PROTECTION OF CONVERTER
DENSE POWER SYSTEMS
PRESENTED BY:- RAJASHREE SAHOO
REGD NO:- 1241019002
1
Contents
 Introduction
 Definition of PECs
 PECs Fault Response
 Grid Code Requirements for PECs
 Positive impact of PECs
 Negative impact of PECs
 Potential Protection Solutions
 Conclusion
 Reference
2
INTRODUCTION
 The number of Power Electronic Converter(PECs) utilised in
power systems throughout the world is increasing.
 PECs are found in a huge range of applications, in power
systems they are used to interface Distributed Generation
(DG) to the main power system and for fault current
limiting/interruption applications.
 These PEC interfaces generally have a low tolerance to
overcurrent and rely on extremely fast acting protection
which is integral to the PECs’ control systems.
 The widespread introduction of PEC-interfaced energy sources
has both positive and negative implications for network
protection.
3
4
The task of a power converter is to process and control the flow of
electric energy by supplying voltages and currents in a form
that is optimally suited for the user loads.
An ideal static converter controls the flow of power between the two
sources with 100% efficiency. Power converter design aims at improving
the efficiency.
What are PECs?
Image Courtesy : Ref[8]
CONTD..
 There are two types of sources: voltage and current sources. Any of
these sources could be a generator or a receptor (load).
 The principle of operation of a converter is based on the switch
mode action of its switches. Commutations of the switches generate
very fast current and/or voltage transients so that the transient
behaviour of the sources is fundamental for converter design.
 The transient behaviour of a source is characterized by its ability or
inability to withstand steps generated by the external circuit in the
voltage across its terminals or in the current flowing through it. Then
new definitions could be stated:
5
CONTD.
a) A source is a voltage source if the voltage across its terminals can
not undergo a discontinuity due to the external circuit variation.
b) A source is a current source if the current flowing through it can
not undergo a discontinuity due to the external circuit variation.
 Minimizing the losses in the switches maximizes the efficiency of the
converter.
 These switches must have a voltage drop as low as possible in the ON-
state, and a negligible leakage current in the OFF-state.
6
PEC FAULT RESPONSE
 A PEC’s response is governed by its control system i.e., how it
should behave (in terms of fault current contribution during
external faults). how it should behave (in terms of fault current
contribution during external faults).
7
Fig. 2. PEC RMS Current
Fault Response
Image Courtesy: Ref[2]
Fig. 3. PEC RMS
Voltage Fault Response
Image Courtesy: Ref[2]
…CONTD
 PECs typically share some general characteristics: they are often
configured to attempt to “ride through” external faults, sometimes at
the expense of providing significant levels of fault current.
 A typical fault response for a PEC during a fault is shown in Fig. 2 and
Fig. 3.
8
9
GRID CODE REQUIREMENTS FOR PECs
Fig. 4. Grid Code - PEC ride through requirements for system
voltage depressions
Image Courtesy: Ref[2]
CONTD..
 The UK grid code specifies that a PEC should conform to the
following parameters for faults on the transmission system:
 “PECs should remain transiently stable and connected for faults
up to and including close-up solid three-phase short circuit faults
for up to 140ms. For faults in excess of 140ms a PEC should
remain transiently stable and connected for voltage depressions
anywhere on or above the heavy black line shown in Fig. 3. For
faults involving voltage depressions, and corresponding times,
below the black line, it is acceptable for the PEC to trip.”
 During the period of the fault the PEC should provide maximum
reactive current without exceeding its transient rating limit.
 Duration and fault clearance times should be specified in a
bilateral agreement between the PEC installer and the
Distribution Network Operator (DNO).”
10
POSITIVE IMPACT OF PECS ON POWER SYSTEM
PROTECTION
11
While this research focuses primarily on the negative impact PECs
have on power system protection there are a number of benefits to
having PEC-dense power systems.
PEC-interfaced DG normally limits the fault current contribution from
the DG and in doing so limits the risk of damage during over current
conditions. They also help mitigate certain protection issues:-
1. Reduction of Protection Blinding- Blinding of protection occurs when a
protection device is unable to detect a fault due to fault current not
being detected by its measurement transformer .
Fig.5. Blinding of Protection
