Document Ares(2018)3524555

COMMISSION REGULATION (EU) …/… implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for servers and data storage products and amending Commission Regulation (EU) No 617/2013

Please be aware that this draft act does not constitute the final position of the institution.

COMMISSION REGULATION (EU) …/…

of XXX

implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for servers and data storage products and amending Commission Regulation (EU) No 617/2013

(Text with EEA relevance)

THE EUROPEAN COMMISSION,

Having regard to the Treaty on the Functioning of the European Union,

Having regard to Directive 2009/125/EC of the European Parliament and of the Council of 21 October 2009 establishing a framework for the setting of ecodesign requirements for energy-related products 1 , and in particular Article 15(1) thereof,

After consulting the Consultation Forum referred to in Article 18 of Directive 2009/125/EC,

Whereas:

(1)Directive 2009/125/EC requires the Commission to set ecodesign requirements for energy-related products that represent significant volumes of sales and trade, that have a significant environmental impact and that present significant potential for improvement in terms of their environmental impact without entailing excessive costs.

(2)The Commission has carried out a preparatory study to analyse the technical, environmental and economic aspects of servers and data storage products typically used for commercial purposes. The study has been carried out with stakeholders and interested parties from the Union and third countries, and the results have been made publicly available. 

(3)Servers and data storage products are typically placed on the market for use in data centres, office and corporate environments.

(4)The environmental aspects of servers and data storage products that have been identified as significant for the purposes of this Regulation are energy consumption in the use phase and resource efficiency, in particular on the aspects related to repairability, reusability, upgradeability and recyclability for security of supply.

(5)Ecodesign requirements should harmonise energy consumption and resource efficiency requirements for servers and data storage products throughout the Union, for the internal market to operate better and in order to improve the environmental performance of those products.

(6)The annual energy consumption related to servers directly is expected to be 48 TWh in 2030, which increases to 75 TWh when the annual energy consumption related to infrastructure (e.g. cooling systems and uninterruptible power supply systems) is also included. The annual energy consumption of data storage products is expected to be 30 TWh in 2030, 47 TWh when infrastructure is also included. The preparatory study shows that use-phase energy consumption by servers and data storage products can be significantly reduced.

(7)The effect of the ecodesign requirements set out in this Regulation is estimated to result by 2030 in annual energy savings of approximately 9 TWh (approximately the yearly electricity consumption of Estonia in 2014). More in detail, the effect of the ecodesign requirements for servers set out in this Regulation is estimated to result by 2030 in direct annual energy savings of approximately 2.4 TWh and indirect (i.e. related to infrastructure) annual energy savings of 3.7 TWh, summing up to a total saving of 6.1 TWh, corresponding to a total of 2.1 Mt of CO2 equivalent. The effect of the ecodesign requirements for data storage products set out in this Regulation is estimated to result by 2030 in direct annual energy savings of approximately 0.8 TWh and indirect (i.e. related to infrastructure) annual energy savings of 2 TWh, summing up to a total saving of 2.8 TWh, corresponding to 0.9 Mt of CO2 equivalent.

(8)In accordance with the Union action plan for the Circular Economy 2  the Commission should make sure that special emphasis is placed on aspects relevant to the circular economy, such as durability and reparability, when setting out or revising ecodesign criteria. Therefore requirements should be laid down on non-energy related aspects, including extraction of key-components and of critical raw materials (CRMs), availability of built-in functionality for secure data deletion and provision of latest available version of firmware.

(9)The requirement on the extraction of key-components is expected to foster the reparability and upgradability of servers and data storage products, in particular by third parties (such as spare parts repairers and maintenance).

(10)The possibility to address CRMs in Ecodesign regulations (including for enterprise servers) has been mentioned in the recent Commission Staff Working Document ‘Report on Critical Raw Materials and the Circular Economy’ 3 .

(11)The requirement on a built-in functionality for secure data deletion could be implemented by means of technical solutions such as, but not limited to, a functionality implemented in firmware, typically in the Basic Input/Output System (BIOS), in software included in a self-contained bootable environment provided in a bootable compact disc, digital versatile disc or universal serial bus memory storage device included with the product, or in software installable in the supported operating systems provided with the product.

(12)The requirements on non-energy related aspects are expected to contribute prolonging the lifetime of servers by making it easier to refurbish and reuse them, while maintaining compliance with the principles of privacy and protection of personal data as set by Regulation (EU) 2016/679 of the European Parliament and of the Council 4 .

(13)The energy consumption of servers and data storage products could be reduced by applying existing non-proprietary technologies without an increase in the combined costs of purchasing and operating these products.

(14)The ecodesign requirements should not affect the functionality or affordability of servers and data storage products from the end-user’s perspective and should not negatively affect health, safety or the environment.

(15)This Regulation should apply without prejudice to the requirements of Union legislation on safety and health, in particular the Directive 2014/35/EU of the European Parliament and of the Council 5 , which covers all health and safety risks of electrical equipment operating with a voltage between 50 and 1000 V for alternating current and between 75 and 1500 V for direct current.

