Basic Training: Control Valves
Elements for Defining, Sizing, and Selecting
Training Module 1
- 2 -
About Trimteck
Trimteck is a family-owned American company with over thirty years of experience in
engineering, manufacturing, and marketing flow control solutions and equipment for a
variety of industries. Our application engineers and certified representatives are
committed to personalized customer service and have an extensive line of products
and technologies to draw upon when designing and specifying a solution.
With a comprehensive line of Optimux control valves – and an array of actuators,
positioners, severe service trims, and other accessories – our engineers and
representatives can solve the most complex flow control problems quickly and
economically. Moreover, our organizational focus on implementing highly efficient
sourcing, engineering, manufacturing, assembly, and distribution processes enables us
to guarantee world-class quality, competitive pricing, and rapid delivery to
anywhere in the world.
Welcome to Trimteck.
- 3 -
A Comprehensive Portfolio of Control Valves
- 4 -
Agenda
I. Definition and Classification
II. Valve Selection
III. Sizing Basics
IV. Actuators
V. Positioners
VI. Common Accessories
- 5 -
What is a Control Valve?
valve noun ’valv
any of numerous mechanical devices by which the flow of liquid, gas, or loose material
in bulk may be started, stopped, or regulated by a movable part that opens, shuts, or
partially obstructs one or more ports or passageways
control valve noun kəәn′trōl ′valv
a power operated device which modifies the fluid flow rate in a process control system;
consists of a valve connected to an actuator mechanism that is capable of changing the
position of a flow controlling element in the valve in response to a signal from the
controlling system
Source: Merriam-Webster, ISA S75.05
- 6 -
How do we Classify Valves?
In order to simplify the selection and specification of a device with such a broad
definition, valves are traditionally classified according to one or more of the
following factors:
¡ General Service
¡ Special Service
¡ Severe Service
¡ Linear
¡ Rotary
By Function
1
By Application
2
By Motion
3
¡ On/Off
¡ Non-return
¡ Throttling
¡ Final Control
Element
- 7 -
1
Classifying Valves
according to
Function
- 8 -
Classifying by Function: On/Off Valves
Sometimes referred to as block valves, on/off valves are used to start or stop the
flow of the medium through the process
• Used in applications where media must
be diverted, in non-critical mixing, and in
safety management systems
• Most are hand-operated, although they
can be automated with the addition of an
actuator as seen in the photo of an
Optimux OpTE herein
• Common On/Off Valves Include:
• Gate
• Plug
• Ball
• Pressure Relief
• Tank Bottom
- 9 -
Classifying by Function: Non-Return Valves
Non-return valves allow fluid to flow in only the desired direction; any flow or
pressure in the opposite direction is mechanically restricted from occurring
• Used to prevent backflow of fluid that
could damage equipment or endanger
the process
• Particularly useful in protecting a pump
in liquid applications or a compressor in
gas applications
• Common Non-Return Valves Include:
• Check
Note: Trimteck does not produce or market check valves
- 10 -
Classifying by Function: Throttling
Throttling valves are used to regulate the flow, temperature, or pressure of a
service; can move to any position within the stroke, including full-open or full-
closed positions
• Can also act as on/off valves
• Many are hand-operated, but some are
equipped with actuators, which provide
greater thrust and positioning capability
as well as automatic control
• Common Throttling Valves Include:
• Pressure Regulators
• Control Valves
Note: Trimteck does not currently produce or market pressure regulators
- 11 -
Classifying by Function: Final Control Element
Final Control Element refers to the high-performance equipment needed to provide
the power and accuracy to control the flowing medium to specific service
conditions
• Part of the control loop, which consists of
at least two other elements besides the
control valves:
• Sensing element
• Controller
• Control valve makes a change
automatically, based on a signal from the
controller, and the sensor measures and
verifies the change
• Control valves are the most common final
control element
Transmitters:
Flow (FT)
Temperature (TT)
Pressure (PT)
- 12 -
2
Classifying Valves
according to
Service
- 13 -
Classifying by Application: General Service
General service valves are those designed for the majority of commonplace
applications with lower pressure ratings
• Lower ANSI Class: 150 - 600
• Moderate Temperature: -50 – 650°F
• Noncorrosive fluids
• Minimal Pressure Drops
• No cavitation
• No flashing
• Carbon or Stainless Steel
• Interchangeable and common to a wide
variety of applications
Optimux OpGL globe control valve in
general service at a pulp plant in Chile
- 14 -
Classifying by Application: Special Service
Special service valves are custom-engineered and designed for a single
application outside normal process applications
• High pressures
• Demanding temperatures
• Corrosive fluids
• Minimal to Moderate Pressure Drops
• Mild cavitation
• No flashing
• Special materials
• Unique applications
Optimux OpGL globe control valve designed to
withstand high temperatures and corrosion at a
tereftalic acid plant in Mexico
- 15 -
Classifying by Application: Severe Service
Severe service valves are fitted with special features to handle extreme
applications, such as high pressure drops that result in severe cavitation,
flashing, choking, or high noise levels
• High pressures
• Extreme temperatures
• Corrosive fluids
• Severe Pressure Drops
• Cavitation
• Flashing
• Choking
• Noise
• Custom-engineered trims aimed to
prevent or reduce effects of service
• Unique applications
Optimux OpGL globe control valve fitted with a
multi-stage trim designed to withstand high
pressure drop with oil, gas, saltwater and sand
media
- 16 -
3
Classifying Valves
according to
Motion
- 17 -
Classifying by Motion: Linear
Linear valves have a sliding-stem that pushes a closure element – any internal
device that is used to open, close, or regulate the flow – into an open or closed
position
• Simple design
• Easy maintenance
• Versatility in:
• Sizes
• Pressure classes
• Design options
• Common linear valve styles:
• Gate
• Globe
• Pinch
• Diaphragm
• Split-body
• Three-way
• Angle
Optimux OpGL linear globe control valve
- 18 -
Classifying by Motion: Rotary
Rotary valves use a closure element that rotates – through a quarter-turn or 45°
range – to open or block the flow
• Larger port compared to linear valves of
similar size
• Weigh less than linear size-for-size
• Limited in applications with pressure
drops
• Prone to cavitation and flashing
• Often less costly
Cross-section view of an eccentric rotary plug valve
- 19 -
Agenda
I. Definition and Classification
II. Valve Selection
III. Sizing Basics
IV. Actuators
V. Positioners
VI. Common Accessories
- 20 -
Valve Coefficients
The measurement commonly applied to valves is the valve coefficient (CV) - also
referred to as the flow coefficient - which is used to determine the valve size that
will best allow the valve to pass the required flow rate while providing control of
the process fluid
One CV is defined as one U.S. gallon (3.78 liters) of 60°F (16°C) water that flows
through an opening during 1 minute with a 1- psi (0.1-bar) pressure drop
CV = Flow coefficient
F = Flow rate (US GPM).