Image Courtesy: Ref[2]
2.
12
Reduction of False Tripping -False tripping may occur when two or more
lines are connected to a common bus.
The PEC interface reduces the likelihood of this problem occurring by
limiting the fault current from the DG as shown in Fig. 6.
With the PEC interface in place the protective device on line 2 will measure
a higher fault current than the device on line 1 and should trip faster.
Fig.6. False Tripping
Image Courtesy: Ref[2]
NEGATIVE IMPACT OF PEC ON POWER SYSTEM
PROTECTION
 PECs have a low tolerance to overcurrent and their protection must
therefore operate extremely quickly to avoid damage to their
semiconductors during a fault.
13
Fig. 7. Fault on PEC Dense Power System
Image Courtesy: Ref[2]
 For a fault, as shown in Fig.7, there is a risk that the PEC
protection will operate before downstream relays, either tripping or
limiting the fault current.
 Neither of these responses are desirable from a PEC/network
protection coordination perspective.
 Tripping before network protection relays will result in an
unnecessary loss of load; fault current limiting may result in a
sustained fault current condition wherein the fault current is not
high enough to trip the overcurrent relays on the network.
14
POTENTIAL PROTECTION SOLUTIONS
 There are a number of potential solutions to the problems created
for power system protection by PEC-interfaced sources:-
A. Incorporation of Energy Storage Devices: One of the most
significant problems with PEC interfaces is their lack of fault
current contribution. Energy storage devices could be used to
contribute to fault current and thus enable fault detection by
conventional overcurrent relays as shown in Fig. 8.
15
Fig. 8.Energy storage fault current contribution
Image Courtesy: Ref[2]
B. Control of Fault Behaviour of PECs:
16
Fig. 9.PEC Fold Back Response
Image Courtesy: Ref[2]
Fig.10. PEC Brickwalling
Response
Image Courtesy: Ref[2]
 Fold back is a method for controlling the fault current provided
by the PEC. All of the control is carried out internally by the
PEC’s control system.
 Directly after the fault, the control system allows the PEC
current output to peak; the peak being dependent on the
capabilities of the PEC switches and the source supplying the
PEC.
 This peak fault current level is sustained for a short period of
time in an attempt to operate overcurrent protection devices
while limiting damage to the PEC’s power electronics.
 The brickwalling response differs from fold back in several
ways: the fault current output is sustained at a lower level for a
longer duration and the output current isn’t reduced to a level
less than load current to facilitate switchgear interruption
17
CONCLUSION
 A description of the behaviour of PECs during faults, both in
terms of fault current and response time has been presented and
the positive and negative impacts.
 One of the main objectives of this research is to determine the
level of PEC proliferation at which the overall protection system
may begin to experience problems and to investigate solutions
that could be used to mitigate such problems.
18
REFERENCES
[1] L. Freeris and D. Infield, "Renewable Energy in Power Systems," 1st ed
Chichester: John Wiley & Sons Ltd, 2008, pp. 122, 133, 192, 144-145.
[2] J. Morren and S. W. H. de Haan, "Impact of distributed generation units
with power electronic converters on distribution network protection," in
Developments in Power System Protection, 2008. DPSP 2008. IET 9th
International Conference on, 2008, pp. 664669.
[3] The Grid Code, Issue 4 Revision 1, Connection Conditions, N. G. E.
Transmission, 2009.
[4] H. Wan, K. P. Wong, and C. Y. Chung, "Multi-agent application in
protection coordination of power system with distributed generations,"
in Power and Energy Society General Meeting - Conversion and
Delivery of Electrical Energy in the 21st Century, 2008 IEEE, 2008, pp.
1-6.
[5] J. R. S. S. Kumara, A. Atputharajah, J. B. Ekanayake, and F. J. Mumford,
"Over current protection coordination of distribution networks with fault
current limiters," in Power Engineering Society General Meeting, 2006.
IEEE, 2006, p. 8 pp. 19
REFERENCES
[6] S. M. Blair, A. J. Roscoe, C. D. Booth, G. M. Burt, A. Teo, and C. G.
Bright, "Implications of Fault Current Limitation for Electrical
Distribution Networks," Developments in Power System Protection, pp. 1-
5, 2010.
[7] K. Kauhaniemi and L. Kumpulainen, "Impact of distributed generation on
the protection of distribution networks," in Developments in Power
System Protection, 2004. Eighth IEE International Conference on, 2004,
pp. 315-318 Vol.1.
[8] F. Bordry CERN, Geneva, Switzerland , “Power converters: definitions,
classification and converter topologies” .
20
21
THANK YOU

