Assignment - 1
Q1. A balanced star connected load of (3+j4) per phase is connected to a balanced 3-phase, 415V supply.
Find the line currents and the power absorbed by the load. Find also the total reactive power and
apparent power. Assume A-B-C phase sequence. Draw the phasor diagram.
Sol:
Figure 1: Circuit Diagram of 3 phase star connected load
a) To nd line currents:
Phase Impedances:
ZAN = ZBN = ZCN = (3 + j4)Ω = 5∠53.13◦
Ω
Phase Voltage:
|Vph| = VLL =
415
√
3
= 239.6V
∴ VAN = 239.6∠0◦
V , VBN = 239.6∠ − 120◦
V , VCN = 239.6∠120◦
V .
Phase currents:
∴ IA =
VAN
ZAN
=
239.6∠0◦
5∠53.13◦
= 47.92∠ − 53.13◦
A
∴ IB =
VBN
ZBN
=
239.6∠ − 120◦
5∠53.13◦
= 47.92∠ − 173.13◦
A
1
∴ IC =
VCN
ZCN
=
239.6∠120◦
5∠53.13◦
= 47.92∠66.87◦
A
Hence Line currents :
|IA| = |IB| = |IC| = |IL| = |Iph| = 47.92A
b)To nd power absorbed by the load, total reactive power and apparent power:
Active Power(P), Reactive(Q) and Apparent Power(S):
P = 3VphIph cos φ =?
cos φ =
Rph
|Zph|
=
3
5
= 0.6
Lagging as it is +ve jXL.
∴ P = 3 × 239.6 × 47.92 × 0.6 = 20, 667W = 20.67kW
Hence absorbed power by the load = 20.67kW
φ = cos−1
(0.6) = 53.13◦
∴ sin φ = sin(53.13◦
) = 0.8
∴ Q = 3VphIph sin φ = 3 × 239.6 × 47.92 × 0.8 = 27, 544W = 27.54kW
Hence total reactive power = 27.54kW
To calculate Apparent Power (S):
S2
= P2
+ Q2
∴ S = P2 + Q2 = ((20, 667)2 + (27, 544)2) = 34, 435W = 34.44kW
Apparent Power = 34.44kW
2
c) Phasor Diagram:
Figure 2: Phasor Diagram for phase voltages
From phasor diagram:
VAB = VAN + (−VBN )
∴ VAB = VAN − VBN
∴ VAB = 239.6∠0◦
− 239.6∠ − 120◦
= 415∠ − 30◦
V
Q2. A three-phase balanced delta connected coil having a resistance of4Ω per phase and inductance
of 25.46mH per phase is connected across 415V, 50 Hz, three-phase supply. Determine the phase cur-
rents and line currents. Also calculate total active, reactive and apparent power. Assume A-B-C phase
sequence.
Sol:
For Delta :
VL = Vph
IL =
√
3Iph
XL = ωL = 2πfL = 2π × 50 × 25.46 × 10−3
= 8Ω
a)To compute phase currents:
3
Phase impedances:
ZAB = ZBC = ZCA = Zph = 4 + j8Ω = 8.94∠63.43◦
Ω
Figure 3: Circuit Diagram for 3 phase delta connected load
Phase voltages:
|VL| = |Vph| = 415V
∴ VAB = 415∠0◦
, VBC = 415∠ − 120◦
, VCB = 415∠120◦
Phase currents:
∴ IAB =
VAB
ZAB
=
415∠0◦
8.94∠63.43◦
= 46.42∠ − 63.43◦
A
∴ IBC =
VBC
ZBC
=
415∠ − 120◦
8.94∠63.43◦
= 46.42∠ − 183.43◦
A
∴ ICA =
VCA
ZCA
=
415∠120◦
8.94∠63.43◦
= 46.42∠56.57◦
A
b)To compute line currents:
∴Line currents:
|IL| =
√
3|Iph| =
√
3 × 46.42 = 80.4A
Apply KCL at node A:
IA + ICA = IAB
4
∴ IA = IAB − ICA = 46.42∠ − 63.43◦
− 46.42∠56.57◦
IA = (20.76 − j41.52) − (25.57 + j38.74) = −4.81 − j80.26
IA = 80.4∠ − 93.4◦
A
Similarly for IB and IC:
IB = 80.4∠ − 213.4◦
A delayed by 120◦
IC = 80.4∠ − 333.4◦
A delayed by 120◦
c) To calculate total active, reactive and apparent power:
Active Power (P) = 3VphIph cos φ
cos φ =
Rph
Zph
=
4
8.94
= 0.447
∴ P = 3 × 415 × 46.32 × 0.447 = 25, 710W = 25.7kW
φ = cos−1
(0.447) = 63.44◦
∴ sin φ = sin(63.44◦
) = 0.894
Reactive Power (Q) = 3VphIph sin φ
∴ Q = 3 × 415 × 46.32 × 0.894 = 51, 555W = 51.6kW
Apparent Power (S):
S2
= P2
+ Q2
∴ S = P2 + Q2 = ((25, 710)2 + (51, 555)2) = 57, 610W = 57.6kW
Q3 A three-phase 415V, 50Hz supply is connected to a factory which has a star connected motor requiring
30 kVA at a power factor of 0.8 lagging and a heating load (balanced) star connected requiring 7kW per
5
phase. Calculate the power drawn from the supply and the capacitance per phase necessary to obtain
unity power factor of the combined load.
Sol:
a) To nd power drawn from supply:
Load 1 - Induction motor, 30kVA, cosφ = 0.8, Y - connected
Load 2 - Heating load, 7kW/phase, Y - connected
Table 1: Data to calculate required variables
Load Active Power(P) Reactive Power(Q) Apparent Power (S) cosφ φ
Induction motor Scosφ Ptanφ 30kVA 0.8 (lag) φ=cos−1
0.8
= 30 × 0.8 = 24 × tan(36.86◦
) = 36.86◦
= 24kW = 18kVAr
Heating load 7 × 3 = 21kW 0 1 0
45kW 18kVAr
Hence, Power drawn from supply = 24+21= 45kW
b) The capacitance per phase necessary to obtain unity power factor of the combined load:
Power factor correction:
Figure 4: Power factor triangle
tanφ1 =
18
45
= 0.4
φ1 = tan−1
(0.4) = 21.8◦
cos φ1 = cos(21.8◦
) = 0.928
6
(lag)
In order to raise power factor to 1,
cos φ2 = 1, φ2 = 0◦
∴Leading kVAr supplied by the capacitor bank : Qc = P[tanφ1 − tanφ2]
Qc = 45, 000[tan(21.8◦
) − tan(0◦
)] = 18, 000V Ar
Qc =
3V 2
ph
Xc
Rearranging Qcgives:
Xc =
3V 2
ph
Qc
=
(3 × 239.62
)
18, 000
= 9.57Ω
Hence capacitance per phase in order to obtain unity power factor of combined load:
C =
1
ωXc
=
1
2π50 × 9.57
= 3.32 × 10−4
F = 0.33mF
Q4. The power input to a 2000 V, 50 Hz, three-phase motor running on a full-load at an eciency of 90%
is measured by two wattmeters. If the readings on the wattmeters are 300 kW and 100 kW respectively,
nd
a) Input power b) Power factor c) Line current d) Output power e) Per-phase Impedance of the load.
Sol:
a) To nd input power:
Pin = W1 + W2 = 300 + 100 = 400kW
Hence input power = 400,000W
b)To nd Power factor:
tanφ =
√
3[
W1 − W2
W1 + W2
]
tanφ =
√
3[
300 − 100
300 + 100
] =
√
3[
200
400
] =
√
3 × 0.5
7
∴ tanφ = 0.866
φ = tan−1
0.866 = 40.9◦
power factor = cos φ = cos(40.9◦
) = 0.76 (lag)
c)To calculate Line Current:
P =
√
3|VL||IL| cos φ
∴ IL =
P
(
√
3|VL| cos φ)
=
400, 000
(
√
3 × 2000 × 0.76)
∴ IL = 151.93A
d)To nd the output power:
Pout = η × Pin
Pout = 0.9 × 400 = 360kW
e)To calculate per phase impedance of the load:
It is assumed the induction motor load to have arranged in Delta Connection.
So, VL = Vph and IL =
√
3Iph.
Iph =
IL
√
3
=
151.93
√
3
∴ |Iph| = 87.71A
Hence, per phase impedance of the load (Zph):
Vph = |Iph||Zph|
8
∴ |Zph| =
2000
87.71
= 22.8Ω
∴ Zph = 22.8∠40.9◦
Ω = (17.23 + j14.93)Ω
Q5. Write a short note on a) constructional details and types of synchronous generator b) Excitation
scheme
Sol:
a) Constructional details and types of synchronous generator:
The function of the synchronous generator is to convert mechanical energy from the turbine into electrical
energy. This type of generator requires a winding that will carry direct current (or in small sizes a series
of permanent magnets) in order to generate the magnetic ux. In most of the machinery, this excitation
winding (known as the eld winding) is carried on the rotor at frequency of 50-60Hz, in order to rotate
at synchronous speed. The synchronous generator consists of 2 parts:
1. Stator: Stator carries 3-phase armature windings (it is where the main voltage is induced). It is
connected to the AC power supply. The armature windings are physically displaced from each other
by 120 degrees. At the terminals of the armature, 3 phase power is obtained.
2. Rotor: Rotor carries eld windings (responsible for generating main magnetic eld). It is connected
to an external DC source via slip rings and brushes or from special DC source mounted directly
on the shaft of the machine. Once the rotor or the eld poles are made to rotate in the presence
of armature windings placed on the stator, an alternating 3 phase voltage induced in the armature
conductors thus resulting in the generation of 3 phase electrical power.
Figure 5: Types of Synchronous Generator
There are mainly two types of synchronous generator based on the type of rotor used in construction:
9
1. Hydro generators or salient pole type generators: These machines makes use of salient pole type
rotor. They are driven by water turbines at a speed ranging from 50 to 1000 rev/min. The speed
is dependent on the type of turbine, which in turn depends on the head and the ow rate of the
availability of water. At low speeds, the permissible rotor diameter will be several times its active
length. Generally, the largest allowable diameter of rotor is used to maximize the machine's inertia
which is an important part of governing the water turbine. Outputs up to 800MW have been
achieved.
2. Turbo generators or non-salient pole type generators: These machines use a cylindrical rotor in
which the eld winding is placed in axial slots. They are invariably driven by a steam turbine or
a gas turbine. At ratings below 60MW a gear box may be used to provide a rotational speed of
3600 (2 pole) or 1800 rev/min (4 pole) to provide power at 60 Hz, or 3000 rev/min (2 pole) or 1500
rev/min (4 pole) to provide power at 50 Hz. Smaller machines may use a laminated construction
for the rotor while larger machines will use a forged rotor. A feature of these machines is that their
length is several times their diameter. Power outputs range from a few megawatts up to about
1500MW.
b) Excitation schemes:
Any electric generators or motors consists of a rotor spinning in a magnetic eld. The magnetic eld can
be generated by permanent magnets or by eld coils. In the case of a machine with eld coils, current
must ow in the coils to generate the eld. This is to ensure power transfer to take place, in or out of
the rotor. The process of generating a magnetic eld via means of an electric current is called excitation.
Mainly two types of excitation schemes are used in the power stations:
1. Separate excitation: For large or older generators, it is usual for a separate exciter dynamo to be
operated in conjunction with the main power generator. It is a small permanent-magnet or battery-
excited dynamo that produces the eld current for the larger generator.
10
Figure 6: Circuit of separately excited generator
2. Self excitation: Modern generators with eld coils are self-excited. Some of the power output from
the rotor is used to power the eld coils. The magnetism is retained by the rotor iron even after the
generator is turned o. The generator is initially started with no load connected to it. The initial weak
eld creates a weak voltage in the stator coils, which in turn increases the eld current, until the machine
shoots to full voltage.
Figure 7: Circuit of self excited generator
11