SG = Specific Gravity fluid (Water = 1).
ΔP = Pressure drop (psi).
- 21 -
Flow Characteristics
Each valve has a flow characteristic, which describes the relationship between the
valve coefficient (CV) and the valve stroke – as a valve opens, the flow
characteristic—which is inherent to the design of the selected valve—allows a
certain amount of flow through the valve at a particular percentage of the stroke,
which allows the valve to control the flow in a predictable manner
The three most common types of flow characteristics are equal percentage, linear,
and quick-open
Equal
Percentage
Linear Quick Open
- 22 -
Flow Characteristics Cont’d
Two rules of thumb for choosing the right flow characteristic:
1. If most of the pressure drop is taken through the valve and the upstream
pressure is constant, a linear characteristic will provide better control
2. If the piping and downstream equipment cause significant resistance to the
system, equal percentage will provide better control
Control Valve Pressure Drop Recommended Inherent Flow
Characteristic
Constant ΔP Linear
Decreasing ΔP with increasing load: ΔP at maximum
load >20% of minimum load ΔP
Linear
Decreasing ΔP with increasing load: ΔP at maximum
load <20% of minimum load ΔP
Equal Percentage
Increasing ΔP with increasing load: ΔP at maximum
load <200% of minimum load ΔP
Linear
Increasing ΔP with increasing load: ΔP at maximum
load >200% of minimum load ΔP
Quick Open
- 23 -
Rangeability
Rangeability is the ratio of maximum to minimum flow that can be acted upon by a
control valve after receiving a signal from a controller
High rangeability allows a valve to control flow from large to small flows
Rangeability is affected by three factors:
1. Valve geometry – inherent rangeability due to the design of the body and the
regulating element
2. Seat leakage – excessive seat leakage can cause instability as the valve lifts off
of the seat
3. Actuator – diaphragm actuators are seldom accurate at less than 5% of the valve
opening, whereas piston-cylinder actuators can provide control within 1% of valve
lift due to the presence of air in two chambers
- 24 -
Shutoff Requirements
Industry standards regarding the amount of permissible leakage of the process
fluid through a valve’s seat or seal – most applicable to throttling valves
Leakage Class
Designation
Maximum
Allowable
Leakage
Test Medium Test Pressure Test Procedure
Class I N/A N/A N/A No Test
Class II 0.5% of rated
capacity
Air or water at 50 -
125o F(10 - 52oC)
Lower of 45 - 60 psig or
maximum operating
differential
Lower of 45 - 60 psig or
maximum operating
differential
Class III 0.1% of rated
capacity
As above As above As above
Class IV 0.01% of rated
capacity
As above As above As above
Class V 0.0005 ml per
minute of water
per inch of port
diameter per psi
differential
Water at 50
to125oF (10 to
52oC)
Maximum service pressure
drop across valve plug not
to exceed ANSI body rating
Maximum service pressure
drop across valve plug not
to exceed ANSI body rating
Class VI Not to exceed
Class VI standard
per port diameter
Air or nitrogen at
50 to 125o F (10 to
52oC)
50 psig or max rated
differential pressure across
valve plug whichever is
lower
Actuator should be
adjusted to operating
conditions specified with
full normal closing thrust
applied to valve plug seal
- 25 -
Body End Connections
There are various end connections to allow a valve to be fitted to the system’s
piping, and in ideal circumstances, the valve’s end connections and materials
will match those of the system
Threaded
Flanged
Welded
- 26 -
Pressure Classes
A valve is designed to handle a range of pressures up to a certain limit, called the
valve’s pressure rating – the higher the rating, the thicker the walls of the valve
vessel to prevent rupture
Temperature effects: the higher the process temperature, the less pressure can be
handled by the body subassembly
Standard Classes: 150, 300, 600, 900,
1500, 2500, 4500
Sources: ANSI B16.34, Emerson Process Management
- 27 -
Face-to-Face
The dimension between one pipe mating surface of the valve to the surface on the
opposite end is called the face-to-face dimension This physical dimension is
always determined by the surface-to-surface measurement regardless of the type
of end connection (threaded, flanged, or welded)
Standard Valve Type Pressure Rating
ANSI/ISA S75.03 Globe valves 150 – 600 (valve is interchangeable
between Class 150, 300, and 600
ANSI/ISA S75.04 Flanged globe valves 125, 150, 250, 300, 600
ANSI/ISA S75.04 Flangeless globe valves 150, 300, 600
ANSI/ISA S75.08 Flanged clamp or pinch valves All classes
ANSI/ISA S75.12 Socketweld and threaded end globe valves 150, 300, 600, 900, 1500, 2500
ANSI/ISA S75.14 Buttweld globe valves 4500
ANSI/ISA S75.15 Buttweld globe valves 150, 300, 600, 900, 1500, 2500
ANSI/ISA B16.10 Iron (ferrous), gate, plug, globe valves All classes
BS 2080 Steel valves used in the petroleum, petrochemical, and
associated industries
All classes
MSS SP-67 Butterfly valves All classes
MSS SP-88 Diaphragm valves All classes
MSS SP-42 Stainless steel valves All classes
- 28 -
Body Materials
Common practice dictates that the end-user specify the body material, especially
with special or severe service valves
General service valves are specified with commonly found materials to match the
pipe material
¡ Carbon Steel
¡ Stainless Steel
¡ Chrome-moly
Standard Materials
¡ Hastelloy B and C
¡ Titanium
¡ Monel
¡ Bronze
Special Alloys
Control valve bodies are either cast, forged, or machined from bar stock, with
standard sand casting as the most commonplace method
Trimteck elects to use an advanced investment casting method as its
standard for control valve bodies between .5” and 4”
Investment casting offers the following benefits:
¡ Consistent and repetitive close tolerances
¡ Superior integrity and no porosity
¡ Fatigue performance equal to that of forgings
¡ Minimal need for machining
A Word on Investment Casting …
- 29 -
Trim Materials
Valve parts – body, bonnet, bonnet bolting, plug, ball, disk, wedge, and/or drainage
plug – exposed to pressure, process fluid, corrosion, and other effects of the
service are required by regulation to be manufactured from approved metals
In applications requiring elevated material hardness levels and resistance to
corrosion and abrasion, Trimteck has pioneered the use of CVD-5B