More Related Content

PPTX
Circuit breaker arc interruption.pptx
AnshulShekhar3
 
PPT
Generation shift factor and line outage factor
Viren Pandya
 
PDF
Comparision of svc and statcom
jawaharramaya
 
PDF
Power system stability
Balaram Das
 
PPTX
Facts static voltage & phase angle regulators
SITCOE, Yadrav
 
PPTX
Differential Protection Relay
kishore kish
 
PPTX
Load dispatch center
ddxdharmesh
 
PPTX
Synchronous motor drive
Guru Moorthi
 
Circuit breaker arc interruption.pptx
AnshulShekhar3
 
Generation shift factor and line outage factor
Viren Pandya
 
Comparision of svc and statcom
jawaharramaya
 
Power system stability
Balaram Das
 
Facts static voltage & phase angle regulators
SITCOE, Yadrav
 
Differential Protection Relay
kishore kish
 
Load dispatch center
ddxdharmesh
 
Synchronous motor drive
Guru Moorthi
 

What's hot (20)

PPT
ABCB(air blast circuit breaker)
AB Amit
 
PPTX
Inter Connected Power System(Turbine Speed Governing Mechanism )
Raviraj solanki
 
PPTX
Generator and Transformer Protection (PART 2)
Dr. Rohit Babu
 
PPTX
Classification Of Power System Stability
Aravind Shaji
 
PPT
upfc
nehakardam
 
PPTX
Insulation coordination
Rakshita Upadhyay
 
PPTX
Single phase compensated motor
SayanSarkar55
 
PPTX
Sssc
Divya Yennam
 
PDF
Protection of transmission lines (distance)
Rohini Haridas
 
PPTX
Surge arrester ppt
IrinElsa
 
PPTX
PPT ON POWER SYSTEM STABILITY
MAHESH CHAND JATAV
 
PPTX
Unit- 3 DC-DC Converter
johny renoald
 
PPTX
Zener and avalanche diode
AnuJyothi2
 
PPT
3 reactive power and voltage control
8141245710
 
PPT
Switchgear and protection lecture 2 type of circuit breakers and applications
anuphowlader1
 
PPTX
Rotary and linear switched reluctance motors
karthi1017
 
PDF
Protection of transmission lines(encrypted)
Rohini Haridas
 
PPTX
Cascade control presentation
Inara Ahmadova
 
PDF
As per KITS r20 facts unit-5 combined controllers
HARIMADHAVAREDDY YENIREDDY7
 
PPTX
Automatic Generation Control
Birju Besra
 
ABCB(air blast circuit breaker)
AB Amit
 
Inter Connected Power System(Turbine Speed Governing Mechanism )
Raviraj solanki
 
Generator and Transformer Protection (PART 2)
Dr. Rohit Babu
 
Classification Of Power System Stability
Aravind Shaji
 
Insulation coordination
Rakshita Upadhyay
 
Single phase compensated motor
SayanSarkar55
 
Protection of transmission lines (distance)
Rohini Haridas
 
Surge arrester ppt
IrinElsa
 
PPT ON POWER SYSTEM STABILITY
MAHESH CHAND JATAV
 
Unit- 3 DC-DC Converter
johny renoald
 
Zener and avalanche diode
AnuJyothi2
 
3 reactive power and voltage control
8141245710
 
Switchgear and protection lecture 2 type of circuit breakers and applications
anuphowlader1
 