(16)The introduction of ecodesign requirements should give manufacturers sufficient time to redesign their products subject to this Regulation. The timing should take into account the impact on manufacturers’ costs, in particular for small and medium-sized enterprises, while ensuring timely achievement of the objectives of this Regulation.

(17)Product parameters should be measured and calculated using reliable, accurate and reproducible methods which take into account recognised state-of-the-art measurement and calculation methods, including, where available, harmonised standards adopted by the European standardisation organisations following a request by the Commission, in accordance with the procedures laid down in Regulation (EU) No 1025/2012 of the European Parliament and of the Council 6 .

(18)In accordance with Article 8 of Directive 2009/125/EC, this Regulation specifies which conformity assessment procedures apply.

(19)In order to facilitate compliance checks, manufacturers should provide the information contained in the technical documentation referred to in Annexes IV and V to Directive 2009/125/EC insofar as that information relates to the requirements laid down in this Regulation.

(20)In addition to the legally binding requirements laid down in this Regulation, indicative benchmarks for best available technologies should be determined to ensure that information on the life-cycle environmental performance of servers and data storage products is widely available and easily accessible.

(21)Commission Regulation (EU) No 617/2013 7 , should be amended to exclude computer servers from its scope in order to prevent any overlap with the same products in the scope of this Regulation.

(22)The measures provided for in this Regulation are in accordance with the opinion of the Committee established under Article 19(1) of Directive 2009/125/EC

(23)The definitions of this Regulation related to data storage products are consistent with the terminology developed by the Storage Networking Industry Association (SNIA) Green Storage Initiative as defined in the SNIA Emerald taxonomy.

(24)In particular, the small data storage products definition corresponds to the online 1 equipment as set out in the SNIA Emerald taxonomy, and the large data storage products definition corresponds to the online 5 and 6 equipment as set out in the SNIA Emerald taxonomy.

(25)The definitions of this Regulation related to servers, among which the ones related to server efficiency and server performance, are consistent with the terminology adopted in EN 303 470:2018.

(26)The operating conditions classes, and their characteristics, are consistent with the classification set in the Thermal Guidelines for Data Processing Environments by the American Society of Heating, Refrigerating and Air-Conditioning Engineers. In particular, the boundary conditions of each operating class (such as temperature and humidity) are in accord with the allowable environmental ranges of the Thermal Guidelines for Data Processing Environments, where manufacturers test their equipment in order to verify that it will function within those boundaries,

HAS ADOPTED THIS REGULATION:

Article 1
Subject matter and scope

1.This Regulation establishes ecodesign requirements for placing on the market and putting into service of servers and online data storage products.

2.This Regulation shall not apply to the following products:

(a)servers intended for embedded applications;

(b)servers classified as small scale servers in terms of Regulation (EU) No 617/2013;

(c)servers with more than four processor sockets;

(d)server appliances;

(e)large servers;

(f)fully fault tolerant servers;

(g)network servers;

(h)small data storage products;

(i)large data storage products.

Article 2
Definitions

1.For the purposes of this Regulation, the following definitions shall apply:

(1)‘server’ means a computing product that provides services and manages networked resources for client devices, such as desktop computers, notebook computers, desktop thin clients, internet protocol telephones, smartphones, tablets, tele-communication, automated systems or other servers, primarily accessed via network connections, and not through direct user input devices, such as a keyboard or a mousea and with the following characteristics:

(a)it is designed to support server operating systems (OS) and/or hypervisors, and targeted to run user-installed enterprise applications;

(b)it supports error-correcting code and/or buffered memory (including both buffered dual in-line memory modules and buffered on board configurations);

(c)all processors have access to shared system memory and are independently visible to a single OS or hypervisor;

(1)‘server with more than four processor sockets’ means a server containing more than four interfaces designed for the installation of a processor; 

(2)'embedded application' means a software application that permanently resides in an industrial or consumer device, typically stored in a non-volatile memory such as read-only memory or flash memory;

(3)'server appliance' means a server that is not intended to execute user-supplied software, delivers services through one or more networks, is typically managed through a web or command line interface and is bundled with a pre-installed OS and application software that is used to perform a dedicated function or set of tightly coupled functions.;

(4)'resilient server' means a server designed with extensive reliability, availability, serviceability and scalability features integrated in the micro architecture of the system, central processing unit (CPU) and chipset;

(5)‘large server’ means a resilient server which ships as a pre-integrated/pre-tested system housed in one or more full frame racks and that includes a high connectivity input/output subsystem with a minimum of 32 dedicated input/output slots; 

(6)'fully fault tolerant server' means a server that is designed with complete hardware redundancy (to simultaneously and repetitively run a single workload for continuous availability in mission critical applications), in which every computing component is replicated between two nodes running identical and concurrent workloads (i.e., if one node fails or needs repair, the second node can run the workload alone to avoid downtime);

(7)'network server' means a network product which contains the same components as a server in addition to more than 11 network port with a total line rate throughput of 12 Gb/s or more, the capability to dynamically reconfigure ports and speed and support for a virtualized network environment through a software defined network; 