Trim Material Characteristics
- 30 -
Gaskets
A gasket is a malleable material, which can be either soft or hard, that is inserted
between two parts to prevent leakage between that joint
Type Gasket
Material
Max Temp
(oF/oC)
Min Temp
(oF/oC)
Max Pressure
(psi/bars)
Flat Virgin PTFE 350/175 -200/-130 6000 – 1000 psi
415 – 70 bar
Flat Reinforced
PTFE
450/230 -200/-130 6000 – 500 pis
415 – 35 bar
Flat CTFE 200/95 -423/-250 6000 – 500 psi
415 – 35 bar
Flat FEP 400/205 -423/-250 6000 – 500 psi
415 – 35 bar
Spiral-
wound
AFG 1500/815 -20/-30 6250 psi
430 bar
Spiral-
wound
316SS/
PTFE
350/176 -200/-130 6000 – 500 psi
415 – 35 bar
Spiral-
wound
316/
Graphite
1500/815 -423/-250 6250 psi
430 bar
Hollow O-
ring
Inconel
X-750
1500/815 -20/-30 15000 psi
1035 bar
Common Gasket Materials and Types
- 31 -
Agenda
I. Definition and Classification
II. Valve Selection
III. Sizing Basics
IV. Actuators
V. Positioners
VI. Common Accessories
- 32 -
Valve Sizing – Introduction
Valve sizing is based on the standard thermodynamic laws of fluid flow, and is
affected by the function of the valve plus the type and severity of the service
Control valves require a systematic method of determining the required flow, as
well as the size of the valve body, the body style, and materials that can
accommodate (or tolerate) the process conditions, the correct pressure rating,
and the proper installed flow characteristic
¡ Upstream Pressure
¡ Maximum and Minimum Temperatures
¡ Process Fluid
¡ Maximum, Average, and Minimum Flow Rates
¡ Vapor Pressure
¡ Pipeline Size, Schedule, and Material
¡ Maximum, Average, and Minimum Pressure Drop
¡ Specific Gravity of the Fluid
¡ Critical Pressure
Required Conditions
- 33 -
Valve Sizing – Electronic Data Sheet on Trimteck.com
- 34 -
Agenda
I. Definition and Classification
II. Valve Selection
III. Sizing Basics
IV. Actuators
V. Positioners
VI. Common Accessories
- 35 -
Actuators – Introduction
With most valves, some mechanical device or external system must be devised to
open or close the valve, or to change the position of the valve if it is to be used in
throttling service
Automatic control of valves requires an actuator, which is defined as any device
mounted on a valve that, in response to a signal, automatically moves the valve
to the required position using an outside power source
¡ Diaphragm
¡ Piston-Cylinder
¡ Rack and Pinion
¡ Rack and Gear
¡ Scotch Yoke
Pneumatic Actuators
¡ Electromechanical
¡ Electro Hydraulic
¡ Hydraulic
Non-pneumatic Actuators
- 36 -
Diaphragm Actuator
Advantages
• Relatively inexpensive to produce
• Suited to low-pressure ranges where limited
thrust is adequate
• Quick response
• Simple design
Disadvantages
• Height and weight
• Limited stroke
• Low thrust
• Pressure limitations on diaphragm
• Do not provide exceptional stiffness
• Not enough power to prevent “bathtub stopper
effect”
• Not field-reversible, laborious maintenance
Note: Trimteck does not manufacture or market diaphragm actuators
- 37 -
Piston-Cylinder Actuator (OpTK)
Advantages
• Higher thrust capability
• Compact and lightweight
• Faster stroking speed
• Longer stroke
• Greater stiffness prevents “bathtub stopper
effect”
• Better performance than diaphragm actuators,
with virtually no hysteresis, highly accurate
signal response, and excellent linearity
• Field-reversible
Disadvantages
• Some breakout torque required
• Positioner adds to cost and complexity
- 38 -
Diaphragm vs. Piston Cylinder Thrust Comparison
Diaphragm Piston Cylinder
60 inches2 25 inches2
30 psi Air Supply 80 psi Air Supply
750 lbs of thrust 2000 lbs of thrust
Conclusion: A far larger diaphragm actuator
would be needed to provide the same thrust
requirement as the piston cylinder actuator.
- 39 -
Rack and Pinion Actuator (OpRPA)
Advantages
• Suitable for both on/off and modulating control
applications
• Durability and long cycle life
• Cost effective
• Versatility of casing materials
• Field-reversible
Misconceptions
• Only for on/off service
• Meets requirements for modulating control valves
• Mechanical backlash
• Lash between racks and pinion is minimal, and
shaft to control element has no lash; clamping
device ensures no play between actuator pinion
and valve shaft
- 40 -
Rack and Gear Actuator (OpRGA)
Advantages
• Offset pistons eliminate internal cantilever loads
• Low friction
• Exceptional throttling control capability
• Rugged
• Field reversible
• High cycle-life
• Stainless steel standard
• High temperature
• Low pressure options
• High speed option
• Easy installation and maintenance
- 41 -
Heavy Duty Scotch Yoke Actuator (OpSY)
Advantages
• Ideal for heavy-duty applications, particularly for ESD
• Excellent option for large valves with high breakout
torque requirements
• Simple and infrequent maintenance requirements
• Known to achieve 1M cycles
• Pressure ranges from 40psi to 2500psi
• Torque from 1000in-lbs to 17,000in-lbs
- 42 -
Electromechanical (OpEM)
Advantages
• High degree of stability
• Constant thrust
• Extraordinary stiffness
• Fails in place upon loss of electric power
• Great solution for remote, solar-powered applications
Disadvantages
• Higher cost than pneumatic actuators
• Complexity
• Not recommended for flammable atmospheres
• Slower speeds
• Generate heat
- 43 -
Hydraulic and Electrohydraulic
Advantages
• Exceptionally stiff due to incompressibility of liquids
• Used in valves with low rangeability
• Fast stroking speeds
• Ideal for safety management systems
Disadvantages
• Expensive
• Large and bulky
• Complex
• Require specialized engineering
- 44 -
Actuator Performance Terminology
Dead band – the maximum amount of input that is
required to create a reversal in the movement of the
actuator stem
Frequency response – a response to a system or
device to a constant-amplitude sinusoidal input
signal
Hysteresis – a common term used to describe the
amount of position error that occurs when the same
position is approached from opposite directions
Independent linearity – the maximum amount that an
actuator stem will deviate from a true straight linear
line
Maximum flow capacity – the volume of air pressure
that can flow into an actuator during a particular
time period measured in SCFM
Open-loop gain – the ratio of the imbalance that
occurs when an instrument signal change is made