Rotary and linear switched reluctance motors
karthi1017
 
Protection of transmission lines(encrypted)
Rohini Haridas
 
Cascade control presentation
Inara Ahmadova
 
As per KITS r20 facts unit-5 combined controllers
HARIMADHAVAREDDY YENIREDDY7
 
Automatic Generation Control
Birju Besra
 
Ad

Viewers also liked (20)

PPTX
Surge current protection using superconductor ppt mahesh
Kuldeep Singh
 
PDF
Humphree Interceptor for Linked in
Magnus Gripenwald
 
PPTX
Advertisement analysis
Helintezcanli99
 
PPTX
Evaluation Task 1
carlottaba
 
PDF
32nd Annual Fuel Ethanol Workshop & Expo - Milwaukee, WI
Valley Expo Displays
 
DOCX
Tokyopop Final
Malcolm Lenore
 
PDF
Cv jpa
Jesus Penilla
 
PDF
Tub vapor
Aluscka Aretuza
 
PDF
Псалтикийни треби
Petar Vasilev
 
PDF
Псалтикийна утреня
Petar Vasilev
 
PDF
Koulutusrahasto ja aikuiskoulutuksen rahoitus
Koulutusrahasto
 
PPTX
PRESENTACION DE LAS REFERENCIAS (APA).
javier lara
 
PDF
Resume HI
Humberto Infante
 
PDF
Akibat memakan harta riba
ridhofharis
 
PPTX
Introduction to vim
政謙 陳
 
PDF
Igor_Tolkach_Portfolio2015
Igor Tolkach
 
PDF
Sterlin Suttles Resume.docx
sterlin suttles
 
DOCX
Five Irish Musicians to Listen to This Week EDITS
Malcolm Lenore
 
PDF
ปฏิทินรายเดือน
0710091902
 
PPTX
Resolution implementation
parliaments.cluster
 
Surge current protection using superconductor ppt mahesh
Kuldeep Singh
 
Humphree Interceptor for Linked in
Magnus Gripenwald
 
Advertisement analysis
Helintezcanli99
 
Evaluation Task 1
carlottaba
 
32nd Annual Fuel Ethanol Workshop & Expo - Milwaukee, WI
Valley Expo Displays
 
Tokyopop Final
Malcolm Lenore
 
Tub vapor
Aluscka Aretuza
 
Псалтикийни треби
Petar Vasilev
 
Псалтикийна утреня
Petar Vasilev
 
Koulutusrahasto ja aikuiskoulutuksen rahoitus
Koulutusrahasto
 
PRESENTACION DE LAS REFERENCIAS (APA).
javier lara
 
Resume HI
Humberto Infante
 
Akibat memakan harta riba
ridhofharis
 
Introduction to vim
政謙 陳
 
Igor_Tolkach_Portfolio2015
Igor Tolkach
 
Sterlin Suttles Resume.docx
sterlin suttles
 
Five Irish Musicians to Listen to This Week EDITS
Malcolm Lenore
 
ปฏิทินรายเดือน
0710091902
 
Resolution implementation
parliaments.cluster
 
Ad

Similar to Protection of Converter Dense Power Systems (20)

PDF
Concept and Viability of High Temperature Superconductor Fault Current Limite...
IOSR Journals
 
PDF
Green power zone
CHESF
 
PDF
Bb4103331337
IJERA Editor
 
PDF
Parasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
IJMTST Journal
 
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 
PDF
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
IRJET Journal
 
PDF
Single-bit modulator for wireless power transfer system
International Journal of Power Electronics and Drive Systems
 
PDF
Aq33247251
IJERA Editor
 
PDF
Aq33247251
IJERA Editor
 
PDF
Bp36398403
IJERA Editor
 
PDF
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
IAES-IJPEDS
 
PDF
Dynamic voltage restorer (DVR) in a complex voltage disturbance compensation
International Journal of Power Electronics and Drive Systems
 