(8)‘data storage product' means a fully-functional storage system that supplies data storage services to clients and devices attached directly or through a network. Components and subsystems that are an integral part of the data storage product architecture (e.g., to provide internal communications between controllers and disks) are considered to be part of the data storage product. In contrast, components that are normally associated with a storage environment at the data centre level (e.g. devices required for operation of an external storage area network) are not considered to be part of the data storage product. A data storage product may be composed of integrated storage controllers, data storage devices, embedded network elements, software, and other devices;

(9)'Hard Disk Drive' (HDD) means a data storage device which reads and writes to one or more rotating magnetic disk platters;

(10)'Solid State Drive' (SSD) means a data storage device that reads and writes to non-volatile solid state memory instead of rotating magnetic platters for data storage;

(11)‘data storage device’ means HDDs, SSDs, tapes cartridges, and any other mechanisms providing non-volatile data storage, with the exception of aggregating storage elements such as subsystems of redundant arrays of independent disks, robotic tape libraries, filers, and file servers and storage devices which are not directly accessible by end-user application programs, and are instead employed as a form of internal cache;

(12)‘online data storage product' means a data storage product designed for online, random-access of data, accessible in a random or sequential pattern, with a maximum time to first data of an online data storage product less than 80 milliseconds;

(13)'small data storage product' means a data storage product intended for domestic use containing a maximum of four data storage devices; 

(14)'large data storage product' means a high end or mainframe data storage product that supports more than 400 data storage devices in its maximum configuration and with the following required attributes: no single point of failure, non-disruptive serviceability and integrated storage controller. 

2.For the purposes of Annexes II to V, additional definitions are set out in Annex I.

Article 3
Ecodesign requirements and timetable

1.The ecodesign requirements for servers and online data storage products are set out in Annex II.

2.From 1 March 2020 servers shall comply with the ecodesign requirements set out in Annex II points 1.1.1, 1.2.1, 1.2.2, 2.1, 3.1, 3.3 and 3.4.

3.From 1 March 2020 online data storage products shall comply with the ecodesign requirements set out in Annex II points 1.1.1, 1.2.1, 1.2.2, 3.2, 3.3 and 3.4.

(a)From 1 March 2021 servers and online data storage products shall comply with the ecodesign requirement set out in Annex II point 1.2.3.

(b)From 1 January 2023 servers and online data storage products shall comply with the ecodesign requirements set out in Annex II point 1.1.2.

(c)From 1 January 2026 servers and online data storage products shall comply with the ecodesign requirements set out in Annex II point 1.1.3.

(d)Compliance with ecodesign requirements shall be measured and calculated in accordance with the methods set out in Annex III.

Article 4
Conformity assessment

1.The conformity assessment procedure referred to in Article 8(2) of Directive 2009/125/EC shall be the internal design control set out in Annex IV to that Directive or the management system set out in Annex V to that Directive.

2.For the purposes of the conformity assessment pursuant to Article 8 of Directive 2009/125/EC, the technical documentation shall contain the information set out in point 3.4 of Annex II to this Regulation.

Article 5
Verification procedure for market surveillance purposes

The authorities of the Member States shall apply the verification procedure set out in Annex IV to this Regulation when performing the market surveillance checks referred to in Article 3(2) of Directive 2009/125/EC.

Article 6
Indicative benchmarks

The indicative benchmarks for best-performing servers and data storage products available on the market on [OP – please insert the date of entry into force of this Regulation] are set out in Annex V.

Article 7
Review 

The Commission shall review this Regulation in the light of technological progress and present the result of that review to the Consultation Forum by 1 March 2023. In particular, the review shall assess whether:

(a)it is appropriate to set specific ecodesign requirements on server efficiency, performance and power demand;

(b)it is still appropriate to set specific ecodesign requirements for servers on idle state power;

(c)it is necessary to update the definitions or the scope of the Regulation;

(d)it is appropriate to set specific ecodesign requirements on the operating condition class;

(e)it is appropriate to set specific ecodesign requirements on the efficiency, performance and power demand of data storage products. 

Article 8
Amendment to Regulation (EU) No 617/2013

Regulation (EU) No 617/2013 is amended as follows:

1.Article 1 is amended as follows:

(a)paragraph 1 is replaced by the following: "1. This Regulation establishes ecodesign requirements for the placing on the market of computers.",

(b)in paragraph 2, point (h) is deleted,

(c)in paragraph 3, points (a) to (d)are deleted;

2.Article 2 is amended as follows:

(a)point 2 is deleted,

(b)point 4 is replaced by the following:"(4) ‘Internal power supply’ means a component designed to convert AC voltage from the mains to DC voltage(s) for the purpose of powering the computer and has the following characteristics:

(a)is contained within the computer casing but is separate from the main computer board;

(b)the power supply connects to the mains through a single cable with no intermediate circuitry between the power supply and the mains power; and

(c)all power connections from the power supply to the computer components, with the exception of a DC connection to a display in an integrated desktop computer, are internal to the computer casing.