More Related Content

What's hot (20)

PPT
3 reactive power and voltage control
8141245710
 
PPTX
Single Line Diagram.pptx
MAHMOUDMOHAMED431205
 
PPTX
Basics of Electrical Engineering 4th Module Generation of Power
ktustudents
 
PPT
Chapter 7 1
Kiya Alemayehu
 
PDF
Power system fault analysis ppt
karikalan123
 
PPTX
HVDC UNIT-II.pptx
DeivanayakiRAssistan
 
PPTX
Grid integration issues and solutions
Swathi Venugopal
 
PPTX
Power quality 1
Md Irshad Ahmad
 
PPTX
Gauss Siedel method of Load Flow
Abdul Azeem
 
PPTX
Solar Power Based Micro Grid Systems.pptx
Niuru Ranaweera
 
PPTX
Vk
venkatdon
 
DOCX
Analysis of 12 pulse phase control ac dc converter
Asoka Technologies
 
PPTX
MPPT
MANISH BARTHWAL
 
PPTX
Types of conductor
sneh pratap singh
 
PDF
Synhronous motor equivalent circuit
Dr.Raja Masood Larik
 
PDF
Setp by step design of transformer
binodsahu8
 
PPTX
Ac distribution system
Daffodil International University
 
PDF
MCC Motor Control Center 1
Sakshi Vashist
 
PPTX
Power systems voltage and power control
Caner Göksel Sonuzun
 
PPTX
Chapter 5 corona
firaoltemesgen1
 
3 reactive power and voltage control
8141245710
 
Single Line Diagram.pptx
MAHMOUDMOHAMED431205
 
Basics of Electrical Engineering 4th Module Generation of Power
ktustudents
 
Chapter 7 1
Kiya Alemayehu
 
Power system fault analysis ppt
karikalan123
 
HVDC UNIT-II.pptx
DeivanayakiRAssistan
 
Grid integration issues and solutions
Swathi Venugopal
 
Power quality 1
Md Irshad Ahmad
 
Gauss Siedel method of Load Flow
Abdul Azeem
 
Solar Power Based Micro Grid Systems.pptx
Niuru Ranaweera
 
Analysis of 12 pulse phase control ac dc converter
Asoka Technologies
 
Types of conductor
sneh pratap singh
 
Synhronous motor equivalent circuit
Dr.Raja Masood Larik
 
Setp by step design of transformer
binodsahu8
 
Ac distribution system
Daffodil International University
 
MCC Motor Control Center 1
Sakshi Vashist
 
Power systems voltage and power control
Caner Göksel Sonuzun
 
Chapter 5 corona
firaoltemesgen1
 

Similar to Three phase balanced load circuits and synchronous generators (20)

PPTX
class notes of electrical & electronics.pptx
gayathri venkataramani
 
PPTX
lec7 (1).pptx
Devesh39220
 
PPT
Unit4 -Power supplies on electronics.ppt
sandertein
 
PDF
Transformers and Induction Motors
Isham Rashik
 
PPT
10 three phase system.ppt
OXYMORON4
 
PDF
Concept of ac circuit for electrical engineering and this help to study about...
saiyadippu
 
PPT
UNIT-III complex reactive three phase.ppt
Abinaya Saraswathy T
 
PPTX
Synchronous machine
Bharath Sugumar
 
PPT
Lecture 2
Forward2025
 
PPT
Power system analysis complex power reactive compensation
HariharasudhanAnnadu
 
PPTX
Power relationship (Electrical Engineering)
MOHAMMADSHOAIBBABAR
 
PDF
E L E C T R I C A L M A C H I N E S I I I J N T U M O D E L P A P E R{Www
guest3f9c6b
 
PDF
Electrical Machines Iii Jntu Model Paper{Www.Studentyogi.Com}
guest3f9c6b
 
PPT
Introduction to Power systems lecture1 slide.ppt
GetahunShankoKefeni
 
DOC
120102011
mkazree
 
DOC
Bee questionbank
Modugu Srinivas
 
PPT
132232442681497329.pptfgggggggggggggggggg
majidmajeed17
 
PPT
Unit 1
W3Edify
 
PPT
Chapter 02 Fundamentals PS [Autosaved].ppt
Mohd Ishak
 
class notes of electrical & electronics.pptx
gayathri venkataramani
 
lec7 (1).pptx
Devesh39220
 
Unit4 -Power supplies on electronics.ppt
sandertein
 
Transformers and Induction Motors
Isham Rashik
 
10 three phase system.ppt
OXYMORON4
 
Concept of ac circuit for electrical engineering and this help to study about...
saiyadippu
 
UNIT-III complex reactive three phase.ppt
Abinaya Saraswathy T
 
Synchronous machine
Bharath Sugumar
 
Lecture 2
Forward2025
 
Power system analysis complex power reactive compensation
HariharasudhanAnnadu
 
Power relationship (Electrical Engineering)
MOHAMMADSHOAIBBABAR
 
E L E C T R I C A L M A C H I N E S I I I J N T U M O D E L P A P E R{Www
guest3f9c6b
 
Electrical Machines Iii Jntu Model Paper{Www.Studentyogi.Com}
guest3f9c6b
 
Introduction to Power systems lecture1 slide.ppt
GetahunShankoKefeni
 
120102011
mkazree
 
Bee questionbank
Modugu Srinivas
 
132232442681497329.pptfgggggggggggggggggg
majidmajeed17
 
Unit 1
W3Edify
 
Chapter 02 Fundamentals PS [Autosaved].ppt
Mohd Ishak
 
Ad

More from Isham Rashik (20)

PDF
Text Preprocessing - 1
Isham Rashik
 
PDF
9608 Computer Science Cambridge International AS level Pre-Release May June p...
Isham Rashik
 
