Air conditioningAir conditioning
requirements in hospitalsrequirements in hospitals
Presented by
Heena kousar
Introduction
 Microbiological transmission in healthcare
setting is inevitably a very potential risk. The
main routes are droplets, contact, common
vehicle and air borne transmissions. Infection
control for patients, healthcare providers and
visitors is of paramount importance in the
healthcare process in medical facilities. Proper air
conditioning of medical care facilities is helpful
in prevention and treatment of diseases.
 Continual advances in medicine and technology
have led to the development in medical care
processes as many new complex diagnostic and
therapeutic procedures have been added to the
armamentarium of medical care.
 There is a need for constant evaluation of air
conditioning needs of the hospitals and medical
facilities for better patient care.
What is air conditioning?
 Air conditioning (often referred to as aircon, AC or
A/C) is the process of altering the properties of air
(primarily temperature and humidity) to more favorable
conditions.
 More generally, air conditioning can refer to any form of
technological cooling, heating, ventilation, or disinfection
that modifies the condition of air.
DefinitionDefinition
Air conditioning is defined as a processAir conditioning is defined as a process
which cools(or heats), cleans, freshenswhich cools(or heats), cleans, freshens
air and controls its moisture contentair and controls its moisture content
simultaneously.simultaneously.
Types of air conditioning in hospital
 HVAC designer will recommend different types of air
conditioning systems for different applications. most
commonly using are:
1)Window air conditioner: is the most commonly used air
conditioner for single rooms. In this air conditioner all the
components, namely the compressor, condenser,
expansion valve or coil, evaporator and cooling coil are
enclosed in a single box. This unit is fitted in a opening
made in the wall of the room, or more commonly a
window sill.
2) Split Air Conditioner:
 The split air conditioner comprises of two parts: the
outdoor unit and the indoor unit. The outdoor unit, fitted
outside the room, houses components like the
compressor, condenser and expansion valve. The indoor
unit comprises the evaporator or cooling coil and the
cooling fan. For this unit you don’t have to make any slot
in the wall of the room. Further, present day split units
have aesthetic appeal and do not take up as much space as
a window unit. A split air conditioner can be used to cool
one or two rooms.
3) Packaged Air Conditioner
 An HVAC designer will suggest this type of air
conditioner which is used to cool more than two rooms or
a larger space at home or office.
 There are two possible arrangements with the package
unit. In the first one, all the components, namely the
compressor, condenser (which can be air cooled or water
cooled), expansion valve and evaporator are housed in a
single box.
 The cooled air is thrown by the high capacity blower, and
it flows through the ducts laid through various rooms. In
the second arrangement, the compressor and condenser
are housed in one casing. The compressed gas passes
through individual units, comprised of the expansion
valve and cooling coil, located in various rooms.
Air condition requirement in hospitals
4) Central Air Conditioning System
 Central air conditioning is used for cooling big buildings,
houses, offices, entire hotels, gyms, movie theaters,
factories etc.
 If the whole building is to be air conditioned, HVAC
engineers find that putting individual units in each of the
rooms is very expensive making this a better option.
 A central air conditioning system is comprised of a huge
compressor that has the capacity to produce hundreds of
tons of air conditioning.
 Cooling big halls, malls, huge spaces, galleries etc is
usually only feasible with central conditioning units.
Air condition requirement in hospitals
Chilled Water Applied Systems
 A chilled-water applied system uses chilled water to
transport heat energy between the airside, chillers and the
outdoors.
 These systems are more commonly found in large HVAC
installations, given their efficiency advantages.
 The components of the chiller (evaporator, compressor,
an air- or water-cooled condenser, and expansion device)
are often manufactured, assembled, and tested as a
complete package within the factory.
HEPA FILTERS
 High-efficiency particulate air or HEPA is a type of air
filter.
 The filter must satisfy certain standards of efficiency such
as those set by the United States Department of Energy
(DOE).
 To qualify as HEPA by US government standards, an air
filter must remove (from the air that passes through)
99.97% of particles that have a size of 0.3 micro metres
or larger.
 HEPA filters are critical in the prevention of the spread of
airborne bacterial and viral organisms and, therefore,
infection.
 Typically, medical-use HEPA filtration systems also
incorporate high-energy ultra-violet light units to kill off
the live bacteria and viruses trapped by the filter media.
 Some of the best-rated HEPA units have an efficiency
rating of 99.95%, which assures a very high level of
protection against airborne disease transmission.
Why do hospitals really require air
conditioning?
 Installing these units in hospitals provides a comfortable
environment to patients. Doctors and staff will also be able
to work more comfortably and concentrate on their duty in a
better manner.
 These days most modern hospitals are equipped with this
air conditioning. The technology is also utilized to provide
various therapies to patients.
 According to studies it has been proved that patients show
speedy recovery in controlled environment than in an
uncontrolled environment. For example, cardiac patients
may not be able to maintain adequate circulation to
facilitate standard heat loss. This is also a reason that
cardiac wards and rooms are equipped with air conditioning
units.
 Patients within head injuries, those subjected with brain
operations and those with poisoning may have high fever
in a hot environment due to trouble in the brain’s heat
regulatory system. The best thing to ensure recovery here
is to maintain cool and comfortable environment.
 Burn patients also require a warm environment with high
relative humidity. The room for severe burn patients must
possess temperature controls that can keep the level of
temperature should be 32 degree Celsius.
 The relative humidity should go up to 95 per cent, this is
where air conditioning is used as a clean room
