PARALLEL OPERATION OF
ALTERNATORS
Citharthan D
Assistant Professor
Christ the King Engineering College
Coimbatore, India
If we need to operate the alternator in parallel we need to synchronize the
alternators.
Condition for synchronizing:
The source (generator or sub-network) must have equal
1. line voltage
2. Frequency
3. Phase sequence
4. Phase angle
5. Waveform
to that of the system to which it is being synchronized.
Waveform and phase sequence are fixed by the construction of the generator
and its connections to the system.
So the voltage, frequency and phase angle must be controlled each time a
generator is to be connected to a grid.
A1 A2
ZS ZS
Local circuit
Consider alternator A1 produces an
e.m.f E1 whereas alternator A2
produces an e.m.f E2.
With respect to the load, their e.m.fs
are normally in phase: with respect
to the local circuit their e.m.fs are in
phase-opposition as shown in below fig.
E1 E2
So there will not be any circulating
current ( since resultant e.m.f is zero)
E1 E2
Circulating current (Ic) = Er/2Zs
Analysis of Synchronized Alternators A1 and A2 on no load
Let us consider two abnormal conditions on no-load
1)Change in prime mover
2)Change in Excitation
Suppose there to be no external load if machine 2 for some reason
accelerates (by its prime mover), its e.m.f. will draw ahead of machine 1.
Consider the resulting Phase difference is 2∂.
E1
2∂
E2Er
1) Change in Prime mover input (On no Load)
When Zs = Resistance Circulating current (Ic) will be in phase with the resultant EMF (Er)
E1
2∂
E2Er
Ic (circulating current)
almost Quadrature to E1 and E2)
When Zs= inductive Circulating current (Ic) will lags the resultant EMF (Er)
E1
2∂
E2Er
Ic
almost
in phase
with E2
}Synchronizing
power
This synchronizing power makes the alternator A2 to work as generator
and A1 as motor. i.e alternator A2 supplies current to alternator A1
Since alternator A2 supplies current it gradually lags whereas alternator A1
acting as a motor gradually leads.
E1
2∂
E2
E2
∂
E1
(During Transition)
(At steady state condition Er= 0 , Hence no circulating current )
Thus the presence of more resistance in the generators will
resist or oppose their synchronous operation. More reactance
in the generators can cause good reaction between the two
and help the generators to remain synchronism in spite of
any disturbance occurring in any one of the generators.
From phasor diagram , total synchronizing power, Maximum
synchronizing power and synchronizing torque can be calculated
2) Change in Excitation (on no load)
With respect to the load, their e.m.fs
are normally in phase: with respect to
the local circuit their e.m.fs are in
phase-opposition as shown below.
A1 A2
ZS
Local circuit
E2
Circulating current (Ic) = Er/2Zs
E1 E2
I1 I2
If excitation of alternator 1 is increased then magnitude of E1 will be more than that
of E2
E2
E1 Er
Isy (circulating current)
Isy - lagging current for E1 which will produce demagnetizing effect and will try to
reduce the emf E1.
Isy - leading current for E2 which will produce Magnetising effect and will try to
increase the emf E2.
Hence circulating current will try to make the two generated emf equal at no load.
Hence cos φ1 (phase 1) is reduced and cos φ2 (phase 2) is increased.
Thus changes in KW loading of the two alternator is negligible
but reactive power KVAR1 from the alternator is increased
whereas KVAR2 supplied by second alternator is decreased which
can seen from power triangle.
THANKS

More Related Content

PPTX
POWER QUALITY IMPROVEMENT BY DSTATCOM
Sajid Sheikh
 
PDF
Speed control of dc motors
ragulkncet
 
PPTX
Braking methods of induction motor
raviarmugam
 
PPT
EXCITATION SYSTEM.ppt
vishal laddha
 
PDF
Introduction
jawaharramaya
 
PPTX
Protection of alternator
Biswajit Pratihari
 
PDF
Power factor improvement
Saiful Islam Rukon
 
PPTX
PERMANENT MAGNET BRUSHLESS DC MOTOR
Archana Balachandran
 
POWER QUALITY IMPROVEMENT BY DSTATCOM
Sajid Sheikh
 
Speed control of dc motors
ragulkncet
 
Braking methods of induction motor
raviarmugam
 
EXCITATION SYSTEM.ppt
vishal laddha
 
Introduction
jawaharramaya
 
Protection of alternator
Biswajit Pratihari
 
Power factor improvement
Saiful Islam Rukon
 
PERMANENT MAGNET BRUSHLESS DC MOTOR
Archana Balachandran
 

What's hot (20)