PDF
Fundamentals of Cryptography - Caesar Cipher - Python
Isham Rashik
 
PDF
Python 3.x Dictionaries and Sets Cheatsheet
Isham Rashik
 
PDF
HackerRank Repeated String Problem
Isham Rashik
 
PDF
Operations Management - BSB INC - Case Study
Isham Rashik
 
PDF
Corporate Finance - Disney Sea Park Project
Isham Rashik
 
PDF
Questionnaire - Why women entrepreneurs are happier than men?
Isham Rashik
 
PDF
Human Resource Management - Different Interview Techniques
Isham Rashik
 
PDF
Python 3.x File Object Manipulation Cheatsheet
Isham Rashik
 
PDF
Android Application Development - Level 3
Isham Rashik
 
PDF
Android Application Development - Level 2
Isham Rashik
 
PDF
Android Application Development - Level 1
Isham Rashik
 
PDF
Managerial Skills Presentation - Elon Musk
Isham Rashik
 
PDF
Operations Management - Business Process Reengineering - Example
Isham Rashik
 
PPTX
Lighting Design - Theory and Calculations
Isham Rashik
 
PDF
Linear Control Hard-Disk Read/Write Controller Assignment
Isham Rashik
 
PPTX
Circuit Breakers for Low Voltage Applications
Isham Rashik
 
PDF
Linux Commands - Cheat Sheet
Isham Rashik
 
PPTX
Ratio Analysis - Case Study - ITC LTD
Isham Rashik
 
Text Preprocessing - 1
Isham Rashik
 
9608 Computer Science Cambridge International AS level Pre-Release May June p...
Isham Rashik
 
Fundamentals of Cryptography - Caesar Cipher - Python
Isham Rashik
 
Python 3.x Dictionaries and Sets Cheatsheet
Isham Rashik
 
HackerRank Repeated String Problem
Isham Rashik
 
Operations Management - BSB INC - Case Study
Isham Rashik
 
Corporate Finance - Disney Sea Park Project
Isham Rashik
 
Questionnaire - Why women entrepreneurs are happier than men?
Isham Rashik
 
Human Resource Management - Different Interview Techniques
Isham Rashik
 
Python 3.x File Object Manipulation Cheatsheet
Isham Rashik
 
Android Application Development - Level 3
Isham Rashik
 
Android Application Development - Level 2
Isham Rashik
 
Android Application Development - Level 1
Isham Rashik
 
Managerial Skills Presentation - Elon Musk
Isham Rashik
 
Operations Management - Business Process Reengineering - Example
Isham Rashik
 
Lighting Design - Theory and Calculations
Isham Rashik
 
Linear Control Hard-Disk Read/Write Controller Assignment
Isham Rashik
 
Circuit Breakers for Low Voltage Applications
Isham Rashik
 
Linux Commands - Cheat Sheet
Isham Rashik
 
Ratio Analysis - Case Study - ITC LTD
Isham Rashik
 
Ad

Recently uploaded (20)

PPTX
Element 11. ELECTRICITY safety and hazards
merrandomohandas
 
PDF
Water Industry Process Automation & Control Monthly July 2025
Water Industry Process Automation & Control
 
PDF
AI TECHNIQUES FOR IDENTIFYING ALTERATIONS IN THE HUMAN GUT MICROBIOME IN MULT...
vidyalalltv1
 
PPTX
Depth First Search Algorithm in 🧠 DFS in Artificial Intelligence (AI)
rafeeqshaik212002
 
DOCX
CS-802 (A) BDH Lab manual IPS Academy Indore
thegodhimself05
 
PPT
Carmon_Remote Sensing GIS by Mahesh kumar
DhananjayM6
 
PPTX
Arduino Based Gas Leakage Detector Project
CircuitDigest
 
PPTX
Introduction to Design of Machine Elements
PradeepKumarS27
 
PPTX
Heart Bleed Bug - A case study (Course: Cryptography and Network Security)
Adri Jovin
 
PDF
MAD Unit - 2 Activity and Fragment Management in Android (Diploma IT)
JappanMavani
 
PPTX
美国电子版毕业证南卡罗莱纳大学上州分校水印成绩单USC学费发票定做学位证书编号怎么查
Taqyea
 
PPTX
Solar Thermal Energy System Seminar.pptx
Gpc Purapuza
 
PDF
Viol_Alessandro_Presentazione_prelaurea.pdf
dsecqyvhbowrzxshhf
 
PDF
Pressure Measurement training for engineers and Technicians
AIESOLUTIONS
 
PDF
Biomechanics of Gait: Engineering Solutions for Rehabilitation (www.kiu.ac.ug)
publication11
 
PPTX
The Role of Information Technology in Environmental Protectio....pptx
nallamillisriram
 
PDF
GTU Civil Engineering All Semester Syllabus.pdf
Vimal Bhojani
 
PPTX
Damage of stability of a ship and how its change .pptx
ehamadulhaque
 
DOC
MRRS Strength and Durability of Concrete
CivilMythili
 
PPTX
Hashing Introduction , hash functions and techniques
sailajam21
 
Element 11. ELECTRICITY safety and hazards
merrandomohandas
 
Water Industry Process Automation & Control Monthly July 2025
Water Industry Process Automation & Control
 
