults, i.e. phase to phase and phase to ground faults. • This is also called biased differential protection or longitudinal differential protection. • The polarity of the secondary voltage of CTs at a particular moment for an external fault has been shown in the figure. • In the operating coil, the current sent by the upper CT is cancelled by the current sent by the lower CT and the relay does not operate.
  • 6. Stator Protection Department of Electrical and Electronics Engineering Fig. 2 Percentage differential protection of generator (instantaneous current directions shown for internal fault condition) • For an internal fault, the polarity of the secondary voltage of the upper CT is reversed, as shown in Fig. 2. • The operating coil carries the sum of the currents sent by the upper CT and the lower CT and it operates and trips the circuit breaker. • The percentage differential protection does not respond to external faults and overloads. • It provides complete protection against phase to phase faults. • It provides protection against ground faults to about 80 to 85 per cent of the generator windings.
  • 7. Stator Protection Department of Electrical and Electronics Engineering • It does not provide protection to 100 per cent of the winding because it is influenced by the magnitude of the earth fault current which depends upon the method of neutral grounding. • Due to the difference in the magnetizing currents of the upper and the lower CTs, the current through the operating coil will not be zero even under normal loading conditions or during external fault conditions. • In case of stator faults, the tripping of circuit breaker to isolate the faulty generator is not sufficient to prevent further damage as the generator will still continue to supply power to the fault until its field excitation is suppressed.
  • 8. Stator Protection Department of Electrical and Electronics Engineering Restricted earth-fault protection by differential system Fig. 3 Percentage of unprotected winding against phase to ground fault • When the neutral is solidly grounded, it is possible to provide protection to complete winding of the generator against ground faults. • However, the neutral is grounded through resistance to limit ground fault currents. • With resistance grounding it is not possible to protect the complete winding against ground faults. • The percentage of winding protected depends on the value of the neutral grounding resistor and the relay setting. • The usual practice is to protect 80 to 85% of the generator winding against ground fault. The remaining 15-20% from neutral end is left unprotected. • In Fig. 3 for phase to ground fault, it can be seen that the relay setting for the differential protection is determined by the value of the neutral grounding resistor and the percentage of winding to be protected.
  • 9. Stator Protection Department of Electrical and Electronics Engineering In Fig. 3, let p% of the winding from the neutral remains unprotected. Then (100 – p)% of the winding is protected. The ground fault current If is given by where, V is the line to neutral voltage and Rn is the neutral grounding resistance. For the operation of the relay, the fault current must be greater than the relay pick-up current.
  • 10. Stator Protection Department of Electrical and Electronics Engineering Percentage differential protection for a Y-connected generator with only four leads brought out • When the neutral connection is made within the generator and only the neutral terminal is brought out, the percentage differential protection can be provided, as shown in Fig. 4. Fig. 4 Percentage differential protection for Y connected generator with only four leads brought out • This scheme protects the generator winding only against ground faults. • It does not protect it against phase faults. Generator-transformer unit protection
  • 11. Stator Protection Department of Electrical and Electronics Engineering (B) Protection against Stator Interturn Faults • Longitudinal percentage differential protection does not detect stator interturn faults. • A transverse percentage differential protection, as shown in Fig. 5 is employed for the protection of the generator against stator interturn faults. Fig. 5 Transverse percentage differential protection for multi- winding generators
  • 12. Stator Protection Department of Electrical and Electronics Engineering • A faster and more sensitive split-phase protection as shown in Fig. 6 can be employed. • In this scheme, a single CT having double primary is used. • No bias is necessary because a common CT is employed so that errors due to CT differences do not occur. Fig. 6 Split-phase protection of generator using double primary CTs
  • 13. Stator Protection Department of Electrical and Electronics Engineering Interturn protection based on zero-sequence component • If generators do not have access to parallel windings, a method based on zero-sequence voltage measurement can be employed for the protection against stator interturn faults. • This type of scheme will also be applicable to single winding generators having multi-turn per phase per slot to protect against interturn faults. • Figure 7 shows the schematic diagram of interturn protection by zero-sequence • voltage measurement across the machine. Fig. 7 Interturn protection of generator using zero-sequence voltage
  • 14. Stator Protection Department of Electrical and Electronics Engineering (C) Stator-overheating Protection Modern generators employ two methods to detect overheating both being used in large generators (above 2 MW). First Method, the inlet and outlet temperatures of the cooling medium which may be hydrogen/ water are compared for detecting overheating. Second Method, the temperature sensing elements are embedded in the stator slots to sense the temperature.
  • 15. Stator Protection Department of Electrical and Electronics Engineering Fig. 8 Stator-overheating protection • When the temperature exceeds a certain preset maximum temperature limit, the relay sounds an alarm. • The scheme employs a temperature detector unit, relay and Wheatstone-bridge for the purpose. • The temperature sensing elements may either be thermistors, thermocouples or resistance temperature indicators. • They are embedded in the stator slots at different locations. • These elements are connected to a multi-way selector switch which checks each one in turn for a period long enough to operate an alarm relay.