PPTX
Power factor
NAVEEN KOREDDI
 
PPTX
Speed Control Of DC Motor
PRAVEEN KUMAR
 
PPTX
Unit 5 series motor (universal)motors
Er.Meraj Akhtar
 
PPTX
Ppt of current transformer
ROOPAL PANCHOLI
 
PPTX
Series & shunt compensation and FACTs Devices
khemraj298
 
PPTX
Unified Power Flow Controller(upfc)1
JayakalyanReddy
 
PPT
Starter of an induction motor
sbpatel199688
 
PPTX
Reluctance motor
Chetan Patil
 
PPT
Instrument transformer CT & PT
Chandan Singh
 
PPTX
Current Source Inverter and Voltage Source Inverter
Sadanand Purohit
 
PPT
Capacitance on transmission line
vishalgohel12195
 
PPTX
Speed Control of Synchronous Motor
Ashutosh Jha
 
PDF
Statcom
jawaharramaya
 
PPTX
Synchronous reluctance motor
karthi1017
 
PPTX
Current Transformer
MAYURSINH RATHOOD
 
PDF
Chapter 01- High Voltage Engineering Introduction
MUET SZAB Campus Khairpur Mir's Sindh Pakistan
 
PPTX
1 phase induction motor
AbhishekLalkiya
 
PPTX
Effects on transmission line
Ajaj Shaikh
 
PPTX
Voltage source Converters as a building block of HVDC and FACTS
Karthik Bharadwaj
 
PDF
Generator capability curve
Amit Pathak
 
Power factor
NAVEEN KOREDDI
 
Speed Control Of DC Motor
PRAVEEN KUMAR
 
Unit 5 series motor (universal)motors
Er.Meraj Akhtar
 
Ppt of current transformer
ROOPAL PANCHOLI
 
Series & shunt compensation and FACTs Devices
khemraj298
 
Unified Power Flow Controller(upfc)1
JayakalyanReddy
 
Starter of an induction motor
sbpatel199688
 
Reluctance motor
Chetan Patil
 
Instrument transformer CT & PT
Chandan Singh
 
Current Source Inverter and Voltage Source Inverter
Sadanand Purohit
 
Capacitance on transmission line
vishalgohel12195
 
Speed Control of Synchronous Motor
Ashutosh Jha
 
Statcom
jawaharramaya
 
Synchronous reluctance motor
karthi1017
 
Current Transformer
MAYURSINH RATHOOD
 
Chapter 01- High Voltage Engineering Introduction
MUET SZAB Campus Khairpur Mir's Sindh Pakistan
 
1 phase induction motor
AbhishekLalkiya
 
Effects on transmission line
Ajaj Shaikh
 
Voltage source Converters as a building block of HVDC and FACTS
Karthik Bharadwaj
 
Generator capability curve
Amit Pathak
 
Ad

Similar to Parallel operation of alternators 1 (20)

PPTX
parallel operation of alternator.pptx of pokhara university
lopchanmahima
 
PPT
Parallel Operation on Alternators.
R-One Power
 
PDF
Eet3082 binod kumar sahu lecturer_16
BinodKumarSahu5
 
PDF
Eet3082 binod kumar sahu lecturer_18
BinodKumarSahu5
 
PDF
Eet3082 binod kumar sahu lecturer_15
BinodKumarSahu5
 
PDF
Eet3082 binod kumar sahu lecturer_19
BinodKumarSahu5
 
PPT
ENERGY_CONVERSION_12.ppt
GoldenDaisy3
 
PPTX
Parallel operation of transformer
Manish Kumar
 
PPTX
Synchronous generator
Prasant Kumar
 
PDF
Synchronous Generator presentation is given here.pdf
YaminShahriar
 
PPTX
Synchronizing and Parallel operation.pptx
Selva Sam
 
PPTX
Parallel.pptx
AssistantEngineer13
 
PPTX
Chapter 1 - Experiment 1 slides.pptx
asmasharab1
 
PDF
em-II ppt 12345678912345669878951255.pdf
Dhana Prasad
 
PDF
Machine Chapter-5 Synchronous macine.pdf
EstifanosKebede2
 
PDF
Comparative review of analogue and digital Synchroscope in India used for syn...
IRJET Journal
 