application.
 Air conditioning is extremely important in the operation
theater. This helps in controlling the temperature,
humidity and sterile filtration.
 These units are also considered as a necessity for other
departments of hospitals such as delivery room,
radiology, recovery room, intensive care unit, CT, &
MRI.
 Air conditioning has helped in making the environment
of hospitals livable and extremely comfortable.
 This also facilitates in keeping the environment of the
hospital clean and hygienic. The patients will feel happy,
healthy and comfortable with an air conditioning installed
in hospitals.
Need for air conditioning of hospital
facilities
 Proper air conditioning is helpful in the prevention and
treatment of diseases. The factors determining the need for
air conditioning in hospital facilities are:
(a) The need to restrict air movement within and between
various departments.
(b) The specific requirements for ventilation and filtration to
dilute and remove contaminants in the form of airborne
microorganisms, viruses, odour, hazardous chemicals and
radioactive substances.
(c) Different types of temperature and humidity requirements
for various areas.
(d) Permit accurate control of environmental conditions.
(e) Control of air quality and air movement
Infection Sources and Control
Measures
 Bacterial Infection. Infectious bacteria are transported by
air. Droplet or infectious agents of 5 mm or less in size
can remain airborne indefinitely. It has been shown that
90 to 95 per cent effective filters remove 99.9 per cent of
all bacteria present in hospitals.
Viral Infection
 Epidemiological evidence and other studies indicate that
many of the air borne viruses that transmit infections are
sub- micron in size, thus there is no known method to
effectively eliminate 100 per cent of the viable particles.
HEPA filters and/or Ultra-Low Penetration (ULPA)
filters provide the greatest efficiency currently available.
Therefore, the isolation rooms with appropriate
ventilation pressure relationships are the primary means
used to prevent the spread of airborne viruses in the
hospital environment.
 Outdoor air in comparison to room air is virtually free of
bacteria and viruses.
 Infection control problems frequently involve a bacterial
or viral source within the hospital. Ventilation air dilutes
the viral and bacterial contamination within the hospital.
 Properly designed, constructed and maintained
ventilation systems preserve the correct pressure
relationship between functional areas; they remove
airborne infectious agents from hospital environment.
Indoor Air Quality in Hospitals
 Indoor air quality in
hospital is a complex multi-
faceted issue. Contaminants
come with dust, air and
visitors as well as originate
inside the hospital complex
and threaten the quality of
environment. Most
common contaminants are
microbes and organic
compounds.
 Ventilation and filtration
provides a means of
fighting contaminants by
diluting their concentration.
 Acceptable indoor air quality can be achieved by
following the fundamental principles:
 (a) Contaminant source control.
 (b) Proper ventilation.
 (c) Humidity management.
 (d) Adequate filtration.
 The temperature and humidity conditions in hospital
environment can inhibit or promote the growth of
bacteria and activate or deactivate viruses. Ventilation
systems are used to provide air virtually free of dust, dirt,
odour, chemicals and radioactive pollutants.
 Contamination can be dispersed into the air of the
hospital environment by one of the many routine
activities of normal patient care.
 Because of the dispersal of bacteria resulting from such
necessary activities, air-handling system should provide
air movement patterns to minimize the spread of
contamination.
 The sense of thermal comfort results from an interaction
between temperature, relative humidity, air movement,
clothing, activity levels and individual physiology.
 The temperature and relative humidity measurements are
indicators of thermal comfort. The medical care needs of
patients require thermal comfort provided by air
conditioning system.
Operating Room Air Conditioning
Requirements
 The primary task of the
ventilation system in an
operating room is to
provide an acceptable
indoor climate for
personnel and patients, to
remove odor, released
anesthetic gases and to
reduce the risk of infection
in the operating area. The
greatest amount of bacteria
found in operating rooms
comes from the surgical
team and is a result of their
activity during surgery.
 During an operation most members of the surgical team
are in the vicinity of the operating table, creating the
undesirable situation of concentrating contaminants in
this highly sensitive area.
 Studies of operating room air distribution systems and
various air delivery systems indicate that these are the
most effective methods for air movement pattern in
operation theatres for limiting the concentration of
contaminants to an acceptable level.
The total heat production per hour caused by the staff,
operation room lighting and equipment may be about 2
KW or 1750 Kcal/h.
Operating Room Ventilation
 To maintain oxygenation for 10 persons in the operating
room, a volume of about 28 m3 of air will be required per
hour. How much outside air is required for the dilution of
odour will depend on the nature and intensity of odor
producing sources.
 It is indicated by some studies that air supplied at 0.24
m3 per minute per person is the critical level of odour
suppression.
 A ventilation rate of 10 air changes per hour reduces the
level of any contamination present in the air by about 99
per cent.
 15 to 20 air changes per hour should be sufficient for
comfort, to ensure pressurization in the operation room
and to maintain considerable control of airborne micro
organisms in an operation room of the size of about 40 sq
meter, if an average surgical team is involved.
 Another study shows that bacteriological contamination
of the air is markedly reduced by the use of ultra clean air
filters.
 Airborne contamination in operating room is mainly
derived from the personnel in the operation theatre and
their activities.
 The number of
individuals present,
ventilation and airflow
implements the bacterial
count in operation
theatre.
 Proper design and
ventilation of operation
theatre is the most
important means of
controlling airborne
infection in operation
theatre.
 Empty Operation Theatre
The empty operation theatre should have:
a) Less than 35 colony-forming units (CFU) of bacteria/m3
of air.
b) Less than one CFU of Clostridium perfingens or