and the actuator stem is locked up
Repeatability – similar to hysteresis, although it
records the maximum variation of position when the
same position is approached from the same
direction
Resolution – the smallest change possible in a valve-
stem position
Response level – the maximum amount of input
change required to create a change in valve-stem
position (in one direction only)
Steady-state air consumption – applies to actuators
with positioners in which the positioner consumes a
certain amount of air pressure to maintain a required
position
Stiffness – the ability to hold a position despite process
forces
Stroking speed – the amount of time, in seconds, that
an actuator requires to move from the fully retracted
to the fully extended position
Supply-pressure effect – the change of the actuator
stem’s position for a 10-psi (0.7-bar) pressure
change in the supply
- 45 -
Agenda
I. Definition and Classification
II. Valve Selection
III. Sizing Basics
IV. Actuators
V. Positioners
VI. Common Accessories
- 46 -
Positioners – Introduction
A positioner is a device attached to an actuator that receives an electronic or
pneumatic signal from a controller and compares that signal to the actuator’s
position
If the signal and the actuator position differ, the positioner sends the necessary
power—usually through compressed air—to move the actuator until the correct
position is reached
Receive and convert pneumatic signal
3 to 15 psi
6 to 30 psi
Pneumatic Positioners
Receive and convert electronic signal
4 to 20 mA
10 to 50 mA
Digital Positioners
- 47 -
Pneumatic Positioner
Optimux HPP2500 Pneumatic Positioner
Technical Specifications
Type Pneumatic Electropneumatic
Input Signal 3 to 15 psi 4 to 20 mA
Supply
Pressure
30 to 150 psi
Hysteresis 1.0% F.S.
Repeatability 0.5% F.S.
Max Flow
Capacity
11 SCFM @ 60 psi
Air
Consumption
0.25 SCFM @ 60 psi 0.31 SCFM @ 60 psi
Pneumatic
Connections
¼-18 NPT female connection
¡ Characterized cam operation
¡ Easy adjustment and calibration
¡ Built-in dampers and gauge ports
¡ Corrosion-resistant
- 48 -
Intrinsically Safe Smart Digital Positioner
Optimux HPP4500 Digital Positioner
Technical Specifications
Type Digital
Input Signal 4 to 20 mA
Minimum Current
Signal
3.8 mA
Output
Characteristics
Linear, Equal Percentage, Quick Open,
configurable to 16 points
Power
requirements
8.5 V
Max Impedance 500Ω/20 mA Dc
Enclosure NEMA 4X, IEC IP66
Safety
Certification
Intrinsically Safe Ex ia IIC T6/T5
Digital
Communication
HART®
Digital Display LCD
Weight 3.3 lbs (1.5 kg)
¡ Auto Setup
¡ Flexibility in installation
¡ High reliability
¡ One model for multiple characterizations
- 49 -
Explosion Proof Smart Digital Positioner
Optimux HPP4000 Digital Positioner
Technical Specifications
Type Digital
Input Signal 4 to 20 mA
Feedback Signal 4 to 20 mA
Output
Characteristics
Linear, Equal Percentage, Quick Open,
configurable to 16 points
Max Impedance 500Ω/20 mA Dc
Enclosure NEMA 4X, IEC IP66
Safety
Certification
Explosion Proof Ex d IIC T6
Digital
Communication
HART®
Digital Display LCD
Air Consumption Below 2LPM @ 20 psi, 3 LPM @ 100 psi
Auxiliary Switches Dual limit switches
Repeatability +/- 0.3% F.S.
¡ Auto Calibration
¡ Variable orifices minimize hunting
¡ Corrosion resistant
¡ One model for multiple characterizations
- 50 -
Agenda
I. Definition and Classification
II. Valve Selection
III. Sizing Basics
IV. Actuators
V. Positioners
VI. Common Accessories
- 51 -
Common Accessories – Introduction
Some special actuation systems or actuators require fast stroking speeds, signal
conversions from one medium to another, position transmissions, etc.
In these applications, accessories are included with the actuator to help perform
these functions
Ideally, accessories are mounted directly onto the valve to ensure that the user is
aware of the location of the device
¡ Air Filter/Regulator
¡ Limit Switch
¡ Proximity Switch
¡ Position Transmitter
¡ Flow Booster
¡ Solenoid
¡ Safety Relief Valve
¡ Speed Control Valve
¡ Transducer
Common Accessories
- 52 -
Air Filter/Regulator
The Air Filter/Regulator is designed to screen the power supply medium of
impurities that may contaminate an actuation system, positioner, or other
accessory, as well as to regulate or limit the air supply to the actuator
Mounted between the source of power supply and the actuator or positioner
- 53 -
Limit Switch
When an electrical signal must be sent indicating an open, closed, or midstroke
position of an actuator or valve, an electrical switching device—called a limit
switch—is used
Limit switches are normally used to sound alarms or operate signal lights, electric
relays, or small solenoid valves
- 54 -
Proximity Switch
When a mechanical connection between the limit switch and the stem or shaft is
not desirable, a proximity switch is used.
A proximity switch is a limit switch that uses a magnetic sensor instead of a
mechanical arm
- 55 -
Position Transmitter
A position transmitter is a device that provides a continuous signal indicating the
position of the valve or actuator
Allows for signal indication, monitoring actuator performance, logging data, or
controlling associated instrumentation or equipment
- 56 -
Flow Booster
Flow boosters are used to increase the stroking speed of larger pneumatic
actuators
Because of their increased volumes, large actuators have difficulty making fast and
immediate stokes
- 57 -
Solenoid
A solenoid is an electrical control device that receives an electrical signal (usually
a 4- to 20-mA) and, in response, channels air supply directly to the actuator
- 58 -
Safety Relief Valve
Safety relief valves are designed to open to atmosphere when a particular pressure
is exceeded
When volume tanks are used or if high-pressure actuators must be used to handle
the service conditions, some local codes require the installation of safety relief
valves on these high-pressure vessels as protection against overpressurization
- 59 -
Speed Control Valve
Speed control valves are used to limit the stroking speed of an actuator by
restricting the amount of air flow to or from the actuator
These small valves can be mounted between the tubing and the actuator and are
available in sizes that match common tubing sizes
Thank you for your attention, for more information please
visit us at trimteck.com

Basic Training - Control Valves Training .pdf

  • 1.