PDF
Dk36667674
IJERA Editor
 
PDF
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
International Journal of Power Electronics and Drive Systems
 
PDF
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
SultanAlSaiari1
 
PDF
Adaptability of Distribution Automation System to Electric Power Quality Moni...
IOSR Journals
 
PDF
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
elelijjournal
 
PDF
Impact of LCC–HVDC multiterminal on generator rotor angle stability
IJECEIAES
 
PDF
CPRI-Power quality report
Nageswar Rao
 
PDF
Review of DC Offset Compensation Techniques for Grid Connected Inverters
International Journal of Power Electronics and Drive Systems
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
IOSR Journals
 
Green power zone
CHESF
 
Bb4103331337
IJERA Editor
 
Parasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
IJMTST Journal
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
IRJET Journal
 
Single-bit modulator for wireless power transfer system
International Journal of Power Electronics and Drive Systems
 
Aq33247251
IJERA Editor
 
Aq33247251
IJERA Editor
 
Bp36398403
IJERA Editor
 
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
IAES-IJPEDS
 
Dynamic voltage restorer (DVR) in a complex voltage disturbance compensation
International Journal of Power Electronics and Drive Systems
 
Dk36667674
IJERA Editor
 
Predictive Direct Power Control (PDPC) of Grid-connected Dual-active Bridge M...
International Journal of Power Electronics and Drive Systems
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
SultanAlSaiari1
 
Adaptability of Distribution Automation System to Electric Power Quality Moni...
IOSR Journals
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
elelijjournal
 
Impact of LCC–HVDC multiterminal on generator rotor angle stability
IJECEIAES
 
CPRI-Power quality report
Nageswar Rao
 
Review of DC Offset Compensation Techniques for Grid Connected Inverters
International Journal of Power Electronics and Drive Systems
 

More from Aditya Kumar Tripathy (7)

PPTX
SQL for interview
Aditya Kumar Tripathy
 
PPTX
Remote control using 4 channel Relay
Aditya Kumar Tripathy
 
PPT
Voice controlled Robot
Aditya Kumar Tripathy
 
PPTX
SUPERCONDUCTING MAGNETIC ENERGY STORAGE SYSTEM (SMES)
Aditya Kumar Tripathy
 
PPTX
Design and Implementation of a Robotic Vehicle With Real-Time Video Feedback ...
Aditya Kumar Tripathy
 
PPTX
Cell phone jammer
Aditya Kumar Tripathy
 
PPTX
Plasma antenna
Aditya Kumar Tripathy
 
SQL for interview
Aditya Kumar Tripathy
 
Remote control using 4 channel Relay
Aditya Kumar Tripathy
 
Voice controlled Robot
Aditya Kumar Tripathy
 
SUPERCONDUCTING MAGNETIC ENERGY STORAGE SYSTEM (SMES)
Aditya Kumar Tripathy
 
Design and Implementation of a Robotic Vehicle With Real-Time Video Feedback ...
Aditya Kumar Tripathy
 
Cell phone jammer
Aditya Kumar Tripathy
 
Plasma antenna
Aditya Kumar Tripathy
 

Recently uploaded (20)

PPTX
New ThousandEyes Product Innovations: Cisco Live June 2025
ThousandEyes
 
PDF
Doc9.....................................
SofiaCollazos
 
PPTX
Dev Dives: Automate, test, and deploy in one place—with Unified Developer Exp...
AndreeaTom
 
PDF
The Future of Artificial Intelligence (AI)
Mukul
 
PDF
Oracle AI Vector Search- Getting Started and what's new in 2025- AIOUG Yatra ...
Sandesh Rao
 
PPTX
Applied-Statistics-Mastering-Data-Driven-Decisions.pptx
parmaryashparmaryash
 
PDF
Responsible AI and AI Ethics - By Sylvester Ebhonu
Sylvester Ebhonu
 
PDF
Data_Analytics_vs_Data_Science_vs_BI_by_CA_Suvidha_Chaplot.pdf
CA Suvidha Chaplot
 