Staphylococcus aureus in 30 m3.
c) During operation less than 180 CFU/ m3 of air using ultra
clean laminar flow in the theatre.
d) Less than 20 CFU/ m 3 at the periphery of the enclosure
and less than 10 CFU/ m3 at the centre.
 Direction of Air Flow
 Direction of airflow should be from clean to less clean
areas.
 Airflow rate of 0.28 -0.47 m /sec is desirable across an
open door to prevent back flow into cleaner area.
 In Ultra clean air enclosure, the airflow should not be less
than 0.2 m/sec .
 Humidity Control
 One of the aspects of humidity is that bacteriological
microorganisms ride on dust particles whose attract
ability to one another is favored by low relative humidity
resulting in increased static energy.
 Low relative humidity is reported to be suitable for
Klebsiella pneumoniae activity.
 High humidity in the hospital enhances the danger of
growth of Pseudomonas aeruginosa.
 Humidity in operation room is believed to contribute to
the prevention of dehydration of exposed tissue.
 To minimize the explosion risk , the relative humidity
required is 40-65 per cent.
Air conditioning other zones
1) Patient rooms: air conditioning of bed rooms in our warm
humid climate desirable not only for medical reason but
also to keep out noise , pollution from mainly cars &
buses, trucks.
 It is more important in dry areas where dust storm
common in the summer months.
 When central air-conditioning system used for pt rooms
avoid ducted air supply and return to the rooms in order
to eliminate chance of cross infection. and to odours
through the common ducts for the same reason, packaged
air conditioner feeding a group of rooms through a ducted
supply must also be avoided.
Use of individual fan coil units in each room
connected to a central chilled water plant and room
thermo stats for indipendent temp control is ideal
solution .
2) ICU :These units serves seriously ill pts from post
operative to coronary pts.
 There needs of clean filtered air without the possibility
of contamination from adjoining areas and variable
range of temp capability from 24 to 27 °c are important .
3) LABOUR & DELIVERY : The procedures for
normal child birth are considered non invasive and
rooms are controlled similar to pts rooms .
Invasive procedures such as a caesarian section are
performed in an OT .
4)MRI &CT SCAN ROOMS :
Normal comforts AC and
ventilation is required. How
ever the special needs of the
equipment manufacturer
must be checked out and at
times a precision AC may
be called for to handle the
high heat release of
computer equipment and
cryogens used to cool the
magnet .
5) AUTOPSY ROOM :
comforts conditions are
maintained with a 100%
fresh air system with full
exhaust . Due to heavy
bacterial contamination
and odor, autopsy room
require special attention
for exhausting all air above
the roof of the hospital . To
prevent spread of
contamination to adjoining
areas ,the autopsy room
must be maintained at –ve
pressure.
6)PHYSICAL
THERAPHY DEPT :
The normal AC cooling
load of the electro
therapy section is
affected by the short
wave diathermy ,
infrared and ultraviolet
equipment used in this
area .
The exercise section
requires no special
treatment and temp and
humidity should be
within the comfort zone.
7)CSSD : comfort Ac is optional but ventilation and exhaust
air system are essential . Used and contaminated utensils,
instruments and equipment are brought to this unit for
cleaning and sterilization prior to reuse. the dept usually
consists of cleaning area ,a sterilizing area and a storage
area where supplies are kept until requested. the storage
area should preferably be air conditioned on 24 hour basis
in case the remaining CSSD dept in merely ventilated.
8) KITCHEN: This is generally
ventilated, meaning that fresh
filtered air is distributed to the
entire area and stale air exhausted
through the hoods kept over the
cooking area where the heat is
concentrated.
 cooler and freezer rooms are
located close to the kitchen area
and the refrigeration equipment
and for these should preferably be
water cooled for the best cooling
efficiency.
 the dietitian’s office is often
located within or adjoining the
kitchen . It is usually completely
enclosed to ensure privacy and
noise reduction and air
conditioned for comfort.
9) LAUNDRY: this is
another area which is
generally ventilated with
fresh filtered air and
exhausted through hoods
placed over the heat
generating laundry
equipment such as
washers ,flat work
ironers and tumblers .
special advice must be
taken from the
equipment manufacturers
and all exhaust should
terminate above the roof
or where it’ll not be are
nuisance to neighbors
10) PHARMACIES AND DRUG STORAGE AREAS:
Are another unit within hospitals and other healthcare
organizations than require air conditioning in order to
carry 'temperature dependent' drugs.
Inadequate temperature control here either means that
medication would not function as required or the hospital
would simply not be able to stock some emergency
treatments.
Air condition requirement in hospitals
Disadvantages of air conditioners
 Air conditioners use a lot of electricity.
 financial disadvantage.
 spending too much time in an air-conditioned
environment can contribute to health problems such as
asthma, tightness in the chest and other respiratory
ailments.
 Low temperatures will lead to a sharp contraction of
blood vessels, poor blood flow and joint pain.
 the temperature difference between indoor and outdoor,
people often will feel hot and cold, this will result in the
body conditioning system disorders.
Conclusion
 The benefit to the clientele, prompt recovery, restoration
of quality of life, disability limitation, prevention of
hospital acquired infection, enhancing the productivity of
the equipment and staff cannot be quantified in to the
exact financial terms. A single case of hospital acquired
infection requires at least double the duration of stay in
hospital, which leads the antibiotic cost to manifold, leads
to increase in the cost due to management of antecedent
complications and loss of productive man-hours, justifies
the case for air conditioning. The hospitals/medical
institution deals with life of the clientele, the lives saved
by providing appropriate therapeutic, diagnostic and
treatment facilities justify that the investment for air
conditioning is a small cost for better quality care to the
patients.
REFERANCE
 http://www.brilliantstore.com/portable_air_conditioners.h
tml http://www.brilliantstore.com/window_air_conditione
rs.
 html http://www.brilliantstore.com/mini_split_air_conditi
oners...
 www.wikipidia.com.
THANK YOU