    Basic Training: ControlValves Elements for Defining, Sizing, and Selecting Training Module 1
  • 2.
    - 2 - AboutTrimteck Trimteck is a family-owned American company with over thirty years of experience in engineering, manufacturing, and marketing flow control solutions and equipment for a variety of industries. Our application engineers and certified representatives are committed to personalized customer service and have an extensive line of products and technologies to draw upon when designing and specifying a solution. With a comprehensive line of Optimux control valves – and an array of actuators, positioners, severe service trims, and other accessories – our engineers and representatives can solve the most complex flow control problems quickly and economically. Moreover, our organizational focus on implementing highly efficient sourcing, engineering, manufacturing, assembly, and distribution processes enables us to guarantee world-class quality, competitive pricing, and rapid delivery to anywhere in the world. Welcome to Trimteck.
  • 3.
    - 3 - AComprehensive Portfolio of Control Valves
  • 4.
    - 4 - Agenda I.Definition and Classification II. Valve Selection III. Sizing Basics IV. Actuators V. Positioners VI. Common Accessories
  • 5.
    - 5 - Whatis a Control Valve? valve noun ’valv any of numerous mechanical devices by which the flow of liquid, gas, or loose material in bulk may be started, stopped, or regulated by a movable part that opens, shuts, or partially obstructs one or more ports or passageways control valve noun kəәn′trōl ′valv a power operated device which modifies the fluid flow rate in a process control system; consists of a valve connected to an actuator mechanism that is capable of changing the position of a flow controlling element in the valve in response to a signal from the controlling system Source: Merriam-Webster, ISA S75.05
  • 6.
    - 6 - Howdo we Classify Valves? In order to simplify the selection and specification of a device with such a broad definition, valves are traditionally classified according to one or more of the following factors: ¡ General Service ¡ Special Service ¡ Severe Service ¡ Linear ¡ Rotary By Function 1 By Application 2 By Motion 3 ¡ On/Off ¡ Non-return ¡ Throttling ¡ Final Control Element
  • 7.
    - 7 - 1 ClassifyingValves according to Function
  • 8.
    - 8 - Classifyingby Function: On/Off Valves Sometimes referred to as block valves, on/off valves are used to start or stop the flow of the medium through the process • Used in applications where media must be diverted, in non-critical mixing, and in safety management systems • Most are hand-operated, although they can be automated with the addition of an actuator as seen in the photo of an Optimux OpTE herein • Common On/Off Valves Include: • Gate • Plug • Ball • Pressure Relief • Tank Bottom
  • 9.
    - 9 - Classifyingby Function: Non-Return Valves Non-return valves allow fluid to flow in only the desired direction; any flow or pressure in the opposite direction is mechanically restricted from occurring • Used to prevent backflow of fluid that could damage equipment or endanger the process • Particularly useful in protecting a pump in liquid applications or a compressor in gas applications • Common Non-Return Valves Include: • Check Note: Trimteck does not produce or market check valves
  • 10.
    - 10 - Classifyingby Function: Throttling Throttling valves are used to regulate the flow, temperature, or pressure of a service; can move to any position within the stroke, including full-open or full- closed positions • Can also act as on/off valves • Many are hand-operated, but some are equipped with actuators, which provide greater thrust and positioning capability as well as automatic control • Common Throttling Valves Include: • Pressure Regulators • Control Valves Note: Trimteck does not currently produce or market pressure regulators
  • 11.
    - 11 - Classifyingby Function: Final Control Element Final Control Element refers to the high-performance equipment needed to provide the power and accuracy to control the flowing medium to specific service conditions • Part of the control loop, which consists of at least two other elements besides the control valves: • Sensing element • Controller • Control valve makes a change automatically, based on a signal from the controller, and the sensor measures and verifies the change • Control valves are the most common final control element Transmitters: Flow (FT) Temperature (TT) Pressure (PT)
  • 12.
    - 12 - 2 ClassifyingValves according to Service
  • 13.
    - 13 - Classifyingby Application: General Service General service valves are those designed for the majority of commonplace applications with lower pressure ratings • Lower ANSI Class: 150 - 600 • Moderate Temperature: -50 – 650°F • Noncorrosive fluids • Minimal Pressure Drops • No cavitation • No flashing • Carbon or Stainless Steel • Interchangeable and common to a wide variety of applications Optimux OpGL globe control valve in general service at a pulp plant in Chile
  • 14.
    - 14 - Classifyingby Application: Special Service Special service valves are custom-engineered and designed for a single application outside normal process applications • High pressures • Demanding temperatures • Corrosive fluids • Minimal to Moderate Pressure Drops • Mild cavitation • No flashing • Special materials • Unique applications Optimux OpGL globe control valve designed to withstand high temperatures and corrosion at a tereftalic acid plant in Mexico
  • 15.
    - 15 - Classifyingby Application: Severe Service Severe service valves are fitted with special features to handle extreme applications, such as high pressure drops that result in severe cavitation, flashing, choking, or high noise levels • High pressures • Extreme temperatures • Corrosive fluids • Severe Pressure Drops • Cavitation • Flashing • Choking • Noise • Custom-engineered trims aimed to prevent or reduce effects of service • Unique applications Optimux OpGL globe control valve fitted with a multi-stage trim designed to withstand high pressure drop with oil, gas, saltwater and sand media
  • 16.
    - 16 - 3 ClassifyingValves according to Motion
  • 17.
    - 17 - Classifyingby Motion: Linear Linear valves have a sliding-stem that pushes a closure element – any internal device that is used to open, close, or regulate the flow – into an open or closed position • Simple design • Easy maintenance • Versatility in: • Sizes • Pressure classes • Design options • Common linear valve styles: • Gate • Globe • Pinch • Diaphragm • Split-body • Three-way • Angle Optimux OpGL linear globe control valve
  • 18.
    - 18 - Classifyingby Motion: Rotary Rotary valves use a closure element that rotates – through a quarter-turn or 45° range – to open or block the flow • Larger port compared to linear valves of similar size • Weigh less than linear size-for-size • Limited in applications with pressure drops • Prone to cavitation and flashing • Often less costly Cross-section view of an eccentric rotary plug valve
  • 19.