AI TECHNIQUES FOR IDENTIFYING ALTERATIONS IN THE HUMAN GUT MICROBIOME IN MULT...
vidyalalltv1
 
Depth First Search Algorithm in 🧠 DFS in Artificial Intelligence (AI)
rafeeqshaik212002
 
CS-802 (A) BDH Lab manual IPS Academy Indore
thegodhimself05
 
Carmon_Remote Sensing GIS by Mahesh kumar
DhananjayM6
 
Arduino Based Gas Leakage Detector Project
CircuitDigest
 
Introduction to Design of Machine Elements
PradeepKumarS27
 
Heart Bleed Bug - A case study (Course: Cryptography and Network Security)
Adri Jovin
 
MAD Unit - 2 Activity and Fragment Management in Android (Diploma IT)
JappanMavani
 
美国电子版毕业证南卡罗莱纳大学上州分校水印成绩单USC学费发票定做学位证书编号怎么查
Taqyea
 
Solar Thermal Energy System Seminar.pptx
Gpc Purapuza
 
Viol_Alessandro_Presentazione_prelaurea.pdf
dsecqyvhbowrzxshhf
 
Pressure Measurement training for engineers and Technicians
AIESOLUTIONS
 
Biomechanics of Gait: Engineering Solutions for Rehabilitation (www.kiu.ac.ug)
publication11
 
The Role of Information Technology in Environmental Protectio....pptx
nallamillisriram
 