More Related Content

PPTX
Operation theater DEMC
Akeem Dot Dot
 
PDF
Hospital hvac design salah ramadan
Eng Salah Ramadan
 
PPTX
Medical gases.pptx
MahmoudAbdElmoneam4
 
DOC
Operating theatre suite planning and design
Mahmoud Shaqria
 
PPTX
Hospital training
Riku Rik
 
PDF
Modular ot presentation
mayur_32
 
PPSX
Modular Operation Theatre by WORKSPACE
Modular Operation theatre
 
Operation theater DEMC
Akeem Dot Dot
 
Hospital hvac design salah ramadan
Eng Salah Ramadan
 
Medical gases.pptx
MahmoudAbdElmoneam4
 
Operating theatre suite planning and design
Mahmoud Shaqria
 
Hospital training
Riku Rik
 
Modular ot presentation
mayur_32
 
Modular Operation Theatre by WORKSPACE
Modular Operation theatre
 

What's hot (20)

PDF
Air Conditioning For Hospital
Loter Malingka Rindonggon
 
PPT
Medical gas supply system
Dr.Ashok Khandelwal
 
PPTX
HVAC System
Self employed
 
PPTX
Ventilation system
Noorule Inie Osman
 
PPTX
Operation theatre services
Nc Das
 
PPT
Medical gas supply. (central supply)
BKMC
 
DOC
Intensive care unit design
Mahmoud Shaqria
 
PPTX
Air Conditioning & Hvac Systems
GAURAV. H .TANDON
 
PDF
Fire safety in hospitals
Komal Gupta
 
PPTX
ICU AND IT'S TYPES
Anjali Makhijani
 
PPT
Equipments used in mechanical ventilation
Rishikesh Kalal
 
PPTX
Heat ventilation and air conditioning (hvac)
Satish kumar Hiremath
 
PDF
literature study for EMERGENCY DEPARTMENT in hospital
Balaji Ar
 
PPTX
IPD Hospital
Abshir Abdirizak
 
PPT
Hospital-Design.ppt
RohitKapoor113
 
PPTX
Air conditioning system
Noorule Inie Osman
 
PPT
Hvac Basics
Alvin Bene
 
PPTX
Report on hospital design
Bee Key Verma
 
Air Conditioning For Hospital
Loter Malingka Rindonggon
 
Medical gas supply system
Dr.Ashok Khandelwal
 
HVAC System
Self employed
 
Ventilation system
Noorule Inie Osman
 
Operation theatre services
Nc Das
 
Medical gas supply. (central supply)
BKMC
 
Intensive care unit design
Mahmoud Shaqria
 
Air Conditioning & Hvac Systems
GAURAV. H .TANDON
 
Fire safety in hospitals
Komal Gupta
 
ICU AND IT'S TYPES
Anjali Makhijani
 
Equipments used in mechanical ventilation
Rishikesh Kalal
 
Heat ventilation and air conditioning (hvac)
Satish kumar Hiremath
 
literature study for EMERGENCY DEPARTMENT in hospital
Balaji Ar
 
IPD Hospital
Abshir Abdirizak
 
Hospital-Design.ppt
RohitKapoor113
 
Air conditioning system
Noorule Inie Osman
 
Hvac Basics
Alvin Bene
 
Report on hospital design
Bee Key Verma
 
Ad

Similar to Air condition requirement in hospitals (20)

PDF
AIR CONDITIONING REQUIREMENTS IN HOSPITALS PPT.pdf
AbhishekRai980934
 
PDF
Case study of Heat ventilation and air conditioning ppt
merinblessan
 
PDF
alturascontractors.com-HVAC Design for Healthcare Facilities.pdf
Ahmad Affan
 
PPTX
This is for the pharmaceutical IndustryHVAC SYSTEM.pptx
dpwande
 
PPTX
Air based hazard
Mukesh Patil
 
PPT
HVAC designooooooooooooooooooooooooo.ppt
sanjeevkhanal2
 
PPTX
Alternate ventilation in hospitals
ajayhvaidya
 
PPTX
Lecture 6 & 7 Aseptic Pharmaceutical Manufacturing.pptx
Sardar Arifuzzaman
 
PPTX
Presentation on HVAC
Avishek Sen Sarma
 
PDF
AIR CONDITIONING PRINCIPLES & CONCEPTS.pdf
Abhishek Koduvayur Venkitaraman
 
PDF
FundamentalofcGMPforPharmaceuticalHVACSystem.pdf
mohamedibrahim219956
 
PDF
What is hvac
Sahil Mansuri
 
PPT
ngshvacsystem-150722103725-lva1-app6892.ppt
Viknesh Selvaratnam
 
PPT
HVAC System for Pharmaceuticals Industry
navakadhammavaro
 
PPT
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
Namdeo Shinde
 
PPT
presentation for heat ventilation and ac systems.ppt
pokemonking2303
 
PPTX
Risk with hvac system and mitigation plan
Akshay Mehta
 
PDF
HVAC design for health care facilities is all about providing a safer environ...
Varun Mithran
 