    - 19 - Agenda I.Definition and Classification II. Valve Selection III. Sizing Basics IV. Actuators V. Positioners VI. Common Accessories
  • 20.
    - 20 - ValveCoefficients The measurement commonly applied to valves is the valve coefficient (CV) - also referred to as the flow coefficient - which is used to determine the valve size that will best allow the valve to pass the required flow rate while providing control of the process fluid One CV is defined as one U.S. gallon (3.78 liters) of 60°F (16°C) water that flows through an opening during 1 minute with a 1- psi (0.1-bar) pressure drop CV = Flow coefficient F = Flow rate (US GPM). SG = Specific Gravity fluid (Water = 1). ΔP = Pressure drop (psi).
  • 21.
    - 21 - FlowCharacteristics Each valve has a flow characteristic, which describes the relationship between the valve coefficient (CV) and the valve stroke – as a valve opens, the flow characteristic—which is inherent to the design of the selected valve—allows a certain amount of flow through the valve at a particular percentage of the stroke, which allows the valve to control the flow in a predictable manner The three most common types of flow characteristics are equal percentage, linear, and quick-open Equal Percentage Linear Quick Open
  • 22.
    - 22 - FlowCharacteristics Cont’d Two rules of thumb for choosing the right flow characteristic: 1. If most of the pressure drop is taken through the valve and the upstream pressure is constant, a linear characteristic will provide better control 2. If the piping and downstream equipment cause significant resistance to the system, equal percentage will provide better control Control Valve Pressure Drop Recommended Inherent Flow Characteristic Constant ΔP Linear Decreasing ΔP with increasing load: ΔP at maximum load >20% of minimum load ΔP Linear Decreasing ΔP with increasing load: ΔP at maximum load <20% of minimum load ΔP Equal Percentage Increasing ΔP with increasing load: ΔP at maximum load <200% of minimum load ΔP Linear Increasing ΔP with increasing load: ΔP at maximum load >200% of minimum load ΔP Quick Open
  • 23.
    - 23 - Rangeability Rangeabilityis the ratio of maximum to minimum flow that can be acted upon by a control valve after receiving a signal from a controller High rangeability allows a valve to control flow from large to small flows Rangeability is affected by three factors: 1. Valve geometry – inherent rangeability due to the design of the body and the regulating element 2. Seat leakage – excessive seat leakage can cause instability as the valve lifts off of the seat 3. Actuator – diaphragm actuators are seldom accurate at less than 5% of the valve opening, whereas piston-cylinder actuators can provide control within 1% of valve lift due to the presence of air in two chambers
  • 24.
    - 24 - ShutoffRequirements Industry standards regarding the amount of permissible leakage of the process fluid through a valve’s seat or seal – most applicable to throttling valves Leakage Class Designation Maximum Allowable Leakage Test Medium Test Pressure Test Procedure Class I N/A N/A N/A No Test Class II 0.5% of rated capacity Air or water at 50 - 125o F(10 - 52oC) Lower of 45 - 60 psig or maximum operating differential Lower of 45 - 60 psig or maximum operating differential Class III 0.1% of rated capacity As above As above As above Class IV 0.01% of rated capacity As above As above As above Class V 0.0005 ml per minute of water per inch of port diameter per psi differential Water at 50 to125oF (10 to 52oC) Maximum service pressure drop across valve plug not to exceed ANSI body rating Maximum service pressure drop across valve plug not to exceed ANSI body rating Class VI Not to exceed Class VI standard per port diameter Air or nitrogen at 50 to 125o F (10 to 52oC) 50 psig or max rated differential pressure across valve plug whichever is lower Actuator should be adjusted to operating conditions specified with full normal closing thrust applied to valve plug seal
  • 25.
    - 25 - BodyEnd Connections There are various end connections to allow a valve to be fitted to the system’s piping, and in ideal circumstances, the valve’s end connections and materials will match those of the system Threaded Flanged Welded
  • 26.
    - 26 - PressureClasses A valve is designed to handle a range of pressures up to a certain limit, called the valve’s pressure rating – the higher the rating, the thicker the walls of the valve vessel to prevent rupture Temperature effects: the higher the process temperature, the less pressure can be handled by the body subassembly Standard Classes: 150, 300, 600, 900, 1500, 2500, 4500 Sources: ANSI B16.34, Emerson Process Management
  • 27.
    - 27 - Face-to-Face Thedimension between one pipe mating surface of the valve to the surface on the opposite end is called the face-to-face dimension This physical dimension is always determined by the surface-to-surface measurement regardless of the type of end connection (threaded, flanged, or welded) Standard Valve Type Pressure Rating ANSI/ISA S75.03 Globe valves 150 – 600 (valve is interchangeable between Class 150, 300, and 600 ANSI/ISA S75.04 Flanged globe valves 125, 150, 250, 300, 600 ANSI/ISA S75.04 Flangeless globe valves 150, 300, 600 ANSI/ISA S75.08 Flanged clamp or pinch valves All classes ANSI/ISA S75.12 Socketweld and threaded end globe valves 150, 300, 600, 900, 1500, 2500 ANSI/ISA S75.14 Buttweld globe valves 4500 ANSI/ISA S75.15 Buttweld globe valves 150, 300, 600, 900, 1500, 2500 ANSI/ISA B16.10 Iron (ferrous), gate, plug, globe valves All classes BS 2080 Steel valves used in the petroleum, petrochemical, and associated industries All classes MSS SP-67 Butterfly valves All classes MSS SP-88 Diaphragm valves All classes MSS SP-42 Stainless steel valves All classes
  • 28.
    - 28 - BodyMaterials Common practice dictates that the end-user specify the body material, especially with special or severe service valves General service valves are specified with commonly found materials to match the pipe material ¡ Carbon Steel ¡ Stainless Steel ¡ Chrome-moly Standard Materials ¡ Hastelloy B and C ¡ Titanium ¡ Monel ¡ Bronze Special Alloys Control valve bodies are either cast, forged, or machined from bar stock, with standard sand casting as the most commonplace method Trimteck elects to use an advanced investment casting method as its standard for control valve bodies between .5” and 4” Investment casting offers the following benefits: ¡ Consistent and repetitive close tolerances ¡ Superior integrity and no porosity ¡ Fatigue performance equal to that of forgings ¡ Minimal need for machining A Word on Investment Casting …
  • 29.