PDF
Using Anchore and DefectDojo to Stand Up Your DevSecOps Function
Anchore
 
PPTX
AI in Daily Life: How Artificial Intelligence Helps Us Every Day
vanshrpatil7
 
PPTX
IT Runs Better with ThousandEyes AI-driven Assurance
ThousandEyes
 
PDF
Advances in Ultra High Voltage (UHV) Transmission and Distribution Systems.pdf
Nabajyoti Banik
 
PPTX
OA presentation.pptx OA presentation.pptx
pateldhruv002338
 
PDF
How Open Source Changed My Career by abdelrahman ismail
a0m0rajab1
 
PPTX
AI and Robotics for Human Well-being.pptx
JAYMIN SUTHAR
 
PDF
How-Cloud-Computing-Impacts-Businesses-in-2025-and-Beyond.pdf
Artjoker Software Development Company
 
PDF
Unlocking the Future- AI Agents Meet Oracle Database 23ai - AIOUG Yatra 2025.pdf
Sandesh Rao
 
PDF
Cloud-Migration-Best-Practices-A-Practical-Guide-to-AWS-Azure-and-Google-Clou...
Artjoker Software Development Company
 
PDF
Presentation about Hardware and Software in Computer
snehamodhawadiya
 
PDF
Get More from Fiori Automation - What’s New, What Works, and What’s Next.pdf
Precisely
 
New ThousandEyes Product Innovations: Cisco Live June 2025
ThousandEyes
 
Doc9.....................................
SofiaCollazos
 
Dev Dives: Automate, test, and deploy in one place—with Unified Developer Exp...
AndreeaTom
 
The Future of Artificial Intelligence (AI)
Mukul
 
Oracle AI Vector Search- Getting Started and what's new in 2025- AIOUG Yatra ...
Sandesh Rao
 
Applied-Statistics-Mastering-Data-Driven-Decisions.pptx
parmaryashparmaryash
 
Responsible AI and AI Ethics - By Sylvester Ebhonu
Sylvester Ebhonu
 
Data_Analytics_vs_Data_Science_vs_BI_by_CA_Suvidha_Chaplot.pdf
CA Suvidha Chaplot
 
Using Anchore and DefectDojo to Stand Up Your DevSecOps Function
Anchore
 
AI in Daily Life: How Artificial Intelligence Helps Us Every Day
vanshrpatil7
 
IT Runs Better with ThousandEyes AI-driven Assurance
ThousandEyes
 
Advances in Ultra High Voltage (UHV) Transmission and Distribution Systems.pdf
Nabajyoti Banik
 
OA presentation.pptx OA presentation.pptx
pateldhruv002338
 
How Open Source Changed My Career by abdelrahman ismail
a0m0rajab1
 
AI and Robotics for Human Well-being.pptx
JAYMIN SUTHAR
 
How-Cloud-Computing-Impacts-Businesses-in-2025-and-Beyond.pdf
Artjoker Software Development Company
 
Unlocking the Future- AI Agents Meet Oracle Database 23ai - AIOUG Yatra 2025.pdf
Sandesh Rao
 
Cloud-Migration-Best-Practices-A-Practical-Guide-to-AWS-Azure-and-Google-Clou...
Artjoker Software Development Company
 
Presentation about Hardware and Software in Computer
snehamodhawadiya
 
Get More from Fiori Automation - What’s New, What Works, and What’s Next.pdf
Precisely
 