PDF
CHAP 4 HVAC.pdf
MuhammadFarisBinNord
 
PPT
Hvac
Mahmood Asif
 
AIR CONDITIONING REQUIREMENTS IN HOSPITALS PPT.pdf
AbhishekRai980934
 
Case study of Heat ventilation and air conditioning ppt
merinblessan
 
alturascontractors.com-HVAC Design for Healthcare Facilities.pdf
Ahmad Affan
 
This is for the pharmaceutical IndustryHVAC SYSTEM.pptx
dpwande
 
Air based hazard
Mukesh Patil
 
HVAC designooooooooooooooooooooooooo.ppt
sanjeevkhanal2
 
Alternate ventilation in hospitals
ajayhvaidya
 
Lecture 6 & 7 Aseptic Pharmaceutical Manufacturing.pptx
Sardar Arifuzzaman
 
Presentation on HVAC
Avishek Sen Sarma
 
AIR CONDITIONING PRINCIPLES & CONCEPTS.pdf
Abhishek Koduvayur Venkitaraman
 
FundamentalofcGMPforPharmaceuticalHVACSystem.pdf
mohamedibrahim219956
 
What is hvac
Sahil Mansuri
 
ngshvacsystem-150722103725-lva1-app6892.ppt
Viknesh Selvaratnam
 
HVAC System for Pharmaceuticals Industry
navakadhammavaro
 
HVAC SYSTEM IN PHARMACEUTICAL INDUSTRY
Namdeo Shinde
 
presentation for heat ventilation and ac systems.ppt
pokemonking2303
 
Risk with hvac system and mitigation plan
Akshay Mehta
 
HVAC design for health care facilities is all about providing a safer environ...
Varun Mithran
 
CHAP 4 HVAC.pdf
MuhammadFarisBinNord
 
Ad

Recently uploaded (20)

PPTX
Oro-antral Communications and its management strategies
Srinjoy Chatterjee
 
PPT
9. Applied Biomechanics (fracture fixation)etc.ppt
Bolan University of Medical and Health Sciences ,Quetta
 
DOCX
Paediatrics Question Papers – III MBBS (Part II), RUHS Main Exam 2025-2016
Shivankan Kakkar
 
PPTX
HALITOSIS presentation for Ear, Nose and throat.pptx
stefanumerah1
 
PPTX
Describe Thyroid storm & it’s Pharmacotherapy Drug Interaction: Pyridoxine + ...
Dr. Deepa Singh Rana
 
PPTX
Birth Preparedness & Complication Readiness
Pratiksha Rai
 
PPTX
QUIZ Questions Emergency department.pptx
smiti24dml064
 
PPTX
Models of screening of Adrenergic Blocking Drugs.pptx
Dr Fatima Rani
 
PPTX
12. Neurosurgery (part. 2) SURGERY OF VERTEBRAL COLUMN, SPINAL CORD AND PERIP...
Bolan University of Medical and Health Sciences ,Quetta
 
PPTX
Digital Dichoptic Therapy for Amblyopia.
Gamal Saif
 
PPTX
Anaesthesia Machine - Safety Features and Recent Advances - Dr.Vaidyanathan R
VAIDYANATHAN R
 
PPTX
CANSA Womens Health UTERINE focus Top Cancers slidedeck Aug 2025
CANSA The Cancer Association of South Africa
 
PPTX
Anatomy of eyelids basic anatomy covered along with abnormalities of eyelids
SummyBhatnagar1
 
DOCX
RUHS II MBBS Pharmacology Paper-I with Answer Key | 26 July 2025 (New Scheme)
Shivankan Kakkar
 
PPTX
Models for screening of Local Anaesthetics.pptx
AntoRajiv1
 
PPTX
13.Anesthesia and its all types.....pptx
Bolan University of Medical and Health Sciences ,Quetta
 
PDF
Digital literacy note level 6 perioperative theatre technician
mercylindah47
 
PPTX
HANAU ARTICULATORS AND CLASSIFICATION.pptx
Priya Singaravelu
 
PPTX
Pharmacotherapy of Myasthenia Gravis- Dr. Anurag Sharma (1).pptx
Anurag Sharma
 
PPTX
Surgical management of colorectal cancer.pptx
Oladele Situ
 
Oro-antral Communications and its management strategies
Srinjoy Chatterjee
 
9. Applied Biomechanics (fracture fixation)etc.ppt
Bolan University of Medical and Health Sciences ,Quetta
 
Paediatrics Question Papers – III MBBS (Part II), RUHS Main Exam 2025-2016
Shivankan Kakkar
 
HALITOSIS presentation for Ear, Nose and throat.pptx
stefanumerah1
 
Describe Thyroid storm & it’s Pharmacotherapy Drug Interaction: Pyridoxine + ...
Dr. Deepa Singh Rana
 
Birth Preparedness & Complication Readiness
Pratiksha Rai
 
QUIZ Questions Emergency department.pptx
smiti24dml064
 
Models of screening of Adrenergic Blocking Drugs.pptx
Dr Fatima Rani
 
12. Neurosurgery (part. 2) SURGERY OF VERTEBRAL COLUMN, SPINAL CORD AND PERIP...
Bolan University of Medical and Health Sciences ,Quetta
 
Digital Dichoptic Therapy for Amblyopia.
Gamal Saif
 
Anaesthesia Machine - Safety Features and Recent Advances - Dr.Vaidyanathan R
VAIDYANATHAN R
 
CANSA Womens Health UTERINE focus Top Cancers slidedeck Aug 2025
CANSA The Cancer Association of South Africa
 
Anatomy of eyelids basic anatomy covered along with abnormalities of eyelids
SummyBhatnagar1
 
RUHS II MBBS Pharmacology Paper-I with Answer Key | 26 July 2025 (New Scheme)
Shivankan Kakkar
 