Internal DC-to-DC converters used to convert a single DC voltage from an external power supply into multiple voltages for use by a computer are not considered internal power supplies;",

(c)points 11 to 16 are deleted,

(d)point 22 is replaced by the following: "(22) ‘Product type’ means desktop computer, integrated desktop computer, notebook computer, desktop thin client, workstation, mobile workstation, small-scale server, game console, docking station, internal power supply or external power supply;"

3.Article 3 is replaced by the following: "Article 3

Ecodesign requirements

The ecodesign requirements for computers are set out in Annex II.

Compliance of computers with the applicable ecodesign requirements shall be measured in accordance with the methods set out in Annex III.";

4.in Article 7, the second paragraph is replaced by the following: "Checking of computers for compliance with the applicable ecodesign requirements shall be carried out in accordance with the verification procedure set out in point 2 of Annex III to this Regulation.";

5.Annex II is amended as follows:

(a)point 5.2 is deleted,

(b)the title of point 7.3 is replaced by the following: "Workstation, mobile workstation, desktop thin client and small-scale server".

Article 9
Entry into force

This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union.

However, Article 8 shall apply from 1 March 2020.

This Regulation shall be binding in its entirety and directly applicable in all Member States.

Done at Brussels,

   For the Commission

   The President
   Jean-Claude JUNCKER    

(1)    OJ L 285, 31.10.2009, p. 10.
(2)    COM(2015) 614 final.
(3)    Regulation (EU) 2016/679 of the European Parliament and of the Council of 27 April 2016 on the protection of natural persons with regard to the processing of personal data and on the free movement of such data, and repealing Directive 95/46/EC (General Data Protection Regulation) (OJ L 119, 4.5.2016, p. 1).
(4)    Regulation (EU) 2016/679 of the European Parliament and of the Council of 27 April 2016 on the protection of natural persons with regard to the processing of personal data and on the free movement of such data, and repealing Directive 95/46/EC (General Data Protection Regulation) (OJ L 119, 4.5.2016, p. 1).
(5)    Directive 2014/35/EU of the European Parliament and of the Council of 26 February 2014 on the harmonisation of the laws of the Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits (OJ L 96, 29.3.2014, p. 357).
(6)    Regulation (EU) No 1025/2012 of the European Parliament and of the Council of 25 October 2012 on European standardisation, amending Council Directives 89/686/EEC and 93/15/EEC and Directives 94/9/EC, 94/25/EC, 95/16/EC, 97/23/EC, 98/34/EC, 2004/22/EC, 2007/23/EC, 2009/23/EC and 2009/105/EC of the European Parliament and of the Council and repealing Council Decision 87/95/EEC and Decision No 1673/2006/EC of the European Parliament and of the Council (OJ L 316, 14.11.2012, p. 12).
(7)    Commission Regulation (EU) No 617/2013 of 26 June 2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for computers and computer servers (OJ L 175, 27.6.2013, p. 13).
Top

ANNEX I
Definitions applicable to Annexes II to V

For the purposes of Annexes II to VI the following definitions shall apply:

(1)'server with one or two processor sockets' means a server containing one or two interfaces designed for the installation of a processor;

(2)‘Input/Output (I/O) device’ means a device, which provides data input and output capability between a server or a data storage product and other devices. An I/O device may be integral to the server motherboard or may be connected to the motherboard via expansion slots (such as Peripheral Component Interconnect, or Peripheral Component Interconnect Express); 

(3)‘motherboard’ means the main circuit board of the server. For purposes of this regulation, the motherboard includes connectors for attaching additional boards and typically includes the following components: processor, memory, BIOS, and expansion slots;

(4)‘processor’ means the logic circuitry that responds to and processes the basic instructions that drive a server. For purposes of this regulation, the processor is the CPU of the server. A typical CPU is a physical package to be installed on the server motherboard via a socket or direct solder attachment. The CPU package may include one or more processor cores;

(5)‘memory’ means a part of a server external to the processor in which information is stored for immediate use by the processor;

(6)'expansion card' means an internal component connected by an edge connection over a common/standard interface such as Peripheral Component Interconnect Express providing additional functionality. It does not include CPUs, random access memory (RAM) or storage modules;

(7)'graphics card' means an expansion card containing one or more graphics processing units with a local memory controller interface and local graphics-specific memory;

(8)'buffered double data rate (DDR) channel' means a channel or memory port connecting a memory controller to a defined number of memory devices in a server. A typical server may contain multiple memory controllers, which may in turn support one or more buffered DDR channels. As such, each buffered DDR channel serves only a fraction of the total addressable memory space in a server;

(9)'blade server' means a server that is designed for use in a blade chassis. A blade server is a high-density device that functions as an independent server and includes at least one processor and system memory, but is dependent upon shared blade chassis resources (e.g., power supplies, cooling) for operation. A processor or memory module that is intended to scale up a standalone server is not considered a blade server;

(10)'blade chassis' means an enclosure that contains shared resources for the operation of blade servers, blade storage, and other blade form-factor devices. Shared resources provided by a chassis may include power supplies, data storage, and hardware for direct current power distribution, thermal management, system management, and network services;