    - 29 - TrimMaterials Valve parts – body, bonnet, bonnet bolting, plug, ball, disk, wedge, and/or drainage plug – exposed to pressure, process fluid, corrosion, and other effects of the service are required by regulation to be manufactured from approved metals In applications requiring elevated material hardness levels and resistance to corrosion and abrasion, Trimteck has pioneered the use of CVD-5B Trim Material Characteristics
  • 30.
    - 30 - Gaskets Agasket is a malleable material, which can be either soft or hard, that is inserted between two parts to prevent leakage between that joint Type Gasket Material Max Temp (oF/oC) Min Temp (oF/oC) Max Pressure (psi/bars) Flat Virgin PTFE 350/175 -200/-130 6000 – 1000 psi 415 – 70 bar Flat Reinforced PTFE 450/230 -200/-130 6000 – 500 pis 415 – 35 bar Flat CTFE 200/95 -423/-250 6000 – 500 psi 415 – 35 bar Flat FEP 400/205 -423/-250 6000 – 500 psi 415 – 35 bar Spiral- wound AFG 1500/815 -20/-30 6250 psi 430 bar Spiral- wound 316SS/ PTFE 350/176 -200/-130 6000 – 500 psi 415 – 35 bar Spiral- wound 316/ Graphite 1500/815 -423/-250 6250 psi 430 bar Hollow O- ring Inconel X-750 1500/815 -20/-30 15000 psi 1035 bar Common Gasket Materials and Types
  • 31.
    - 31 - Agenda I.Definition and Classification II. Valve Selection III. Sizing Basics IV. Actuators V. Positioners VI. Common Accessories
  • 32.
    - 32 - ValveSizing – Introduction Valve sizing is based on the standard thermodynamic laws of fluid flow, and is affected by the function of the valve plus the type and severity of the service Control valves require a systematic method of determining the required flow, as well as the size of the valve body, the body style, and materials that can accommodate (or tolerate) the process conditions, the correct pressure rating, and the proper installed flow characteristic ¡ Upstream Pressure ¡ Maximum and Minimum Temperatures ¡ Process Fluid ¡ Maximum, Average, and Minimum Flow Rates ¡ Vapor Pressure ¡ Pipeline Size, Schedule, and Material ¡ Maximum, Average, and Minimum Pressure Drop ¡ Specific Gravity of the Fluid ¡ Critical Pressure Required Conditions
  • 33.
    - 33 - ValveSizing – Electronic Data Sheet on Trimteck.com
  • 34.
    - 34 - Agenda I.Definition and Classification II. Valve Selection III. Sizing Basics IV. Actuators V. Positioners VI. Common Accessories
  • 35.
    - 35 - Actuators– Introduction With most valves, some mechanical device or external system must be devised to open or close the valve, or to change the position of the valve if it is to be used in throttling service Automatic control of valves requires an actuator, which is defined as any device mounted on a valve that, in response to a signal, automatically moves the valve to the required position using an outside power source ¡ Diaphragm ¡ Piston-Cylinder ¡ Rack and Pinion ¡ Rack and Gear ¡ Scotch Yoke Pneumatic Actuators ¡ Electromechanical ¡ Electro Hydraulic ¡ Hydraulic Non-pneumatic Actuators
  • 36.
    - 36 - DiaphragmActuator Advantages • Relatively inexpensive to produce • Suited to low-pressure ranges where limited thrust is adequate • Quick response • Simple design Disadvantages • Height and weight • Limited stroke • Low thrust • Pressure limitations on diaphragm • Do not provide exceptional stiffness • Not enough power to prevent “bathtub stopper effect” • Not field-reversible, laborious maintenance Note: Trimteck does not manufacture or market diaphragm actuators
  • 37.
    - 37 - Piston-CylinderActuator (OpTK) Advantages • Higher thrust capability • Compact and lightweight • Faster stroking speed • Longer stroke • Greater stiffness prevents “bathtub stopper effect” • Better performance than diaphragm actuators, with virtually no hysteresis, highly accurate signal response, and excellent linearity • Field-reversible Disadvantages • Some breakout torque required • Positioner adds to cost and complexity
  • 38.
    - 38 - Diaphragmvs. Piston Cylinder Thrust Comparison Diaphragm Piston Cylinder 60 inches2 25 inches2 30 psi Air Supply 80 psi Air Supply 750 lbs of thrust 2000 lbs of thrust Conclusion: A far larger diaphragm actuator would be needed to provide the same thrust requirement as the piston cylinder actuator.
  • 39.
    - 39 - Rackand Pinion Actuator (OpRPA) Advantages • Suitable for both on/off and modulating control applications • Durability and long cycle life • Cost effective • Versatility of casing materials • Field-reversible Misconceptions • Only for on/off service • Meets requirements for modulating control valves • Mechanical backlash • Lash between racks and pinion is minimal, and shaft to control element has no lash; clamping device ensures no play between actuator pinion and valve shaft
  • 40.
    - 40 - Rackand Gear Actuator (OpRGA) Advantages • Offset pistons eliminate internal cantilever loads • Low friction • Exceptional throttling control capability • Rugged • Field reversible • High cycle-life • Stainless steel standard • High temperature • Low pressure options • High speed option • Easy installation and maintenance
  • 41.
    - 41 - HeavyDuty Scotch Yoke Actuator (OpSY) Advantages • Ideal for heavy-duty applications, particularly for ESD • Excellent option for large valves with high breakout torque requirements • Simple and infrequent maintenance requirements • Known to achieve 1M cycles • Pressure ranges from 40psi to 2500psi • Torque from 1000in-lbs to 17,000in-lbs
  • 42.
    - 42 - Electromechanical(OpEM) Advantages • High degree of stability • Constant thrust • Extraordinary stiffness • Fails in place upon loss of electric power • Great solution for remote, solar-powered applications Disadvantages • Higher cost than pneumatic actuators • Complexity • Not recommended for flammable atmospheres • Slower speeds • Generate heat
  • 43.
    - 43 - Hydraulicand Electrohydraulic Advantages • Exceptionally stiff due to incompressibility of liquids • Used in valves with low rangeability • Fast stroking speeds • Ideal for safety management systems Disadvantages • Expensive • Large and bulky • Complex • Require specialized engineering
  • 44.