Models for screening of Local Anaesthetics.pptx
AntoRajiv1
 
13.Anesthesia and its all types.....pptx
Bolan University of Medical and Health Sciences ,Quetta
 
Digital literacy note level 6 perioperative theatre technician
mercylindah47
 
HANAU ARTICULATORS AND CLASSIFICATION.pptx
Priya Singaravelu
 
Pharmacotherapy of Myasthenia Gravis- Dr. Anurag Sharma (1).pptx
Anurag Sharma
 
Surgical management of colorectal cancer.pptx
Oladele Situ
 

Air condition requirement in hospitals

  • 1. Air conditioningAir conditioning requirements in hospitalsrequirements in hospitals Presented by Heena kousar
  • 2. Introduction  Microbiological transmission in healthcare setting is inevitably a very potential risk. The main routes are droplets, contact, common vehicle and air borne transmissions. Infection control for patients, healthcare providers and visitors is of paramount importance in the healthcare process in medical facilities. Proper air conditioning of medical care facilities is helpful in prevention and treatment of diseases.
  • 3.  Continual advances in medicine and technology have led to the development in medical care processes as many new complex diagnostic and therapeutic procedures have been added to the armamentarium of medical care.  There is a need for constant evaluation of air conditioning needs of the hospitals and medical facilities for better patient care.
  • 4. What is air conditioning?  Air conditioning (often referred to as aircon, AC or A/C) is the process of altering the properties of air (primarily temperature and humidity) to more favorable conditions.  More generally, air conditioning can refer to any form of technological cooling, heating, ventilation, or disinfection that modifies the condition of air.
  • 5. DefinitionDefinition Air conditioning is defined as a processAir conditioning is defined as a process which cools(or heats), cleans, freshenswhich cools(or heats), cleans, freshens air and controls its moisture contentair and controls its moisture content simultaneously.simultaneously.
  • 6. Types of air conditioning in hospital  HVAC designer will recommend different types of air conditioning systems for different applications. most commonly using are: 1)Window air conditioner: is the most commonly used air conditioner for single rooms. In this air conditioner all the components, namely the compressor, condenser, expansion valve or coil, evaporator and cooling coil are enclosed in a single box. This unit is fitted in a opening made in the wall of the room, or more commonly a window sill.
  • 7. 2) Split Air Conditioner:  The split air conditioner comprises of two parts: the outdoor unit and the indoor unit. The outdoor unit, fitted outside the room, houses components like the compressor, condenser and expansion valve. The indoor unit comprises the evaporator or cooling coil and the cooling fan. For this unit you don’t have to make any slot in the wall of the room. Further, present day split units have aesthetic appeal and do not take up as much space as a window unit. A split air conditioner can be used to cool one or two rooms.
  • 8. 3) Packaged Air Conditioner  An HVAC designer will suggest this type of air conditioner which is used to cool more than two rooms or a larger space at home or office.  There are two possible arrangements with the package unit. In the first one, all the components, namely the compressor, condenser (which can be air cooled or water cooled), expansion valve and evaporator are housed in a single box.  The cooled air is thrown by the high capacity blower, and it flows through the ducts laid through various rooms. In the second arrangement, the compressor and condenser are housed in one casing. The compressed gas passes through individual units, comprised of the expansion valve and cooling coil, located in various rooms.
  • 10. 4) Central Air Conditioning System  Central air conditioning is used for cooling big buildings, houses, offices, entire hotels, gyms, movie theaters, factories etc.  If the whole building is to be air conditioned, HVAC engineers find that putting individual units in each of the rooms is very expensive making this a better option.  A central air conditioning system is comprised of a huge compressor that has the capacity to produce hundreds of tons of air conditioning.  Cooling big halls, malls, huge spaces, galleries etc is usually only feasible with central conditioning units.
  • 12. Chilled Water Applied Systems  A chilled-water applied system uses chilled water to transport heat energy between the airside, chillers and the outdoors.  These systems are more commonly found in large HVAC installations, given their efficiency advantages.  The components of the chiller (evaporator, compressor, an air- or water-cooled condenser, and expansion device) are often manufactured, assembled, and tested as a complete package within the factory.
  • 13. HEPA FILTERS  High-efficiency particulate air or HEPA is a type of air filter.  The filter must satisfy certain standards of efficiency such as those set by the United States Department of Energy (DOE).  To qualify as HEPA by US government standards, an air filter must remove (from the air that passes through) 99.97% of particles that have a size of 0.3 micro metres or larger.
  • 14.  HEPA filters are critical in the prevention of the spread of airborne bacterial and viral organisms and, therefore, infection.  Typically, medical-use HEPA filtration systems also incorporate high-energy ultra-violet light units to kill off the live bacteria and viruses trapped by the filter media.  Some of the best-rated HEPA units have an efficiency rating of 99.95%, which assures a very high level of protection against airborne disease transmission.
  • 15. Why do hospitals really require air conditioning?  Installing these units in hospitals provides a comfortable environment to patients. Doctors and staff will also be able to work more comfortably and concentrate on their duty in a better manner.  These days most modern hospitals are equipped with this air conditioning. The technology is also utilized to provide various therapies to patients.  According to studies it has been proved that patients show speedy recovery in controlled environment than in an uncontrolled environment. For example, cardiac patients may not be able to maintain adequate circulation to facilitate standard heat loss. This is also a reason that cardiac wards and rooms are equipped with air conditioning units.