(11)'multi-node server' means a server that is designed with two or more independent server nodes that share a single enclosure and one or more power supplies. In a multi-node server, power is distributed to all nodes through shared power supplies. Server nodes in a multi-node server are not designed to be hot-swappable;

(12)''High Performance Computing (HPC) server' means a server which is designed and optimized to execute highly parallel applications, for higher performance computing or deep learning artificial intelligence applications. HPC servers must meet all the following criteria:

(a)they consist of multiple computing nodes, clustered primarily to increase computational capability;

(b)they include high speed inter-processing interconnections between nodes;

(13)'server product family' means a high-level description referring to a group of servers sharing one chassis and motherboard combination that may contain more hardware and software configurations. All configurations within a family must share the following common attributes:

(a)be from the same model line or machine type;

(b)either share the same form factor (i.e., rack-mounted, blade, pedestal) or share the same mechanical and electrical designs with only superficial mechanical differences to enable a design to support multiple form factors;

(c)either share processors from a single defined processor series or share processors that plug into a common socket type;

(d)share the power supply unit(s); 

(14)'power supply unit' (PSU) means a device that converts alternate current (AC) or direct current (DC) input power to one or more DC power outputs for the purpose of powering a server or a data storage product. A server or data storage product PSU must be self-contained and physically separable from the motherboard and must connect to the system via a removable or hard-wired electrical connection;

(15)‘power factor’ means the ratio of the real power consumed in Watts to the apparent, or reactive, power drawn in volt amperes; 

(16)'single output PSU' means a PSU designed to deliver the majority of its rated output power to one primary DC output for the purpose of powering a server or a data storage product. Single output PSUs may offer one or more standby outputs that remain active whenever connected to an input power source. The total rated power output from any additional PSU outputs that are not primary and standby outputs shall be no greater than 20 Watts. PSUs that offer multiple outputs at the same voltage as the primary output are considered single-output PSUs unless those outputs:

(a)(a)    are generated from separate converters or have separate output rectification stages, or

(b)(b)    have independent current limits;

(17)‘multi output PSU’ means a PSU designed to deliver the majority of its rated output power to more than one primary dc output for the purpose of powering a server or a data storage product. Multioutput PSUs may offer one or more standby outputs that remain active whenever connected to an input power source. The total rated power output from any additional PSU outputs that are not primary and standby outputs is greater than or equal to 20 Watts;

(18)'direct current server' means a server that is designed solely to operate on a DC power source;

(19)'direct current data storage product' means a data storage product that is designed solely to operate on a DC power source;

(20)‘idle state’ means the operational state in which the OS and other software have completed loading, the server is capable of completing workload transactions, but no active workload transactions are requested or pending by the system (i.e., the server is operational, but not performing any useful work);

(21)'idle state power' (Pidle) is the power demand, in Watts, in idle state; 

(22)‘low-end performance configuration’ of a server product family means the combination of two data storage devices, processor with the lowest product of core count and frequency (in GHz) and memory capacity (in GB) is equal to the product of the number of memory slots and the lowest capacity DIMM (in GB) offered on the server that represents the lowest performance product model within the product family;

(23)‘high-end performance configuration’ of a server product family means the combination of two data storage devices, processor with the highest product of core count and frequency and memory capacity (in GB) equal to or greater than 3 times the product of the number of CPUs, cores and hardware threads that represents the highest performance product model within the product family;

(24)'hardware thread': means the hardware resources in a CPU core to execute a stream of software instructions. A CPU core may have the resources to execute more than one thread simultaneously;

(25)'server efficiency' means the ratio between server performance and server power demand in active state;

(26)'active state' means the operational state in which the server is carrying out work in response to prior or concurrent external requests (e.g., instruction over the network). Active state includes both active processing and data seeking/retrieval from memory, cache, or internal/external storage while awaiting further input over the network;

(27)'server performance' means the number of transactions per unit of time performed by the server under standardised testing of discrete system components (e.g. processors, memory and storage) and subsystems (e.g. RAM and CPU);

(28)'CPU performance (CPUperf)' means the number of transactions per unit of time performed by the server under standardised testing of the CPU subsystem;

(29)'Auxiliary Processing Accelerator' (APA) means a specialized processor and associated subsystem that provide an increase in computing capacity such as graphical processing units or field programmable gate arrays. An APA cannot operate in a server without a CPU. APAs can be installed in a server either on Graphics or Extension add-in cards installed in general-purpose add-in expansion slots or integrated into a server component such as the motherboard;

(30)'Expansion APA' means an APA that is on an add-in card installed in an add-in expansion slot. An expansion APA add-in card may include one or more APAs; 

(31)'Integrated APA' means an APA that is integrated into the motherboard or CPU package; 

(32)'product type' means the design of the server or of the data storage product including the chassis (rack, tower or blade), the number of sockets and, for servers, whether it is a resilient server, a blade server, a multi node server, a HPC server, a server with integrated APA, a direct current server or none of the previous categories;

(33)'disassembly' means a process whereby an item is taken apart in such a way that it could subsequently be reassembled and made operational; 

(34)‘firmware’ means system, hardware, component, or peripheral programming provided with the product to provide basic instructions for hardware to function inclusive of all applicable programming and hardware updates;

(35)‘secure data deletion’ means the effective erasure of all traces of existing data from a data storage device, overwriting the data completely in such a way that access to the original data, or parts of them, becomes infeasible for a given level of effort; 

(36)'built-in functionality' means a functionality that does not require the installation or usage of additional software or hardware components not already present in the server or data storage product.