PPSX
Basic Electrical of Power plant , SLD , Excitation
MANOJ KUMAR MAHARANA
 
PPTX
BASICS OF SYNCHROUS MACHINE AS ELECTRICAL MACHINE.pptx
Bismark Budu
 
PDF
Eet3082 binod kumar sahu lecturer_17
BinodKumarSahu5
 
PPT
gas turbine generator set operation and maintenance
AmrSherif54
 
parallel operation of alternator.pptx of pokhara university
lopchanmahima
 
Parallel Operation on Alternators.
R-One Power
 
Eet3082 binod kumar sahu lecturer_16
BinodKumarSahu5
 
Eet3082 binod kumar sahu lecturer_18
BinodKumarSahu5
 
Eet3082 binod kumar sahu lecturer_15
BinodKumarSahu5
 
Eet3082 binod kumar sahu lecturer_19
BinodKumarSahu5
 
ENERGY_CONVERSION_12.ppt
GoldenDaisy3
 
Parallel operation of transformer
Manish Kumar
 
Synchronous generator
Prasant Kumar
 
Synchronous Generator presentation is given here.pdf
YaminShahriar
 
Synchronizing and Parallel operation.pptx
Selva Sam
 
Parallel.pptx
AssistantEngineer13
 
Chapter 1 - Experiment 1 slides.pptx
asmasharab1
 
em-II ppt 12345678912345669878951255.pdf
Dhana Prasad
 
Machine Chapter-5 Synchronous macine.pdf
EstifanosKebede2
 
Comparative review of analogue and digital Synchroscope in India used for syn...
IRJET Journal
 
Basic Electrical of Power plant , SLD , Excitation
MANOJ KUMAR MAHARANA
 
BASICS OF SYNCHROUS MACHINE AS ELECTRICAL MACHINE.pptx
Bismark Budu
 
Eet3082 binod kumar sahu lecturer_17
BinodKumarSahu5
 
gas turbine generator set operation and maintenance
AmrSherif54
 
Ad

More from Citharthan Durairaj (16)

PDF
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
Citharthan Durairaj
 
PDF
Closed Loop I-F control using six step current source inverter
Citharthan Durairaj
 
PDF
Voltage Source Inverter VSI - Six Step Switching
Citharthan Durairaj
 
PDF
Voltage Source Inverter VSI - Pulse Width Modulation (PWM)
Citharthan Durairaj
 
PDF
V/F control of Induction Motor - Variable voltage and Variable frequency
Citharthan Durairaj
 
PDF
Voltage control of Induction Motor
Citharthan Durairaj
 
PDF
Equivalent circuit of Induction Motor
Citharthan Durairaj
 
PDF
Torque speed characteristics of Squirrel cage & Slip ring induction motors
Citharthan Durairaj
 
PDF
Induction Motor- Principle of Operation
Citharthan Durairaj
 
PDF
Steps to be done in blynk app to get alert notification or email
Citharthan Durairaj
 
PDF
Steps to be done in arduino ide for monitoring
Citharthan Durairaj
 
PDF
Steps to be done in node mcu for monitoring
Citharthan Durairaj
 
PDF
Steps to be done in blynk app for monitoring
Citharthan Durairaj
 
PDF
IoT Introduction
Citharthan Durairaj
 
PPTX
stepper motors
Citharthan Durairaj
 
PPTX
PMBLDC motors
Citharthan Durairaj
 
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
Citharthan Durairaj
 
Closed Loop I-F control using six step current source inverter
Citharthan Durairaj
 
Voltage Source Inverter VSI - Six Step Switching
Citharthan Durairaj
 
Voltage Source Inverter VSI - Pulse Width Modulation (PWM)
Citharthan Durairaj
 
V/F control of Induction Motor - Variable voltage and Variable frequency
Citharthan Durairaj
 