  • 16.  Patients within head injuries, those subjected with brain operations and those with poisoning may have high fever in a hot environment due to trouble in the brain’s heat regulatory system. The best thing to ensure recovery here is to maintain cool and comfortable environment.  Burn patients also require a warm environment with high relative humidity. The room for severe burn patients must possess temperature controls that can keep the level of temperature should be 32 degree Celsius.  The relative humidity should go up to 95 per cent, this is where air conditioning is used as a clean room application.
  • 17.  Air conditioning is extremely important in the operation theater. This helps in controlling the temperature, humidity and sterile filtration.  These units are also considered as a necessity for other departments of hospitals such as delivery room, radiology, recovery room, intensive care unit, CT, & MRI.  Air conditioning has helped in making the environment of hospitals livable and extremely comfortable.  This also facilitates in keeping the environment of the hospital clean and hygienic. The patients will feel happy, healthy and comfortable with an air conditioning installed in hospitals.
  • 18. Need for air conditioning of hospital facilities  Proper air conditioning is helpful in the prevention and treatment of diseases. The factors determining the need for air conditioning in hospital facilities are: (a) The need to restrict air movement within and between various departments. (b) The specific requirements for ventilation and filtration to dilute and remove contaminants in the form of airborne microorganisms, viruses, odour, hazardous chemicals and radioactive substances. (c) Different types of temperature and humidity requirements for various areas. (d) Permit accurate control of environmental conditions. (e) Control of air quality and air movement
  • 19. Infection Sources and Control Measures  Bacterial Infection. Infectious bacteria are transported by air. Droplet or infectious agents of 5 mm or less in size can remain airborne indefinitely. It has been shown that 90 to 95 per cent effective filters remove 99.9 per cent of all bacteria present in hospitals.
  • 20. Viral Infection  Epidemiological evidence and other studies indicate that many of the air borne viruses that transmit infections are sub- micron in size, thus there is no known method to effectively eliminate 100 per cent of the viable particles. HEPA filters and/or Ultra-Low Penetration (ULPA) filters provide the greatest efficiency currently available. Therefore, the isolation rooms with appropriate ventilation pressure relationships are the primary means used to prevent the spread of airborne viruses in the hospital environment.
  • 21.  Outdoor air in comparison to room air is virtually free of bacteria and viruses.  Infection control problems frequently involve a bacterial or viral source within the hospital. Ventilation air dilutes the viral and bacterial contamination within the hospital.  Properly designed, constructed and maintained ventilation systems preserve the correct pressure relationship between functional areas; they remove airborne infectious agents from hospital environment.
  • 22. Indoor Air Quality in Hospitals  Indoor air quality in hospital is a complex multi- faceted issue. Contaminants come with dust, air and visitors as well as originate inside the hospital complex and threaten the quality of environment. Most common contaminants are microbes and organic compounds.  Ventilation and filtration provides a means of fighting contaminants by diluting their concentration.
  • 23.  Acceptable indoor air quality can be achieved by following the fundamental principles:  (a) Contaminant source control.  (b) Proper ventilation.  (c) Humidity management.  (d) Adequate filtration.  The temperature and humidity conditions in hospital environment can inhibit or promote the growth of bacteria and activate or deactivate viruses. Ventilation systems are used to provide air virtually free of dust, dirt, odour, chemicals and radioactive pollutants.
  • 24.  Contamination can be dispersed into the air of the hospital environment by one of the many routine activities of normal patient care.  Because of the dispersal of bacteria resulting from such necessary activities, air-handling system should provide air movement patterns to minimize the spread of contamination.  The sense of thermal comfort results from an interaction between temperature, relative humidity, air movement, clothing, activity levels and individual physiology.  The temperature and relative humidity measurements are indicators of thermal comfort. The medical care needs of patients require thermal comfort provided by air conditioning system.
  • 25. Operating Room Air Conditioning Requirements  The primary task of the ventilation system in an operating room is to provide an acceptable indoor climate for personnel and patients, to remove odor, released anesthetic gases and to reduce the risk of infection in the operating area. The greatest amount of bacteria found in operating rooms comes from the surgical team and is a result of their activity during surgery.
  • 26.  During an operation most members of the surgical team are in the vicinity of the operating table, creating the undesirable situation of concentrating contaminants in this highly sensitive area.  Studies of operating room air distribution systems and various air delivery systems indicate that these are the most effective methods for air movement pattern in operation theatres for limiting the concentration of contaminants to an acceptable level.
  • 27. The total heat production per hour caused by the staff, operation room lighting and equipment may be about 2 KW or 1750 Kcal/h.
  • 28. Operating Room Ventilation  To maintain oxygenation for 10 persons in the operating room, a volume of about 28 m3 of air will be required per hour. How much outside air is required for the dilution of odour will depend on the nature and intensity of odor producing sources.  It is indicated by some studies that air supplied at 0.24 m3 per minute per person is the critical level of odour suppression.  A ventilation rate of 10 air changes per hour reduces the level of any contamination present in the air by about 99 per cent.
  • 29.  15 to 20 air changes per hour should be sufficient for comfort, to ensure pressurization in the operation room and to maintain considerable control of airborne micro organisms in an operation room of the size of about 40 sq meter, if an average surgical team is involved.  Another study shows that bacteriological contamination of the air is markedly reduced by the use of ultra clean air filters.  Airborne contamination in operating room is mainly derived from the personnel in the operation theatre and their activities.
  • 30.  The number of individuals present, ventilation and airflow implements the bacterial count in operation theatre.  Proper design and ventilation of operation theatre is the most important means of controlling airborne infection in operation theatre.