GTU Civil Engineering All Semester Syllabus.pdf
Vimal Bhojani
 
Damage of stability of a ship and how its change .pptx
ehamadulhaque
 
MRRS Strength and Durability of Concrete
CivilMythili
 
Hashing Introduction , hash functions and techniques
sailajam21
 

Three phase balanced load circuits and synchronous generators

  • 1. Assignment - 1 Q1. A balanced star connected load of (3+j4) per phase is connected to a balanced 3-phase, 415V supply. Find the line currents and the power absorbed by the load. Find also the total reactive power and apparent power. Assume A-B-C phase sequence. Draw the phasor diagram. Sol: Figure 1: Circuit Diagram of 3 phase star connected load a) To nd line currents: Phase Impedances: ZAN = ZBN = ZCN = (3 + j4)Ω = 5∠53.13◦ Ω Phase Voltage: |Vph| = VLL = 415 √ 3 = 239.6V ∴ VAN = 239.6∠0◦ V , VBN = 239.6∠ − 120◦ V , VCN = 239.6∠120◦ V . Phase currents: ∴ IA = VAN ZAN = 239.6∠0◦ 5∠53.13◦ = 47.92∠ − 53.13◦ A ∴ IB = VBN ZBN = 239.6∠ − 120◦ 5∠53.13◦ = 47.92∠ − 173.13◦ A 1
  • 2. ∴ IC = VCN ZCN = 239.6∠120◦ 5∠53.13◦ = 47.92∠66.87◦ A Hence Line currents : |IA| = |IB| = |IC| = |IL| = |Iph| = 47.92A b)To nd power absorbed by the load, total reactive power and apparent power: Active Power(P), Reactive(Q) and Apparent Power(S): P = 3VphIph cos φ =? cos φ = Rph |Zph| = 3 5 = 0.6 Lagging as it is +ve jXL. ∴ P = 3 × 239.6 × 47.92 × 0.6 = 20, 667W = 20.67kW Hence absorbed power by the load = 20.67kW φ = cos−1 (0.6) = 53.13◦ ∴ sin φ = sin(53.13◦ ) = 0.8 ∴ Q = 3VphIph sin φ = 3 × 239.6 × 47.92 × 0.8 = 27, 544W = 27.54kW Hence total reactive power = 27.54kW To calculate Apparent Power (S): S2 = P2 + Q2 ∴ S = P2 + Q2 = ((20, 667)2 + (27, 544)2) = 34, 435W = 34.44kW Apparent Power = 34.44kW 2
  • 3. c) Phasor Diagram: Figure 2: Phasor Diagram for phase voltages From phasor diagram: VAB = VAN + (−VBN ) ∴ VAB = VAN − VBN ∴ VAB = 239.6∠0◦ − 239.6∠ − 120◦ = 415∠ − 30◦ V Q2. A three-phase balanced delta connected coil having a resistance of4Ω per phase and inductance of 25.46mH per phase is connected across 415V, 50 Hz, three-phase supply. Determine the phase cur- rents and line currents. Also calculate total active, reactive and apparent power. Assume A-B-C phase sequence. Sol: For Delta : VL = Vph IL = √ 3Iph XL = ωL = 2πfL = 2π × 50 × 25.46 × 10−3 = 8Ω a)To compute phase currents: 3
  • 4. Phase impedances: ZAB = ZBC = ZCA = Zph = 4 + j8Ω = 8.94∠63.43◦ Ω Figure 3: Circuit Diagram for 3 phase delta connected load Phase voltages: |VL| = |Vph| = 415V ∴ VAB = 415∠0◦ , VBC = 415∠ − 120◦ , VCB = 415∠120◦ Phase currents: ∴ IAB = VAB ZAB = 415∠0◦ 8.94∠63.43◦ = 46.42∠ − 63.43◦ A ∴ IBC = VBC ZBC = 415∠ − 120◦ 8.94∠63.43◦ = 46.42∠ − 183.43◦ A ∴ ICA = VCA ZCA = 415∠120◦ 8.94∠63.43◦ = 46.42∠56.57◦ A b)To compute line currents: ∴Line currents: |IL| = √ 3|Iph| = √ 3 × 46.42 = 80.4A Apply KCL at node A: IA + ICA = IAB 4
  • 5. ∴ IA = IAB − ICA = 46.42∠ − 63.43◦ − 46.42∠56.57◦ IA = (20.76 − j41.52) − (25.57 + j38.74) = −4.81 − j80.26 IA = 80.4∠ − 93.4◦ A Similarly for IB and IC: IB = 80.4∠ − 213.4◦ A delayed by 120◦ IC = 80.4∠ − 333.4◦ A delayed by 120◦ c) To calculate total active, reactive and apparent power: Active Power (P) = 3VphIph cos φ cos φ = Rph Zph = 4 8.94 = 0.447 ∴ P = 3 × 415 × 46.32 × 0.447 = 25, 710W = 25.7kW φ = cos−1 (0.447) = 63.44◦ ∴ sin φ = sin(63.44◦ ) = 0.894 Reactive Power (Q) = 3VphIph sin φ ∴ Q = 3 × 415 × 46.32 × 0.894 = 51, 555W = 51.6kW Apparent Power (S): S2 = P2 + Q2 ∴ S = P2 + Q2 = ((25, 710)2 + (51, 555)2) = 57, 610W = 57.6kW Q3 A three-phase 415V, 50Hz supply is connected to a factory which has a star connected motor requiring 30 kVA at a power factor of 0.8 lagging and a heating load (balanced) star connected requiring 7kW per 5