Voltage control of Induction Motor
Citharthan Durairaj
 
Equivalent circuit of Induction Motor
Citharthan Durairaj
 
Torque speed characteristics of Squirrel cage & Slip ring induction motors
Citharthan Durairaj
 
Induction Motor- Principle of Operation
Citharthan Durairaj
 
Steps to be done in blynk app to get alert notification or email
Citharthan Durairaj
 
Steps to be done in arduino ide for monitoring
Citharthan Durairaj
 
Steps to be done in node mcu for monitoring
Citharthan Durairaj
 
Steps to be done in blynk app for monitoring
Citharthan Durairaj
 
IoT Introduction
Citharthan Durairaj
 
stepper motors
Citharthan Durairaj
 
PMBLDC motors
Citharthan Durairaj
 

Parallel operation of alternators 1

  • 1. PARALLEL OPERATION OF ALTERNATORS Citharthan D Assistant Professor Christ the King Engineering College Coimbatore, India
  • 2. If we need to operate the alternator in parallel we need to synchronize the alternators. Condition for synchronizing: The source (generator or sub-network) must have equal 1. line voltage 2. Frequency 3. Phase sequence 4. Phase angle 5. Waveform to that of the system to which it is being synchronized. Waveform and phase sequence are fixed by the construction of the generator and its connections to the system. So the voltage, frequency and phase angle must be controlled each time a generator is to be connected to a grid.
  • 3. A1 A2 ZS ZS Local circuit Consider alternator A1 produces an e.m.f E1 whereas alternator A2 produces an e.m.f E2. With respect to the load, their e.m.fs are normally in phase: with respect to the local circuit their e.m.fs are in phase-opposition as shown in below fig. E1 E2 So there will not be any circulating current ( since resultant e.m.f is zero) E1 E2 Circulating current (Ic) = Er/2Zs Analysis of Synchronized Alternators A1 and A2 on no load
  • 4. Let us consider two abnormal conditions on no-load 1)Change in prime mover 2)Change in Excitation
  • 5. Suppose there to be no external load if machine 2 for some reason accelerates (by its prime mover), its e.m.f. will draw ahead of machine 1. Consider the resulting Phase difference is 2∂. E1 2∂ E2Er 1) Change in Prime mover input (On no Load)
  • 6. When Zs = Resistance Circulating current (Ic) will be in phase with the resultant EMF (Er) E1 2∂ E2Er Ic (circulating current) almost Quadrature to E1 and E2)
  • 7. When Zs= inductive Circulating current (Ic) will lags the resultant EMF (Er) E1 2∂ E2Er Ic almost in phase with E2 }Synchronizing power This synchronizing power makes the alternator A2 to work as generator and A1 as motor. i.e alternator A2 supplies current to alternator A1
  • 8. Since alternator A2 supplies current it gradually lags whereas alternator A1 acting as a motor gradually leads. E1 2∂ E2 E2 ∂ E1 (During Transition) (At steady state condition Er= 0 , Hence no circulating current )
  • 9. Thus the presence of more resistance in the generators will resist or oppose their synchronous operation. More reactance in the generators can cause good reaction between the two and help the generators to remain synchronism in spite of any disturbance occurring in any one of the generators. From phasor diagram , total synchronizing power, Maximum synchronizing power and synchronizing torque can be calculated
  • 10. 2) Change in Excitation (on no load) With respect to the load, their e.m.fs are normally in phase: with respect to the local circuit their e.m.fs are in phase-opposition as shown below. A1 A2 ZS Local circuit E2 Circulating current (Ic) = Er/2Zs E1 E2 I1 I2
  • 11. If excitation of alternator 1 is increased then magnitude of E1 will be more than that of E2 E2 E1 Er Isy (circulating current) Isy - lagging current for E1 which will produce demagnetizing effect and will try to reduce the emf E1. Isy - leading current for E2 which will produce Magnetising effect and will try to increase the emf E2. Hence circulating current will try to make the two generated emf equal at no load.
  • 12. Hence cos φ1 (phase 1) is reduced and cos φ2 (phase 2) is increased. Thus changes in KW loading of the two alternator is negligible but reactive power KVAR1 from the alternator is increased whereas KVAR2 supplied by second alternator is decreased which can seen from power triangle.