ANNEX II
Ecodesign requirements

1.Specific ecodesign requirements for servers and online data storage products

1.1.PSU efficiency and power factor requirements

1.1.1.From 1 March 2020, for servers and online data storage products, with the exception of direct current servers and of direct current data storage products, the internal PSU efficiency at 10%, 20%, 50% and 100% rated load level and the power factor at 50% rated load level shall not be less than the values reported in Table 1.

Table 1 Minimum PSU efficiency and power factor requirements from 1 March 2020

Minimum PSU efficiency

Minimum power factor

% of rated load

10%

20%

50%

100%

50%

Multi output

-

88%

92%

88%

0.90

Single output

-

90%

94%

91%

0.95

1.1.2.From 1 January 2023, for servers and online data storage products, with the exception of direct current servers and of direct current data storage products, the internal PSU efficiency at 20%, 50% and 100% rated load level and the power factor at 50% rated load level shall not be less than the values reported in Table 2.

Table 2 Minimum PSU efficiency and power factor requirements from 1 January 2023

Minimum PSU efficiency

Minimum power factor

% of rated load

10%

20%

50%

100%

50%

Multi output

-

90%

94%

91%

0.95

Single output

90%

94%

96%

91%

0.95

1.1.3.From 1 January 2026, for servers and online data storage products, with the exception of direct current servers and of direct current data storage products,  the internal PSU efficiency at 20%, 50% and 100% rated load level and the power factor at 50% rated load level shall not be less than the values reported in Table 3:

Table 3 Minimum PSU efficiency and power factor requirements from 1 January 2026

Minimum PSU efficiency

Minimum power factor

% of rated load

10%

20%

50%

100%

20%

Multi output

90%

94%

96%

91%

0.95

Single output

90%

94%

96%

91%

0.95

1.2.Material efficiency requirements

1.2.1.From 1 March 2020, manufacturers shall ensure that joining, fastening or sealing techniques do not prevent the disassembly of the following components, when present:

(a)data storage devices;

(b)memory;

(c)processor (CPU);

(d)motherboard;

(e)expansion card/graphic card;

(f)power supply.

1.2.2.From 1 March 2020, a built-in functionality for secure data deletion shall be made available for the deletion of data contained in all the data storage devices of the product.

1.2.3.From 1 March 2021, the latest available version of the firmware shall be made available for a minimum period of eight years after the placing on the market of the product, at a fair, transparent and non-discriminatory cost.

2.Specific ecodesign requirements only for servers with one or two processor sockets

2.1.Idle state power

From 1 March 2020, the idle state power (Pidle) of servers, with the exception of resilient servers, HPC servers and servers with integrated APA, shall not exceed the value calculated using the following equation:

Pidle = Pbase+Padd_i

where Pbase is the basic idle state power allowance in Table 4, and Padd_i is the idle state power allowance for additional components, as determined per Table 5. For blade servers, Pidle is calculated as the total measured power divided by the number of installed blade servers in the tested blade chassis. For multi-node servers, Pidle is calculated as the total measured power divided by the number of installed nodes in the tested enclosure.

Table 4 Base idle state power allowances

Product type

Base idle state power allowance, Pbase (W)

1-socket servers

25

2-socket servers

38

Blade or multi-node servers

40

Table 5 Additional Idle Power Allowances for Extra Components

System characteristics

Applies to

Additional idle power allowance

CPU Performance

All servers

1 socket: 10 × CPUperf W

2 socket: 7 × CPUperf W

Additional power supplies

Power supplies installed explicitly for power redundancy

10 W per power supply

Drives (HDD or SSD)

Per installed HDD and SSD

4.0 W per HDD and SSD

Additional memory

Installed memory greater than 4 GB

0.12 W per GB

Additional buffered DDR channel

Installed buffered DDR channels greater than 8 channels

4.0 W per buffered DDR channel

Additional I/O devices

Installed devices greater than two ports of ≥ 1 Gbit, onboard Ethernet

< 1 Gb/s: No Allowance

= 1 Gb/s: 2.0 W / Active Port

> 1 Gb/s and < 10 Gb/s: 4.0 W/ Active Port

≥ 10 Gb/s and <25Gb/s: 15.0 W/Active Port

≥ 25 Gb/s and <50Gb/s: 20.0 W/Active Port

≥ 50 Gb/s 26.0 W/Active Port

3.Information to be provided by manufacturers

3.1.From 1 March 2020, the following product information on servers shall be provided in the instruction manuals for installers and end-users, and on the free-access websites of manufacturers, their authorised representatives and importers:

(a)product type;

(b)manufacturer’s name, registered trade name and registered trade address at which they can be contacted;