    - 44 - ActuatorPerformance Terminology Dead band – the maximum amount of input that is required to create a reversal in the movement of the actuator stem Frequency response – a response to a system or device to a constant-amplitude sinusoidal input signal Hysteresis – a common term used to describe the amount of position error that occurs when the same position is approached from opposite directions Independent linearity – the maximum amount that an actuator stem will deviate from a true straight linear line Maximum flow capacity – the volume of air pressure that can flow into an actuator during a particular time period measured in SCFM Open-loop gain – the ratio of the imbalance that occurs when an instrument signal change is made and the actuator stem is locked up Repeatability – similar to hysteresis, although it records the maximum variation of position when the same position is approached from the same direction Resolution – the smallest change possible in a valve- stem position Response level – the maximum amount of input change required to create a change in valve-stem position (in one direction only) Steady-state air consumption – applies to actuators with positioners in which the positioner consumes a certain amount of air pressure to maintain a required position Stiffness – the ability to hold a position despite process forces Stroking speed – the amount of time, in seconds, that an actuator requires to move from the fully retracted to the fully extended position Supply-pressure effect – the change of the actuator stem’s position for a 10-psi (0.7-bar) pressure change in the supply
  • 45.
    - 45 - Agenda I.Definition and Classification II. Valve Selection III. Sizing Basics IV. Actuators V. Positioners VI. Common Accessories
  • 46.
    - 46 - Positioners– Introduction A positioner is a device attached to an actuator that receives an electronic or pneumatic signal from a controller and compares that signal to the actuator’s position If the signal and the actuator position differ, the positioner sends the necessary power—usually through compressed air—to move the actuator until the correct position is reached Receive and convert pneumatic signal 3 to 15 psi 6 to 30 psi Pneumatic Positioners Receive and convert electronic signal 4 to 20 mA 10 to 50 mA Digital Positioners
  • 47.
    - 47 - PneumaticPositioner Optimux HPP2500 Pneumatic Positioner Technical Specifications Type Pneumatic Electropneumatic Input Signal 3 to 15 psi 4 to 20 mA Supply Pressure 30 to 150 psi Hysteresis 1.0% F.S. Repeatability 0.5% F.S. Max Flow Capacity 11 SCFM @ 60 psi Air Consumption 0.25 SCFM @ 60 psi 0.31 SCFM @ 60 psi Pneumatic Connections ¼-18 NPT female connection ¡ Characterized cam operation ¡ Easy adjustment and calibration ¡ Built-in dampers and gauge ports ¡ Corrosion-resistant
  • 48.
    - 48 - IntrinsicallySafe Smart Digital Positioner Optimux HPP4500 Digital Positioner Technical Specifications Type Digital Input Signal 4 to 20 mA Minimum Current Signal 3.8 mA Output Characteristics Linear, Equal Percentage, Quick Open, configurable to 16 points Power requirements 8.5 V Max Impedance 500Ω/20 mA Dc Enclosure NEMA 4X, IEC IP66 Safety Certification Intrinsically Safe Ex ia IIC T6/T5 Digital Communication HART® Digital Display LCD Weight 3.3 lbs (1.5 kg) ¡ Auto Setup ¡ Flexibility in installation ¡ High reliability ¡ One model for multiple characterizations
  • 49.
    - 49 - ExplosionProof Smart Digital Positioner Optimux HPP4000 Digital Positioner Technical Specifications Type Digital Input Signal 4 to 20 mA Feedback Signal 4 to 20 mA Output Characteristics Linear, Equal Percentage, Quick Open, configurable to 16 points Max Impedance 500Ω/20 mA Dc Enclosure NEMA 4X, IEC IP66 Safety Certification Explosion Proof Ex d IIC T6 Digital Communication HART® Digital Display LCD Air Consumption Below 2LPM @ 20 psi, 3 LPM @ 100 psi Auxiliary Switches Dual limit switches Repeatability +/- 0.3% F.S. ¡ Auto Calibration ¡ Variable orifices minimize hunting ¡ Corrosion resistant ¡ One model for multiple characterizations
  • 50.
    - 50 - Agenda I.Definition and Classification II. Valve Selection III. Sizing Basics IV. Actuators V. Positioners VI. Common Accessories
  • 51.
    - 51 - CommonAccessories – Introduction Some special actuation systems or actuators require fast stroking speeds, signal conversions from one medium to another, position transmissions, etc. In these applications, accessories are included with the actuator to help perform these functions Ideally, accessories are mounted directly onto the valve to ensure that the user is aware of the location of the device ¡ Air Filter/Regulator ¡ Limit Switch ¡ Proximity Switch ¡ Position Transmitter ¡ Flow Booster ¡ Solenoid ¡ Safety Relief Valve ¡ Speed Control Valve ¡ Transducer Common Accessories
  • 52.
    - 52 - AirFilter/Regulator The Air Filter/Regulator is designed to screen the power supply medium of impurities that may contaminate an actuation system, positioner, or other accessory, as well as to regulate or limit the air supply to the actuator Mounted between the source of power supply and the actuator or positioner
  • 53.
    - 53 - LimitSwitch When an electrical signal must be sent indicating an open, closed, or midstroke position of an actuator or valve, an electrical switching device—called a limit switch—is used Limit switches are normally used to sound alarms or operate signal lights, electric relays, or small solenoid valves
  • 54.
    - 54 - ProximitySwitch When a mechanical connection between the limit switch and the stem or shaft is not desirable, a proximity switch is used. A proximity switch is a limit switch that uses a magnetic sensor instead of a mechanical arm
  • 55.
    - 55 - PositionTransmitter A position transmitter is a device that provides a continuous signal indicating the position of the valve or actuator Allows for signal indication, monitoring actuator performance, logging data, or controlling associated instrumentation or equipment
  • 56.
    - 56 - FlowBooster Flow boosters are used to increase the stroking speed of larger pneumatic actuators Because of their increased volumes, large actuators have difficulty making fast and immediate stokes
  • 57.
    - 57 - Solenoid Asolenoid is an electrical control device that receives an electrical signal (usually a 4- to 20-mA) and, in response, channels air supply directly to the actuator
  • 58.
    - 58 - SafetyRelief Valve Safety relief valves are designed to open to atmosphere when a particular pressure is exceeded When volume tanks are used or if high-pressure actuators must be used to handle the service conditions, some local codes require the installation of safety relief valves on these high-pressure vessels as protection against overpressurization
  • 59.
    - 59 - SpeedControl Valve Speed control valves are used to limit the stroking speed of an actuator by restricting the amount of air flow to or from the actuator These small valves can be mounted between the tubing and the actuator and are available in sizes that match common tubing sizes
  • 60.
    Thank you foryour attention, for more information please visit us at trimteck.com