  • 16. Rotor Protection Department of Electrical and Electronics Engineering (A) Field Ground-fault Protection As the field circuit is operated ungrounded, a single ground fault does not affect the operation of the generator or cause any damage. • A dc voltage is impressed between the field circuit and earth through a polarised moving iron relay. • It is not necessary to trip the machine when a single field earth fault occurs. • Usually an alarm is sounded. Then immediate steps are taken to transfer the load from the faulty generator and to shut it down as quickly. • In case of brushless machines, the main field circuit is not accessible. Fig. 9 Earth fault protection • If there is a partial field failure due to short-circuiting of turns in the main field winding, it is detected by the increase in level of the field current. • A severe fault or short-circuiting of the diode is detected by a relay monitoring the current in the exciter control circuit.
  • 17. Rotor Protection Department of Electrical and Electronics Engineering (B) Loss of Excitation • When the excitation of a generator is lost, it speeds up slightly and operates as an induction generator. • Round-rotor generators do not have damper windings and hence they are not suitable for such an operation. • The rotor is overheated quickly due to heavy induced currents in the rotor iron. • The rotors of salient pole generators are not overheated because they have damper windings which carry induced currents. • The stators of both salient and non-salient pole generators are overheated due to wattless current drawn by the machines as magnetising current from the system. • The stator overheating does not occur as quickly as rotor overheating. Fig. 10 Loss of excitation relay characteristic
  • 18. Rotor Protection Department of Electrical and Electronics Engineering (c) Protection against Rotor Overheating because of Unbalanced Three-phase Stator Currents Fig. 11 Protection against unbalanced stator currents • The overcurrent relay used in the negative phase sequence protection has a long operating time • A typical time range of the relay is 0.2 to 2000 s. • It has a typical construction with a special electromagnet. • It has shaded pole construction with a Mu-metal shunt. • The negative sequence filter gives an output proportional to I2. • It actuates an alarm as well as the time-current relay which has a very inverse characteristic. • The alarm unit also starts a timer which is adjustable from 8% to 40% of negative sequence component. • The timer makes a delay in the alarm to prevent the alarm from sounding unnecessarily on unbalanced loads of short duration.
  • 19. Miscellaneous Department of Electrical and Electronics Engineering A. Overvoltage Protection- • Overvoltage may be caused by a defective voltage regulator or it may occur due to sudden loss of electrical load on generators. • Overvoltage relays are provided with hydro and gas-turbine sets. • Overvoltage relays are not commonly used with turbo-alternators. B. Overspeed Protection- • A turbo-generator is provided with a mechanical overspeed device. • The speed governor normally controls its speed. • It is designed to prevent any speed rise even with a 100 per cent load rejection. • An emergency centrifugal overspeed device is also incorporated to trip emergency steam valves when the speed exceeds 110 percent.
  • 20. Miscellaneous Department of Electrical and Electronics Engineering C. Protection against Motoring- • When the steam supply is cut off, the generator runs as a motor. • The steam turbine gets overheated because insufficient steam passes through the turbine to carry away the heat generated by windage loss. • Therefore, a protective relay is required for the protection of the steam turbine. • Generally, the relay operates when power output falls below 3%. • A sensitive reverse power relay is available which has an operating setting of about 0.5% of the generator’s output. D. Protection against Vibration and Distortion of Rotor- • Vibration is caused by overheating of the rotor or some mechanical failure or abnormality.
  • 21. Miscellaneous Department of Electrical and Electronics Engineering E. Bearing Overheating Protection- • Temperature of the bearing is detected by inserting a temperature sensing device in a hole in the bearing. • For large machines where lubricating oil is circulated through the bearing, an oil flow device is used to detect the failure of oil cooling equipment. F. Protection against Auxiliary Failure- • The power plant auxiliaries are very important for the running of the generating sets. • High grade protective equipment is employed for their reliable operation. • For large generating sets, protection against loss of vacuum and loss of boiler pressure are provided. Such failures are due to the failure of the associated auxiliaries.
  • 22. Miscellaneous Department of Electrical and Electronics Engineering G. Protection against Voltage Regulator Failure- • Modern quick response automatic voltage regulators are very complex. • They are subject to component failures. • Suitable protective devices are provided against their failure. • A definite time dc overcurrent relay is provided which operates when there is overcurrent in the rotor circuit for a period longer than a prescribed limit. • In such a situation, the excitation is switched to a predetermined value for manual control.
  • 23. Miscellaneous Department of Electrical and Electronics Engineering H. Protection against Pole Slipping • In case of system disturbances after the operation of circuit breaker or when heavy load is thrown or switched on, the generator rotor may oscillate. • Consequently, variations in current, voltage and power factor may take place. • Such oscillations may disappear in a few seconds. • Therefore, in such a situation, tripping is not desired. • In some cases, angular displacement of the rotor exceeds the stability limit and the rotor slips a pole pitch. • If the disturbance is over, the generator may regain synchronism. • If it does not, it should be tripped.
  • 24. Miscellaneous Department of Electrical and Electronics Engineering I. Field Suppression • When a fault occurs in the generator winding, the circuit breaker trips and the generator is isolated from the system. • However, the generator still continues to feed the fault as long as the excitation is maintained, and the damage increases. • Therefore, it is desirable to suppress the field as quickly as possible. J. Back-up Protection • Overcurrent relays are used as back-up protection. • As the synchronous impedance of a turbo-generator is more than 100%, the fault current, • may fall below the normal load current. • Therefore, standard time-overcurrent relays cannot be employed for back-up protection. • A voltage controlled overcurrent can be employed for such a purpose. • A better alternative is to use reactance or impedance type distance relays.