(c)product model number;

(d)year of manufacture;

(e)internal power supply efficiency at 10 %, 20 %, 50 % and 100 % of rated output power;

(f)power factor at 50% of rated load level, power factor at 20% of rated load level from 1 January 2026

(g)PSU rated power output (Watts);

(h)idle state power (Watts); 

(i)list of components for additional idle power allowances, if any (additional power supplies, drives, additional memory, additional buffered DDR channels, additional I/O devices);

(j)maximum power demand (Watts);

(k)declared operating condition class, as detailed in Table 6;

(l)idle state power (Watts) at the higher boundary temperature of the declared operating condition class;

(m)the server efficiency and server performance in active state, with the exception of HPC servers and servers with integrated APA;

(n)information on the secure data deletion built-in functionality referred to in point 1.2.2 of this Annex, including instructions on how to use the functionality, the techniques used and the supported secure data deletion standard(s), if any;

(o)if a product model is part of a server product family, a list of all model configurations that are represented by the model can be supplied.

If a product model is part of a server product family, the product information required for items g) to k) under point 3.1 shall be reported either for the product model or, alternatively, for the low-end and high-end configurations of the server product family.

3.2.From 1 March 2020, the following product information on online data storage products shall be provided in the instruction manuals for installers and end-users, and on the free-access websites of manufacturers, their authorised representatives and importers:

(a)product type;

(b)manufacturer’s name, registered trade name and registered trade address at which they can be contacted;

(c)product model number;

(d)year of manufacture;

(e)internal power supply efficiency at 10 %, 20 %, 50 % and 100 % of rated output power;

(f)power factor at 50% of rated load level, power factor at 20% of rated load level from 1 January 2026;

(g)declared operating condition class, as detailed in Table 6; it shall also be indicated that 'This product has been tested in order to verify that it will function within the boundaries (such as temperature and humidity) of the declared operating condition class';

(h)information on the data deletions tool(s) referred to in point 1.2.2 of this Annex, including instructions on how to use the functionality, the techniques used and the supported secure data deletion standard(s), if any.

3.3.From 1 March 2020, the following product information on servers and online data storage products shall be made available free of charge by manufacturers, their authorised representatives and importers to third parties dealing with maintenance, repair, reuse, recycling and upgrading of servers (including brokers, spare parts repairers, spare parts providers, recyclers and third party maintenance) upon registration by the interested third party on a website provided:

(a)weight range (less than 5g, between 5g and 25g, above 25g) at component level, of the following critical raw materials, if any:

(a)Cobalt in the batteries;

(b)Neodymium in the HDDs;

(b)instructions on the disassembly operations referred to in point 1.2.1 of this Annex, including, for each necessary operation and component:

(a)the type of operation;

(b)the type and number of fastening technique(s) to be unlocked;

(c)the tool(s) required.

In the case of servers, if a product model is part of a server product family, the product information required for items a) and b) under point 3.3 shall be reported either for the product model or, alternatively, for the low-end and high-end configurations of the server product family

3.4.From 1 March 2020, the following product information on servers and online data storage products shall be provided in the technical documentation for the purposes of conformity assessment pursuant to Article 4:

(a)Information listed in points 3.1 and 3.3, in the case of servers

(b)Information listed in point 3.2 and 3.3, in the case of data storage products.

Table 6 Operating condition classes

Operating condition class

Dry bulb temp °C

Humidity range, non-condensing

Max dew point (°C)

Maximum rate of change (°C/hr)

A1

15- 32

–12°C DP and 8% RH to

17°C DP and 80% RH

17

5/20

A2

10-35

20% - 80% RH

21

5/20

A3

5-40

-12°C DP and 8% RH to 85% RH

24

5/20

A4

5-45

–12°C DP and 8% RH to 24°C DP and 90% RH

24

5/20



ANNEX III
Measurements and calculations

1.For the purposes of compliance and verification of compliance with the applicable requirements of this Regulation, measurements and calculations shall be made using harmonised standards, the reference numbers of which have been published in the Official Journal of the European Union, or using other reliable, accurate and reproducible methods which take into account the generally recognised state of the art, and produce results deemed to be of low uncertainty.

2.Servers shall be tested in their configuration declared for Annex II, point 3.1.(i), which includes both hardware configuration and system settings, unless otherwise specified. 

For servers with expansion APA, the unit under test shall be tested with the expansion APA removed, when measuring the idle state power, the server efficiency and the server performance in active state.

For multi-node servers, the unit under test shall be tested for per node power consumption in the fully-populated chassis configuration.

For blade servers, the unit under test shall be tested for blade server power consumption in the half-populated chassis configuration, and the chassis shall be populated as follows:

(1)Individual blade server configuration

(a)All individual blade servers installed in the chassis shall be identical, sharing the same configuration

(2)Half chassis population

(a)The number of blade servers required to populate half the number of single-wide blade server slots available in the blade chassis shall be calculated.

(b)For blade chassis having multiple power domains, the number of power domains that is closest to filling half of the chassis shall be chosen. If there are two choices that are equally close to filling half of the chassis, the test shall be performed with the domain or combination of domains which use a higher number of blade servers.