  • 6. phase. Calculate the power drawn from the supply and the capacitance per phase necessary to obtain unity power factor of the combined load. Sol: a) To nd power drawn from supply: Load 1 - Induction motor, 30kVA, cosφ = 0.8, Y - connected Load 2 - Heating load, 7kW/phase, Y - connected Table 1: Data to calculate required variables Load Active Power(P) Reactive Power(Q) Apparent Power (S) cosφ φ Induction motor Scosφ Ptanφ 30kVA 0.8 (lag) φ=cos−1 0.8 = 30 × 0.8 = 24 × tan(36.86◦ ) = 36.86◦ = 24kW = 18kVAr Heating load 7 × 3 = 21kW 0 1 0 45kW 18kVAr Hence, Power drawn from supply = 24+21= 45kW b) The capacitance per phase necessary to obtain unity power factor of the combined load: Power factor correction: Figure 4: Power factor triangle tanφ1 = 18 45 = 0.4 φ1 = tan−1 (0.4) = 21.8◦ cos φ1 = cos(21.8◦ ) = 0.928 6
  • 7. (lag) In order to raise power factor to 1, cos φ2 = 1, φ2 = 0◦ ∴Leading kVAr supplied by the capacitor bank : Qc = P[tanφ1 − tanφ2] Qc = 45, 000[tan(21.8◦ ) − tan(0◦ )] = 18, 000V Ar Qc = 3V 2 ph Xc Rearranging Qcgives: Xc = 3V 2 ph Qc = (3 × 239.62 ) 18, 000 = 9.57Ω Hence capacitance per phase in order to obtain unity power factor of combined load: C = 1 ωXc = 1 2π50 × 9.57 = 3.32 × 10−4 F = 0.33mF Q4. The power input to a 2000 V, 50 Hz, three-phase motor running on a full-load at an eciency of 90% is measured by two wattmeters. If the readings on the wattmeters are 300 kW and 100 kW respectively, nd a) Input power b) Power factor c) Line current d) Output power e) Per-phase Impedance of the load. Sol: a) To nd input power: Pin = W1 + W2 = 300 + 100 = 400kW Hence input power = 400,000W b)To nd Power factor: tanφ = √ 3[ W1 − W2 W1 + W2 ] tanφ = √ 3[ 300 − 100 300 + 100 ] = √ 3[ 200 400 ] = √ 3 × 0.5 7
  • 8. ∴ tanφ = 0.866 φ = tan−1 0.866 = 40.9◦ power factor = cos φ = cos(40.9◦ ) = 0.76 (lag) c)To calculate Line Current: P = √ 3|VL||IL| cos φ ∴ IL = P ( √ 3|VL| cos φ) = 400, 000 ( √ 3 × 2000 × 0.76) ∴ IL = 151.93A d)To nd the output power: Pout = η × Pin Pout = 0.9 × 400 = 360kW e)To calculate per phase impedance of the load: It is assumed the induction motor load to have arranged in Delta Connection. So, VL = Vph and IL = √ 3Iph. Iph = IL √ 3 = 151.93 √ 3 ∴ |Iph| = 87.71A Hence, per phase impedance of the load (Zph): Vph = |Iph||Zph| 8
  • 9. ∴ |Zph| = 2000 87.71 = 22.8Ω ∴ Zph = 22.8∠40.9◦ Ω = (17.23 + j14.93)Ω Q5. Write a short note on a) constructional details and types of synchronous generator b) Excitation scheme Sol: a) Constructional details and types of synchronous generator: The function of the synchronous generator is to convert mechanical energy from the turbine into electrical energy. This type of generator requires a winding that will carry direct current (or in small sizes a series of permanent magnets) in order to generate the magnetic ux. In most of the machinery, this excitation winding (known as the eld winding) is carried on the rotor at frequency of 50-60Hz, in order to rotate at synchronous speed. The synchronous generator consists of 2 parts: 1. Stator: Stator carries 3-phase armature windings (it is where the main voltage is induced). It is connected to the AC power supply. The armature windings are physically displaced from each other by 120 degrees. At the terminals of the armature, 3 phase power is obtained. 