  • 31.  Empty Operation Theatre The empty operation theatre should have: a) Less than 35 colony-forming units (CFU) of bacteria/m3 of air. b) Less than one CFU of Clostridium perfingens or Staphylococcus aureus in 30 m3. c) During operation less than 180 CFU/ m3 of air using ultra clean laminar flow in the theatre. d) Less than 20 CFU/ m 3 at the periphery of the enclosure and less than 10 CFU/ m3 at the centre.
  • 32.  Direction of Air Flow  Direction of airflow should be from clean to less clean areas.  Airflow rate of 0.28 -0.47 m /sec is desirable across an open door to prevent back flow into cleaner area.  In Ultra clean air enclosure, the airflow should not be less than 0.2 m/sec .
  • 33.  Humidity Control  One of the aspects of humidity is that bacteriological microorganisms ride on dust particles whose attract ability to one another is favored by low relative humidity resulting in increased static energy.  Low relative humidity is reported to be suitable for Klebsiella pneumoniae activity.  High humidity in the hospital enhances the danger of growth of Pseudomonas aeruginosa.
  • 34.  Humidity in operation room is believed to contribute to the prevention of dehydration of exposed tissue.  To minimize the explosion risk , the relative humidity required is 40-65 per cent.
  • 35. Air conditioning other zones 1) Patient rooms: air conditioning of bed rooms in our warm humid climate desirable not only for medical reason but also to keep out noise , pollution from mainly cars & buses, trucks.  It is more important in dry areas where dust storm common in the summer months.  When central air-conditioning system used for pt rooms avoid ducted air supply and return to the rooms in order to eliminate chance of cross infection. and to odours through the common ducts for the same reason, packaged air conditioner feeding a group of rooms through a ducted supply must also be avoided.
  • 36. Use of individual fan coil units in each room connected to a central chilled water plant and room thermo stats for indipendent temp control is ideal solution .
  • 37. 2) ICU :These units serves seriously ill pts from post operative to coronary pts.  There needs of clean filtered air without the possibility of contamination from adjoining areas and variable range of temp capability from 24 to 27 °c are important .
  • 38. 3) LABOUR & DELIVERY : The procedures for normal child birth are considered non invasive and rooms are controlled similar to pts rooms . Invasive procedures such as a caesarian section are performed in an OT .
  • 39. 4)MRI &CT SCAN ROOMS : Normal comforts AC and ventilation is required. How ever the special needs of the equipment manufacturer must be checked out and at times a precision AC may be called for to handle the high heat release of computer equipment and cryogens used to cool the magnet .
  • 40. 5) AUTOPSY ROOM : comforts conditions are maintained with a 100% fresh air system with full exhaust . Due to heavy bacterial contamination and odor, autopsy room require special attention for exhausting all air above the roof of the hospital . To prevent spread of contamination to adjoining areas ,the autopsy room must be maintained at –ve pressure.
  • 41. 6)PHYSICAL THERAPHY DEPT : The normal AC cooling load of the electro therapy section is affected by the short wave diathermy , infrared and ultraviolet equipment used in this area . The exercise section requires no special treatment and temp and humidity should be within the comfort zone.
  • 42. 7)CSSD : comfort Ac is optional but ventilation and exhaust air system are essential . Used and contaminated utensils, instruments and equipment are brought to this unit for cleaning and sterilization prior to reuse. the dept usually consists of cleaning area ,a sterilizing area and a storage area where supplies are kept until requested. the storage area should preferably be air conditioned on 24 hour basis in case the remaining CSSD dept in merely ventilated.
  • 43. 8) KITCHEN: This is generally ventilated, meaning that fresh filtered air is distributed to the entire area and stale air exhausted through the hoods kept over the cooking area where the heat is concentrated.  cooler and freezer rooms are located close to the kitchen area and the refrigeration equipment and for these should preferably be water cooled for the best cooling efficiency.  the dietitian’s office is often located within or adjoining the kitchen . It is usually completely enclosed to ensure privacy and noise reduction and air conditioned for comfort.
  • 44. 9) LAUNDRY: this is another area which is generally ventilated with fresh filtered air and exhausted through hoods placed over the heat generating laundry equipment such as washers ,flat work ironers and tumblers . special advice must be taken from the equipment manufacturers and all exhaust should terminate above the roof or where it’ll not be are nuisance to neighbors
  • 45. 10) PHARMACIES AND DRUG STORAGE AREAS: Are another unit within hospitals and other healthcare organizations than require air conditioning in order to carry 'temperature dependent' drugs. Inadequate temperature control here either means that medication would not function as required or the hospital would simply not be able to stock some emergency treatments.
  • 47. Disadvantages of air conditioners  Air conditioners use a lot of electricity.  financial disadvantage.  spending too much time in an air-conditioned environment can contribute to health problems such as asthma, tightness in the chest and other respiratory ailments.  Low temperatures will lead to a sharp contraction of blood vessels, poor blood flow and joint pain.  the temperature difference between indoor and outdoor, people often will feel hot and cold, this will result in the body conditioning system disorders.
  • 48. Conclusion  The benefit to the clientele, prompt recovery, restoration of quality of life, disability limitation, prevention of hospital acquired infection, enhancing the productivity of the equipment and staff cannot be quantified in to the exact financial terms. A single case of hospital acquired infection requires at least double the duration of stay in hospital, which leads the antibiotic cost to manifold, leads to increase in the cost due to management of antecedent complications and loss of productive man-hours, justifies the case for air conditioning. The hospitals/medical institution deals with life of the clientele, the lives saved by providing appropriate therapeutic, diagnostic and treatment facilities justify that the investment for air conditioning is a small cost for better quality care to the patients.