(c)All user manual or manufacturer recommendations for partially populating the chassis, which may include disconnecting some of the power supplies and cooling fans for the unpopulated power domains, should be followed.

(d)If user manual recommendations are not available or are incomplete, then the following guidance shall be used:

(i)    Completely populate the power domains;

(ii)    If possible, disconnect the power supplies and cooling fans for unpopulated power domains;

(iii)    Fill all empty bays with blanking panels or an equivalent airflow restriction for the duration of testing.



ANNEX IV
Verification procedure for market surveillance purposes

The verification tolerances defined in this Annex relate only to the verification of the measured parameters by Member State authorities and shall not be used by the manufacturer or importer as an allowed tolerance to establish the values in the technical documentation or in interpreting these values with a view to achieving compliance or to communicate better performance by any means.

Where a model has been designed so that a model's performance is automatically altered in test conditions with the objective of reaching a more favourable level for any of the parameters specified in this Regulation or included in the technical documentation provided with the product, the model shall be considered not compliant.

When verifying the compliance of a product model with the requirements laid down in this Regulation pursuant to Article 3(2) of Directive 2009/125/EC, for the requirements referred to in this Annex, the authorities of the Member States shall apply the following procedure:

1.The Member State authorities shall verify one single unit of the model or model configuration.

2.The model or model configuration shall be considered to comply with the applicable requirements if:

(a)the values given in the technical documentation pursuant to point 2 of Annex IV to Directive 2009/125/EC (declared values), and, where applicable, the values used to calculate these values, are not more favourable for the manufacturer or importer than the results of the corresponding measurements carried out pursuant to paragraph (g) thereof; and

(b)the declared values meet any requirements laid down in this Regulation, and any required product information published by the manufacturer or importer does not contain values that are more favourable for the manufacturer or importer than the declared values; and

(c)when the Member State authorities test the unit of the model or model configuration, the determined values (the values of the relevant parameters as measured in testing and the values calculated from these measurements) comply with the respective verification tolerances as given in Table 7.

3.If the results referred to in points 2(a) or 2(b) are not achieved, the model and all model configurations that are covered by the same product information (according to Annex II point 3.1(n)) shall be considered not to comply with this Regulation.

4.If the result referred to in point 2(c) is not achieved:

(a)for models that are produced in quantities of less than five per year, the model and all model configurations that are covered by the same product information (according to Annex II point 3.1(n)) shall be considered not to comply with this Regulation;

(b)for models that are produced in quantities of five or more per year, the Member State authorities shall select three additional units of the same model or model configuration for testing.

5.The model or model configuration shall be considered to comply with the applicable requirements if, for these three units, the arithmetical mean of the determined values complies with the respective verification tolerances given in Table 7.

6.If the result referred to in point 4(b) is not achieved, the model and all model configurations that are covered by the same product information (according to Annex II point 3.1(n)) shall be considered not to comply with this Regulation.

7.The Member State authorities shall provide all relevant information to the authorities of the other Member States and to the Commission without delay after a decision being taken on the non-compliance of the model according to points 3 and 6.

The Member State authorities shall use the measurement and calculation methods set out in Annex III.

The Member State authorities shall only apply the verification tolerances that are set out in Table 7 of this Annex and shall only use the procedure described in points 1 to 7 for the requirements referred to in this Annex. No other tolerances shall be applied.

Table 7— Verification tolerances

Parameters

Verification tolerances

PSU efficiency (%)

The determined value shall not be lower than the declared value by more than 2 %.

Power factor

The determined value shall not be lower than the declared value by more than 10 %.

Idle state power, Pidle (W)

The determined value shall not exceed the declared value by more than 10 %.

Server efficiency

The determined value shall not be lower than the declared value by more than 10 %.



ANNEX V
Indicative benchmarks referred to in Article 6

The following indicative benchmarks are identified for the purpose of Part 3, point 2 of Annex I to Directive 2009/125/EC.

They refer to the best available technology by [OP – please insert the date of entry into force of this Regulation].

The indicative benchmarks for the best available technology on the market for servers and online data storage products are as follows.

Table 8 Benchmark for idle state power, server efficiency and operating condition

Product type

Idle power, W

Server efficiency

Operating condition class

Tower server, 1 socket

24

10

A3

Rack server, 1 socket

50

9

A4

Rack server, 2 socket, low performance

67

11

A4

Rack server, 2 socket, high performance

67

20

A4

Rack server, 4 socket

415

No available data

A4

Blade server, 2 socket

75

15

A3

Blade server, 4 socket

127

No available data

A3

Resilient server, 2 socket

234

No available data

A3

Data storage products

Not applicable

Not applicable

A3

Table 9 Benchmark for PSU efficiency at 10%, 20%, 50% and 100% load level and power factor at 50% load level

PSU nameplate power

10%

20%

50%

100%

< 750W

91.17%

93.76%

94.72%

Power factor >0.95

94.14%

≥ 750W

95.02%

95.99%

Power factor >0.95

96.09%

94.69%