2. Rotor: Rotor carries eld windings (responsible for generating main magnetic eld). It is connected to an external DC source via slip rings and brushes or from special DC source mounted directly on the shaft of the machine. Once the rotor or the eld poles are made to rotate in the presence of armature windings placed on the stator, an alternating 3 phase voltage induced in the armature conductors thus resulting in the generation of 3 phase electrical power. Figure 5: Types of Synchronous Generator There are mainly two types of synchronous generator based on the type of rotor used in construction: 9
  • 10. 1. Hydro generators or salient pole type generators: These machines makes use of salient pole type rotor. They are driven by water turbines at a speed ranging from 50 to 1000 rev/min. The speed is dependent on the type of turbine, which in turn depends on the head and the ow rate of the availability of water. At low speeds, the permissible rotor diameter will be several times its active length. Generally, the largest allowable diameter of rotor is used to maximize the machine's inertia which is an important part of governing the water turbine. Outputs up to 800MW have been achieved. 2. Turbo generators or non-salient pole type generators: These machines use a cylindrical rotor in which the eld winding is placed in axial slots. They are invariably driven by a steam turbine or a gas turbine. At ratings below 60MW a gear box may be used to provide a rotational speed of 3600 (2 pole) or 1800 rev/min (4 pole) to provide power at 60 Hz, or 3000 rev/min (2 pole) or 1500 rev/min (4 pole) to provide power at 50 Hz. Smaller machines may use a laminated construction for the rotor while larger machines will use a forged rotor. A feature of these machines is that their length is several times their diameter. Power outputs range from a few megawatts up to about 1500MW. b) Excitation schemes: Any electric generators or motors consists of a rotor spinning in a magnetic eld. The magnetic eld can be generated by permanent magnets or by eld coils. In the case of a machine with eld coils, current must ow in the coils to generate the eld. This is to ensure power transfer to take place, in or out of the rotor. The process of generating a magnetic eld via means of an electric current is called excitation. Mainly two types of excitation schemes are used in the power stations: 1. Separate excitation: For large or older generators, it is usual for a separate exciter dynamo to be operated in conjunction with the main power generator. It is a small permanent-magnet or battery- excited dynamo that produces the eld current for the larger generator. 10
  • 11. Figure 6: Circuit of separately excited generator 2. Self excitation: Modern generators with eld coils are self-excited. Some of the power output from the rotor is used to power the eld coils. The magnetism is retained by the rotor iron even after the generator is turned o. The generator is initially started with no load connected to it. The initial weak eld creates a weak voltage in the stator coils, which in turn increases the eld current, until the machine shoots to full voltage. Figure 7: Circuit of self excited generator 11