Protection of Converter Dense Power Systems

  • 1. PROTECTION OF CONVERTER DENSE POWER SYSTEMS PRESENTED BY:- RAJASHREE SAHOO REGD NO:- 1241019002 1
  • 2. Contents  Introduction  Definition of PECs  PECs Fault Response  Grid Code Requirements for PECs  Positive impact of PECs  Negative impact of PECs  Potential Protection Solutions  Conclusion  Reference 2
  • 3. INTRODUCTION  The number of Power Electronic Converter(PECs) utilised in power systems throughout the world is increasing.  PECs are found in a huge range of applications, in power systems they are used to interface Distributed Generation (DG) to the main power system and for fault current limiting/interruption applications.  These PEC interfaces generally have a low tolerance to overcurrent and rely on extremely fast acting protection which is integral to the PECs’ control systems.  The widespread introduction of PEC-interfaced energy sources has both positive and negative implications for network protection. 3
  • 4. 4 The task of a power converter is to process and control the flow of electric energy by supplying voltages and currents in a form that is optimally suited for the user loads. An ideal static converter controls the flow of power between the two sources with 100% efficiency. Power converter design aims at improving the efficiency. What are PECs? Image Courtesy : Ref[8]
  • 5. CONTD..  There are two types of sources: voltage and current sources. Any of these sources could be a generator or a receptor (load).  The principle of operation of a converter is based on the switch mode action of its switches. Commutations of the switches generate very fast current and/or voltage transients so that the transient behaviour of the sources is fundamental for converter design.  The transient behaviour of a source is characterized by its ability or inability to withstand steps generated by the external circuit in the voltage across its terminals or in the current flowing through it. Then new definitions could be stated: 5
  • 6. CONTD. a) A source is a voltage source if the voltage across its terminals can not undergo a discontinuity due to the external circuit variation. b) A source is a current source if the current flowing through it can not undergo a discontinuity due to the external circuit variation.  Minimizing the losses in the switches maximizes the efficiency of the converter.  These switches must have a voltage drop as low as possible in the ON- state, and a negligible leakage current in the OFF-state. 6
  • 7. PEC FAULT RESPONSE  A PEC’s response is governed by its control system i.e., how it should behave (in terms of fault current contribution during external faults). how it should behave (in terms of fault current contribution during external faults). 7 Fig. 2. PEC RMS Current Fault Response Image Courtesy: Ref[2] Fig. 3. PEC RMS Voltage Fault Response Image Courtesy: Ref[2]
  • 8. …CONTD  PECs typically share some general characteristics: they are often configured to attempt to “ride through” external faults, sometimes at the expense of providing significant levels of fault current.  A typical fault response for a PEC during a fault is shown in Fig. 2 and Fig. 3. 8
  • 9. 9 GRID CODE REQUIREMENTS FOR PECs Fig. 4. Grid Code - PEC ride through requirements for system voltage depressions Image Courtesy: Ref[2]
  • 10. CONTD..  The UK grid code specifies that a PEC should conform to the following parameters for faults on the transmission system:  “PECs should remain transiently stable and connected for faults up to and including close-up solid three-phase short circuit faults for up to 140ms. For faults in excess of 140ms a PEC should remain transiently stable and connected for voltage depressions anywhere on or above the heavy black line shown in Fig. 3. For faults involving voltage depressions, and corresponding times, below the black line, it is acceptable for the PEC to trip.”  During the period of the fault the PEC should provide maximum reactive current without exceeding its transient rating limit.  Duration and fault clearance times should be specified in a bilateral agreement between the PEC installer and the Distribution Network Operator (DNO).” 10
  • 11. POSITIVE IMPACT OF PECS ON POWER SYSTEM PROTECTION 11 While this research focuses primarily on the negative impact PECs have on power system protection there are a number of benefits to having PEC-dense power systems. PEC-interfaced DG normally limits the fault current contribution from the DG and in doing so limits the risk of damage during over current conditions. They also help mitigate certain protection issues:- 1. Reduction of Protection Blinding- Blinding of protection occurs when a protection device is unable to detect a fault due to fault current not being detected by its measurement transformer . Fig.5. Blinding of Protection Image Courtesy: Ref[2]
  • 12. 2. 12 Reduction of False Tripping -False tripping may occur when two or more lines are connected to a common bus. The PEC interface reduces the likelihood of this problem occurring by limiting the fault current from the DG as shown in Fig. 6. With the PEC interface in place the protective device on line 2 will measure a higher fault current than the device on line 1 and should trip faster. Fig.6. False Tripping Image Courtesy: Ref[2]
  • 13. NEGATIVE IMPACT OF PEC ON POWER SYSTEM PROTECTION  PECs have a low tolerance to overcurrent and their protection must therefore operate extremely quickly to avoid damage to their semiconductors during a fault. 13 Fig. 7. Fault on PEC Dense Power System Image Courtesy: Ref[2]
  • 14.  For a fault, as shown in Fig.7, there is a risk that the PEC protection will operate before downstream relays, either tripping or limiting the fault current.  Neither of these responses are desirable from a PEC/network protection coordination perspective.  Tripping before network protection relays will result in an unnecessary loss of load; fault current limiting may result in a sustained fault current condition wherein the fault current is not high enough to trip the overcurrent relays on the network. 14
  • 15. POTENTIAL PROTECTION SOLUTIONS  There are a number of potential solutions to the problems created for power system protection by PEC-interfaced sources:- A. Incorporation of Energy Storage Devices: One of the most significant problems with PEC interfaces is their lack of fault current contribution. Energy storage devices could be used to contribute to fault current and thus enable fault detection by conventional overcurrent relays as shown in Fig. 8. 15 Fig. 8.Energy storage fault current contribution Image Courtesy: Ref[2]
  • 16. B. Control of Fault Behaviour of PECs: 16 Fig. 9.PEC Fold Back Response Image Courtesy: Ref[2] Fig.10. PEC Brickwalling Response Image Courtesy: Ref[2]
  • 17.  Fold back is a method for controlling the fault current provided by the PEC. All of the control is carried out internally by the PEC’s control system.  Directly after the fault, the control system allows the PEC current output to peak; the peak being dependent on the capabilities of the PEC switches and the source supplying the PEC.  This peak fault current level is sustained for a short period of time in an attempt to operate overcurrent protection devices while limiting damage to the PEC’s power electronics.  The brickwalling response differs from fold back in several ways: the fault current output is sustained at a lower level for a longer duration and the output current isn’t reduced to a level less than load current to facilitate switchgear interruption 17
  • 18. CONCLUSION  A description of the behaviour of PECs during faults, both in terms of fault current and response time has been presented and the positive and negative impacts.  One of the main objectives of this research is to determine the level of PEC proliferation at which the overall protection system may begin to experience problems and to investigate solutions that could be used to mitigate such problems. 18
  • 19. REFERENCES [1] L. Freeris and D. Infield, "Renewable Energy in Power Systems," 1st ed Chichester: John Wiley & Sons Ltd, 2008, pp. 122, 133, 192, 144-145. [2] J. Morren and S. W. H. de Haan, "Impact of distributed generation units with power electronic converters on distribution network protection," in Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on, 2008, pp. 664669. [3] The Grid Code, Issue 4 Revision 1, Connection Conditions, N. G. E. Transmission, 2009. [4] H. Wan, K. P. Wong, and C. Y. Chung, "Multi-agent application in protection coordination of power system with distributed generations," in Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE, 2008, pp. 1-6. [5] J. R. S. S. Kumara, A. Atputharajah, J. B. Ekanayake, and F. J. Mumford, "Over current protection coordination of distribution networks with fault current limiters," in Power Engineering Society General Meeting, 2006. IEEE, 2006, p. 8 pp. 19
  • 20. REFERENCES [6] S. M. Blair, A. J. Roscoe, C. D. Booth, G. M. Burt, A. Teo, and C. G. Bright, "Implications of Fault Current Limitation for Electrical Distribution Networks," Developments in Power System Protection, pp. 1- 5, 2010. [7] K. Kauhaniemi and L. Kumpulainen, "Impact of distributed generation on the protection of distribution networks," in Developments in Power System Protection, 2004. Eighth IEE International Conference on, 2004, pp. 315-318 Vol.1. [8] F. Bordry CERN, Geneva, Switzerland , “Power converters: definitions, classification and converter topologies” . 20